SINLINE series UPS – Instruction Manual
2010/01/26
www.ever.eu
25
TECHNICAL PARAMETERS – Tower Model
PARAMETERS /
UPS TYPE
SINLINE
800
SINLINE
1200
SINLINE
1600
SINLINE
2000
SINLINE
3000
Output power
1)
800VA/
520W
1200VA/
780W
1600VA/
1040W
2000VA/
1300W
3000VA/
1950W
Working environment
Office or industrial rooms with low level of pollution
Operating temperature
2)
+10 ÷ +35 °C
Storage temperature
0 ÷ +45 °C
Relative humidity for operation
20 ÷ 80 % (without condensation)
Relative humidity for storage
20 ÷ 95 % (without condensation)
Altitude (above sea level)
3)
up to 1000 m
Maximum length of outgoing cables
< 10 m
MAINS OPERATION MODE
Input voltage
4)
~160 ÷ 264 V (~145 ÷ 280 V) ± 2 %
Frequency of input voltage
45 ÷ 55 Hz ± 1 Hz
Range of output voltage
4)
~184 ÷ 264 V (~167 ÷ 280 V) ± 2 %
Switching thresholds: mains – UPS
4)
~160 V / ~264 V (~145V / ~280 V) ± 2 %
Shape of output voltage
Sinus
Filtering of output voltage
Noise filter RFI/EMI varistor damper
Time to switch to UPS
<3 ms
BATTERY MODULE (BATTERY) OPERATION MODE
Output voltage (effective value)
~230 V ± 5 %
Shape of output voltage
Sinus
Switching thresholds: UPS – mains
4)
~165 V / ~259 V (~150 V / ~275 V) ± 2 %
Frequency of output voltage
50 Hz ± 1 Hz
Filtering of output voltage
LC
Shorting protection
Electronic
Overload protection
Electronic
Time to switch back to mains operation
0 ms
Support time 100%/80%/50%P
max
5/7/12 min
4,5/6/10 min
4/5/8 min
4/5/9 min
3/4/8 min
Battery
2 x 5 Ah
2 x 7 Ah
3 x 5 Ah
4 x 5 Ah
4 x 7 Ah
Maximum charging time
5 h
7 h
5 h
5 h
7 h
MECHANICAL PARAMETERS
Dimensions (h x w x d) [in mm]
190 × 165 × 480
190 × 165
× 640
Weight
14 kg
16 kg
20 kg
23 kg
28 kg
EQUIPMENT
Number of outlet sockets
4
Signalling
Acoustic and visual (LEDs)
Circuit breaker
Fuse 5x20mm 10 A
Circuit breaker 15 A
Telecommunications filter
Available
Communication interface
RS 232
Note: The manufacturer reserves the right to change the abovementioned parameters without prior notice.
Notes:
1)
For normal operation of the UPS the load connected to its output should not exceed 80% of value indicated in the table.
Reserve power is essential to ensure continuous operation of connected devices in case of momentary rushes in load
current.
2)
Continued exposure of the UPS to the temperature of the surrounding exc25°C will shorten the life of batteries.
3)
If the altitude above sea level increases beyond the provided limit the permitted load power of the batter battery module
decreases.
4)
The user change the switching thresholds by setting standard or enhanced thresholds, respectively
(provided in parentheses)