SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE 

Follow  this  procedure  to  switch  the  isolated  UPS-powered  network  to  the  mains 

power with the external bypass system (Fig. 1): 

1.  Turn off the UPS by pressing the button 

 (the UPS will be powered off on the 

logical level), 

2.  Wait  until  the  UPS  is  turned  off  on  the  logical  level  and  indicates  that  the 

connected receivers are powered via the internal bypass, 

 

3.  Turn on the switch disconnector Qsb on the bypass line, 

4.  Turn on the switch fuse Fsb on the bypass line, 

5.  Turn off the switch disconnector Qout on the UPS output line, 

6.  Turn off the switch fuse Fm on the UPS input line. 

 

SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER 

Follow  this  procedure  to  switch  the  isolated  mains-powered  network  (Fig.  1)  to  the 

UPS power: 

1.  Make sure that the UPS has been powered off on the logical level, 

2.  Turn on the switch fuse Fm on the UPS input line, 

3.  Wait  until  the  UPS  indicates  that  the  connected  receivers  are  powered  via  the 

internal bypass, 

4.  Turn on the switch disconnector Qout on the UPS output line, 

5.  Turn off the switch fuse Fsb on the bypass line, 

6.  Turn off the switch disconnector Qsb on the bypass line, 

7.  Turn  on  the  UPS  by  pressing  button 

  (the  UPS  will  be  powered  on  on  the 

logical level). 

 

 

Summary of Contents for POWERLINE RT PLUS 6000

Page 1: ......

Page 2: ...s 2020 04 06 13 55 Technical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 OPERATING THE EXTERNAL BYPASS SYSTEM 3 SWITCHING FROM THE UPS POWER TO THE MAINS POWER LINE 5 SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER 5 NOTES 6 ...

Page 3: ...on Manual of this UPS before attempting any switching operations CAUTION Only trained personnel may switch power to the external bypass system Switching operations carried out against this procedure may result in damage to the UPS CAUTION Read and understand the Instruction Manual for this UPS before attempting the switching operation OPERATING THE EXTERNAL BYPASS SYSTEM Figure 1 Installation diag...

Page 4: ...ion wires The list of safeguards with the wire sizes for the UPS models is shown in a separate documentation Installation guidelines for the POWERLINE RT PLUS 6 10kVA UPS units This UPS has been designed for operation in TN systems Qsb Mechanically locked in the break position when receivers are powered from the UPS Keep the Fsb links outside of the UPS switching room when powering the receivers f...

Page 5: ... the bypass line 4 Turn on the switch fuse Fsb on the bypass line 5 Turn off the switch disconnector Qout on the UPS output line 6 Turn off the switch fuse Fm on the UPS input line SWITCHING FROM THE MAINS POWER LINE TO THE UPS POWER Follow this procedure to switch the isolated mains powered network Fig 1 to the UPS power 1 Make sure that the UPS has been powered off on the logical level 2 Turn on...

Page 6: ...A units 2020 04 06 13 55 Technical support tel 48 61 6500 400 www ever eu 6 CAUTION Once the procedure for restoring the UPS power has been completed secure the disconnectors and fuses on the external bypass line from inadvertent switching on by unauthorised personnel NOTES ...

Reviews: