EVCO S.p.A. 

 

Vcolor 338 S

 | Installer manual ver. 1.2 | Code 144VC338SE124 

page 22 of 52 

8.2

 

Setting the cooking cycle 

Operate as follows to set the cooking type: 

1. 

Ensure that the device is switched on and that no 

other procedure is in progress. 

2. 

Touch 

 . 

3. 

Touch 

 to set: 

 

the cooking time (2a) 

 

the cooking at Delta T (2b) 

 

the core cooking (2c). 

 

Operate as follows to set the work set-point: 

4. 

Touch   . 

5. 

Touch 

 or 

 within 15 s; see also parameters r1 

and r2. 

6. 

Touch the middle of the display. 

 

Operate as follows to set the Delta T set-point: 

7. 

Touch 

 . 

8. 

Repeat  points  5.  and  6.;  see  also  parameters  r7 

and r8. 

 

Operate as follows to set the humidification: 

9. 

Touch 

 . 

10. 

Repeat points 5 and 6. 

 

Operate as follows to set the duration of the phase: 

11. 

Touch 

 . 

12. 

Repeat points 5 and 6. 

 

Operate as follows to set the core set-point: 

13. 

Touch 

 . 

14. 

Repeat  points  5.  and  6.;  see  also  parameters  r4 

and r5. 

 

Operate as follows to set the fan speed: 

15. 

Touch 

 . 

16. 

Repeat points 5 and 6. 

 

Operate  as  follows  to  set  the  duration  of  the  automatic  vent 

opening: 

17. 

Touch 

 . 

18. 

Repeat points 5 and 6. 

 

Operate as follows to add a phase to the cooking cycle: 

19. 

Touch 

 . 

20. 

Repeat the 3 points... 18. 

 

 

 

 

 

 

 

 

 

 

 

 

Setting the cooking cycle.

 

 

 

Setting the cooking type.

 

 

 

Setting the work set-point.

 

 

 

Addition of a phase to the cooking cycle.

 

 

 

 

Summary of Contents for Vcolor 338 S

Page 1: ...144VC338SE124 page 1 of 52 Vcolor 338 S Controller for top class electric ovens for gastronomy and confectionery with TFT graphic display colour touch screen in split version and can be integrated int...

Page 2: ...fore use of the device and follow all recommendations keep this document with the device for future consultation Only use the device in the way described in this document do not use the same as a safe...

Page 3: ...a recipe 26 9 4 Deleting a recipe 26 10 SPECIAL CYCLES FUNCTION 27 10 1 Preliminary notes 27 10 2 Starting a special cycle 28 11 FAVOURITE CYCLES FUNCTION 29 11 1 Preliminary notes 29 11 2 Starting a...

Page 4: ...nting with gasket 0027000007 to order separately for easy cleaning It is able to manage ventilation in on off and modulating mode in this case it is necessary to also use an external speed regulator w...

Page 5: ...ply Vcolor 338 S 115 230 VAC Analogue inputs Vcolor 338 S environment probe J K Pt 100 2 wires needle probe J K Pt 100 2 wires steam reduction probe J K Pt 100 2 wires Digital inputs for NO NC contact...

Page 6: ...ating mode with inversion of fan rotation direction weekly programmed switch on function programs function Notes 1 can be configured for fan left rotation or fan enabling 2 can be configured for fan r...

Page 7: ...r interface dimensions The following drawing illustrates the device s user interface dimensions these are expressed in mm in 2 2 Installation of user interface at rear of panel The following drawing i...

Page 8: ...rough the gasket 0027000007 to be ordered separately it is possible to guarantee the device user interface a protection rating of IP65 through the frame 0026700005 to be ordered separately it is also...

Page 9: ...equipment containing powerful magnets large diffusers etc areas affected by direct sunlight rain humidity excessive dust mechanical vibrations or shocks any metal parts in proximity of the control mo...

Page 10: ...al ver 1 2 Code 144VC338SE124 page 10 of 52 3 ELECTRIC CONNECTION 3 1 Electric connection The following drawing illustrates the device s electric connection Management of the ventilation in on off mod...

Page 11: ...4 page 11 of 52 Management of the ventilation in on off mode and with single speed and inversion of the fan rotation direction parameter F0 1 Management of the ventilation in on off mode and with dual...

Page 12: ...ution plants monitoring and surveillance systems via Web The USB communication port that allows the upload and download of the device settings through a common USB pen drive Example of connection for...

Page 13: ...vice electric power correspond with those of the local power supply see chapter 18 TECHNICAL DATA disconnect the device power supply before proceeding with any type of maintenance position the power c...

Page 14: ...the front parts of the device user interface parts PART MEANING 1 display The following drawing illustrates the aspect of the device s user interface rear panel The following table illustrates the mea...

Page 15: ...tes the meaning of device s control module parts PART MEANING 1 power supply 2 digital outputs K3 and K4 3 digital output K5 4 digital output K1 5 digital output K2 6 digital inputs for potential free...

Page 16: ...lowing table illustrates the meaning of the configuration parameters the parameters are listed with the order according to which it is appropriate that the device is configured PARAM MEANING FACTORY S...

Page 17: ...of 52 Successively check that the remaining settings are appropriate see paragraph 14 3 List of configuration parameters 6 Connect to the electric mains 7 Switch the device on see the paragraph 7 1 S...

