background image

There will be two distinct clicks of relays as it goes through the self-check sequence. These 
relay clicks are the Lite-Minder turning on the output relays to check if any voltages are present 
and then tickling the output with a small voltage to see if short circuits or overloads are 
present.
The faults that are checked for during start-up mode are:

BACKFEED

 – This is when AC voltages are present at any of the outputs. If there are AC 

voltages present at any of the outputs, it means that there is a mis-wire and the utility AC 
power is being back-fed into the inverter. 

ROTATION

 – This fault would occur if the module was replaced and re-connected improperly. 

The Phase Rotation diagnostic energizes the inverter and looks for output voltages out of 
regulation.

BATT LOW 

– This fault would occur if the DC voltage at the power PCB is too low. Possibilities 

for this fault to occur are blown DC fuse on the power PCB,  Battery wiring incorrect or battery 
voltages too low to start the system up without a failure.

OVERLOAD

 – This fault would occur if the connected load exceeds that of the rating of the 

Lite-Minder. This check is performed by tickling the output to a low voltage for one cycle and 
looking for overcurrent faults. This diagnostic features connects all the outputs such as the 
Normally Off and the Switched Output.

MISWIRE

 – This fault would occur if the AC input voltage is not within specification. For 

example if the unit is a 277V model and only 120V was connected, a MISWIRE fault would 
occur. Conversely if a 120V model had 277 VAC connected, a MISWIRE fault would occur. 
Also if no AC voltage was applied to the input, a MISWIRE would occur.

After all the Start-Up diagnostics are performed, the Lite-Minder is OK to proceed to the 
Battery Charging mode.

9.2 

Battery Charging Mode

The Battery Charging mode is where the system will remain for 99.9+ percent of its life. In 
this mode, AC power is being passed through to the units output and subsequently its loads 
and the batteries are keeping a float charge. The charger is floating at 2.27 Volts per Cell (VPC) 
and is temperature compensated to 4mV per deg. C (per cell), centered at 25 degrees C.
For higher temperatures, the float voltage would go down and for lower temperatures, the float 
voltage would go up.
The Lite-Minder nominal DC battery voltage is 24 VDC. The float voltage is 27.2 VDC (2.27 
VPC) and the LVD voltage is 20.5 VDC (1.67 VPC).
Float voltage varies with temperature, LVD voltage is fixed.

Pg. 20

Summary of Contents for Lite-Minder

Page 1: ...g by unauthorized personnel E The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition F Do not use this equipment for other than intended use This unit contain...

Page 2: ...on 5 2 Battery Installation 5 3 DC Voltage of System 6 0 Start up and Shut down procedures 6 1 Start up Procedure 6 2 Shut down Procedure 7 0 Specifications 8 0 User Interface 8 1 Scrolling Display 8...

Page 3: ...ation PWM and the latest MOSFET technology Lite Minder can produce a Pure Sine wave output which is compatible with all types of lighting loads A high crest factor of 4 is extremely beneficial for hig...

Page 4: ...bient temperatures no warmer than 77 F 25 C For storage temperatures greater than 77 F 25 C the batteries must be recharged one 1 month sooner for every 5 F 3 C increase above 77 F 25 C Storage Temper...

Page 5: ...ntly depreciate battery life Heat is the determining factor of battery life Every means should be made to keep the batteries in an environment that keeps the batteries around 25 degrees C for rated ba...

Page 6: ...the Gear Tray forward and lift up while supporting from below disconnect AC Input Output connectors and Installation Switch cable remove 4 screws remove the AC Breaker Terminal Block Assembly Gear Tra...

Page 7: ...1 4 20 bolts No unit dis assembly is required Enclosure Outline Inverter hooks on to plate and is secured by 2x 1 4 20 bolts in battery compartment Plate is fastened to wall or struts hardware suppli...

Page 8: ...tablished At NO time is drilling allowed into the cabinet Drilling causes metal filings to be deposited on surfaces and could land on the Printed Circuit Boards and cause short circuits WARNING Drilli...

Page 9: ...ersonal protective equipment PPE that is suitable such as eye protection when working near batteries 4 1 Removing the Top Cover All the connections for the AC input and output are located on the top r...

Page 10: ...iver NOTE AC Input and AC output wires must be run in separate conduit or raceways per NEC ARTICLE 700 Please ensure all codes and standards are observed NOTE Lite Minder requires that the Neutral and...

Page 11: ...INPUT CONNECTIONS GROUND BAR POWER PCB CONNECTIONS OPTIONAL SUMMARY ALARM CONNECTIONS WIRE PORTS Note Up to three output circuit breakers can be mounted on the terminal block rail Standard AC Input Ou...

Page 12: ...y mounted and secured in a permanent location with all conduit and AC wiring connected 5 1 Battery Inspection Inspect the batteries for any physical damage such as cracks or any other sign of leaking...

Page 13: ...afe manor to accomplish the system buss requirements NOTE Battery potential has galvanic isolation from AC potential Any battery voltage measurements must be made with both meter leads connected to th...

Page 14: ...ess the Test button on the front panel to verify that the normally off and switched output loads are all operational and again measure currents If alarms occur during start up see section 8 3 for poss...

Page 15: ...THD Crest Factor 4 for 525W model 6 5 for 325W model Load Power Factor 0 5 lead to 0 5 lag Protection Optional circuit breakers Output Types Normally On Normally Off and Switched Output Battery Type V...

Page 16: ...ht arrow in the scrolling display mode will advance or retard the scroll Pressing Escape in any of the Sub Menu s will retard back one menu level Pressing Escape multiple times will always return the...

Page 17: ...connected MIS WIRE This indicates there is lack of AC power at the input BATT LOW This indicates that the Batter Voltage is too low to start the unit up Possible fault is that the battery is mis wire...

Page 18: ...ndicate how deep the battery was discharged and if it correlates to a healthy battery The largest benefit of the log though is to keep record of tests and events for Safety Inspectors so they can see...

Page 19: ...up to the maximum output current capability of the Lite Minder To change this value press ENTER at this menu and then there will be a display capable of scrolling with the right arrow key that will r...

Page 20: ...ed by tickling the output to a low voltage for one cycle and looking for overcurrent faults This diagnostic features connects all the outputs such as the Normally Off and the Switched Output MISWIRE T...

Page 21: ...Power mode the inverter is producing a pure sine wave for the output loads and the batteries are being discharged The output current is limited by an active pulse by pulse current limit technique and...

Page 22: ...Warranty Duration Pure Lead 7 years full 13 years pro rata High Rate 3 years full 7 years pro rata Standard VRLA 1 year full 9 years pro rata Extended Warranty is available through a factory start up...

Page 23: ...of the logs will see how the unit is performing A quick test by manually pressing the test button will transfer the system to Battery Power and will turn on all the connected loads such as the Normall...

Page 24: ...urrent available just not nearly as much By running the battery to LVD the available fault current would be substantially less and safer if an inadvertent short circuit were to happen during the remov...

Reviews: