SINLINE XL series UPS – Instruction Manual
2010/01/27
www.ever.eu
31
TECHNICAL PARAMETERS – Rack Model
PARAMETERS
UPS TYPE
SINLINE XL
1800 19’’ Rack 3U
SINLINE XL
2200 19’’ Rack 3U
SINLINE XL
3000 19’’ Rack 3U
Output power
1)
1800VA
1260W
2200VA
1540W
3000VA/
2100W
Working environment
Office or industrial rooms with low level of pollution
Operating temperature
2)
+10 ÷ +35 °C
Storage temperature
0 ÷ +45 °C
Relative humidity for operation
20 ÷ 80 % (without condensation)
Relative humidity for storage
20 ÷ 95 % (without condensation)
Altitude (above sea level)
3)
up to 1000 m
Maximum length of outgoing cables
< 10 m
MAINS OPERATION MODE
Input voltage
4), 5)
~150 ÷ 280 V (~160 ÷ 265 V) ± 2 %
Frequency of input voltage
45 ÷ 55 Hz ± 1 Hz
Range of output voltage
5)
~172 ÷ 280 V (~184 ÷ 265 V) ± 2 %
Switching thresholds: Mains – UPS
4), 5)
~150 ÷170 V (~160 V) / ~255 ÷280 V (~265 V) ± 2 %
Shape of output voltage
Same as input
Filtering of output voltage
Noise filter RFI/EMI varistor damper
Time to switch to UPS
<3 ms
BACK-UP (BATTERY) OPERATION MODE
Output voltage (effective value)
~230 V ± 5 %
Shape of output voltage
Sinus
Switching thresholds: UPS– mains
4), 5)
~155 ÷175 V (~165 V) / ~250 ÷275 V (~260 V) ± 2 %
Frequency of output voltage
50Hz ± 1 Hz
Filtering of output voltage
LC
Shorting safeguard
Electronic
Overload safeguard
Electronic
Time to switch back to mains operation
0 ms
Support time with internal batteries only
(100%/80%/50%P
max
)
7 / 8.5 / 19 min
5 / 7 / 15 min
4 / 5 / 9 min
Support time with battery module installed (
100%/80%/50%P
max
)
28 / 48 / 81 min
25 / 34 / 65 min
17 / 24 / 46 min
Battery
4x VRLA 12V/9 Ah
Additional modules
2x 4x VRLA 12V/9 Ah
Maximum charging time of internal batteries
6)
3 h
Maximum charging time of internal batteries
+ battery module
6)
12 h
MECHANICAL PARAMETERS
Dimensions (h x w x d)
3U x 19’’ × 400 mm
UPS weight
39 kg
Battery module weight
38 kg
EQUIPMENT
Outlet sockets
6 x IEC320 C13
Signalling
Acoustic and visual
Cut-out
Circuit breaker 15 A
Telecommunications filter
Available
LAN filter
Available
Communication interface
RS232, USB, SNMP/HTTP networkmanagement card – optional
Note: The manufacturer reserves the right to change the abovementioned parameters without prior notice.
Notes:
1)
For normal operation of the UPS the load connected to its output should not exceed 80% of value indicated in the table. Reserve power is essential to ensure
continuous operation of connected devices in case of momentary rushes in load current.
2)
Continued exposure of the UPS to the temperature of the surrounding exc25°C will shorten the life of batteries.
3)
If the altitude above sea level increases beyond the provided limit, the permitted load power of the batter back-up decreases.
4)
The User may modify the switching thresholds.
5)
Factory setting is provided in parentheses.
6)
After discharging the UPS with power 80% Pmax, charging the battery to 90% capacity.
Summary of Contents for SINLINE XL 1800