background image

Instruction manual for the bypass system of the POWERLINE RT PLUS 6-10 kVA units 

 

2020-04-06 13:55 

Technical support

, tel.: +48 61 6500 400 

www.ever.eu

 

Installation diagram symbols: 

Fm, Fsb

 

– Switch fuses, 

Qout, Qsb

 

– Switch disconnectors, 

PP1, PP2, PP3

 

– Emergency power-off (EPO) push-buttons, 

 

Connection wires. 

 

 

The list of safeguards with the wire sizes for the UPS models is shown in a separate 

documentation, "Installation guidelines for the POWERLINE RT PLUS 6-10kVA UPS 

units".  

 

  This UPS has been designed for operation in TN systems 

 

Qsb 

–  Mechanically  locked  in  the  break  position  when 

receivers are powered from the UPS 

 

Keep  the  Fsb  links  outside  of  the  UPS  switching  room  when 

powering the receivers from the UPS. 

  Fsb, Qsb 

– Operated by trained personnel only; Incorrect use may 

damage the UPS 

 
 

Summary of Contents for POWERLINE RT PLUS 6000

Page 1: ......

Page 2: ...s 2020 04 06 13 55 Technical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 OPERATING THE EXTERNAL BYPASS SYSTEM 3 SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE 5 SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER 5 NOTES 6 ...

Page 3: ...on Manual of this UPS before attempting any switching operations CAUTION Only trained personnel may switch power to the external bypass system Switching operations carried out against this procedure may result in damage to the UPS CAUTION Read and understand the Instruction Manual for this UPS before attempting the switching operation OPERATING THE EXTERNAL BYPASS SYSTEM Figure 1 Installation diag...

Page 4: ...ion wires The list of safeguards with the wire sizes for the UPS models is shown in a separate documentation Installation guidelines for the POWERLINE RT PLUS 6 10kVA UPS units This UPS has been designed for operation in TN systems Qsb Mechanically locked in the break position when receivers are powered from the UPS Keep the Fsb links outside of the UPS switching room when powering the receivers f...

Page 5: ... the bypass line 4 Turn on the switch fuse Fsb on the bypass line 5 Turn off the switch disconnector Qout on the UPS output line 6 Turn off the switch fuse Fm on the UPS input line SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER Follow this procedure to switch the isolated mains powered network Fig 1 to the UPS power 1 Make sure that the UPS has been powered off on the logical level 2 Turn on...

Page 6: ...A units 2020 04 06 13 55 Technical support tel 48 61 6500 400 www ever eu 6 CAUTION Once the procedure for restoring the UPS power has been completed secure the disconnectors and fuses on the external bypass line from inadvertent switching on by unauthorised personnel NOTES ...