ELECTRICAL SYSTEM
Prepare the electrical system according to the diagram shown in Fig. 1.
Figure 1. Installation diagram of the POWERLINE RT PLUS 6-10 kVA UPS
Installation diagram symbols:
Fm, Fsb
– Switch fuses,
Qout, Qsb
– Switch disconnectors,
PP1, PP2, PP3
– Emergency power-off (EPO) push-buttons,
A
–
Connection wires.
The list of safeguards and wire sizes used in specific locations for specific UPS
models is shown in Table 2.
Table 2. Safeguards and wire sizes.
MODEL
Fm
Fsb
Qout
Qsb
A
POWERLINE RT PLUS 6 kVA
32 A gG
32 A gG
32 A
32 A
4 mm
2
POWERLINE RT PLUS 10 kVA
50 A gG
50 A gG
50 A
50 A
10 mm
2