Page 18: ...ion parameters see paragraph 14 2 Setting the configuration parameters 6 4 Vents The utility managed by the vent output depends on parameter u0 as follows if the parameter u0 is set at 0 the utility w...

Page 19: ...ted by the steam reduction probe reaches the temperature established with parameter t13 and is turned back on when the temperature rises above the established with the parameter t14 i e t13 t14 only i...

Page 20: ...re is a power cut during the cooking cycle and the duration of said interruption is lower than the time established with parameter r12 when the power supply is restored the cycle will be re proposed f...

Page 21: ...t and the work set point is an absolute value with Delta T only if the needle probe is enabled i e if parameter P2 is set at 1 in this case the phase has duration until the temperature detected by the...

Page 22: ...ouch 8 Repeat points 5 and 6 see also parameters r7 and r8 Operate as follows to set the humidification 9 Touch 10 Repeat points 5 and 6 Operate as follows to set the duration of the phase 11 Touch 12...

Page 23: ...ge 23 of 52 Operate as follows to select a phase of the cooking cycle 21 Touch or Operate as follows to eliminate a phase from the cooking cycle 22 Select the phase 23 Touch for 1 s Selection of a pha...

Page 24: ...s and the relative setting To modify the settings see the paragraph 8 2 Setting the cooking cycle Touch to open close the vent to switch the environment light on off to display the value of the proces...

Page 25: ...thin itself It is possible to memorise up to max 99 recipes 9 2 Memorising a recipe Operate as follows to memorise a recipe 1 Set the cooking cycle see the paragraph 8 2 Setting the cooking cycle 2 To...

Page 26: ...e is in progress 2 Touch 3 Touch 4 Touch or to select the recipe 5 Touch the middle of the display 6 Touch the middle of the display again 7 Touch the recipe will be activated 9 4 Deleting a recipe Op...

Page 27: ...wing table illustrates the factory settings of the timed regeneration cycle SETTING DEFAULT MINIMUM MAXIMUM work set point 110 C 20 180 C humidification 70 40 100 duration of the phase 25 min 1 90 min...

Page 28: ...a special cycle Operate as follows to start a special cycle 1 Ensure that the device is switched on and that no other procedure is in progress 2 Touch 3 Touch the identification icon of the special cy...

Page 29: ...ph 8 2 Setting the cooking cycle in this case the last cycle performed can be started recipes from the my recipes function Special cycles function work cycles 11 2 Starting a favourite cycle Operate a...

Page 30: ...Touch the middle of the display Operate as follows to set the switch on time 6 Touch 7 To set the time touch or within 15 s 8 To set the minutes touch the display in proximity of the centre then touc...

Page 31: ...ess 2 Touch for 1 s Operate as follows to select a switch on 3 Touch or Operate as follows to modify a switch on 4 Repeat the 3 points 11 of the paragraph 12 2 Setting the weekly programmed switch on...

Page 32: ...nd of the machine status Operate as follows to access the procedure 1 Ensure that the device is switched on and that no other procedure is in progress 2 Touch 3 Touch to select INTERNAL VALUES 4 Touch...

Page 33: ...no other procedure is in progress 2 Touch 3 Touch the middle of the display Operate as follows to select a value 4 Touch Operate as follows to set a value 5 Touch or within 15 s 6 Touch Operate as fo...

Page 34: ...ch the middle of the display 5 Touch within 15 s to set 19 6 Touch the middle of the display Operate as follows to select a parameter 7 Touch or Operate as follows to set a parameter 8 Touch the middl...

Page 35: ...IN MAX U M DEF MAIN REGULATOR r0 1 99 C F 2 5 work set point differential referring to the temperature detected by the environment probe r1 0 r2 C F 2 0 work set point minimum referring to the tempera...

Page 36: ...nt during cooling referring to the temperature detected by the environment probe r12 0 240 min 240 duration of a power supply cut off 3 PARAM MIN MAX U M DEF VARIOUS c0 1 120 s 10 duration of buzzer a...

Page 37: ...regulation of the temperature during fan switch off due to the effect of the inversion of direction of rotation of the same only if F0 1 2 or 3 0 YES F4 0 F5 0 minimum fan speed intended as a percenta...

Page 38: ...generated with an external humidifier t7 0 t6 s 30 duration of the injection of the steam generated with external humidifier corresponding to the maximum humidification t8 0 999 s 60 injection delay o...

Page 39: ...activated referring to the temperature detected by the environment probe see also A0 and A3 A2 0 240 min 0 maximum temperature alarm delay A3 0 2 0 maximum temperature alarm type 0 no alarm 1 absolute...

Page 40: ...2 u3 and u4 parameters will assume significance u2 0 600 ds s 10 120 duration of the inhibition of vent output from the conclusion of the brief impulse for vent opening and from the conclusion of the...

Page 41: ...ge 41 of 52 2 the unit of measurement depends on P1 3 if the duration of the power cur is shorter that the time established with parameter r12 when the power supply is restored the cycle will be re pr...

Page 42: ...g in a USB flash drive containing a proper text document called prog txt in the USB port of the device and wait a few seconds 3 Touch to select Upload programs 4 Touch the middle of the display the up...

Page 43: ...perate as follows to exit the procedure before the operation is complete 6 Touch before point 4 15 5 Download of the settings contained in the configuration parameters To make the download of the sett...

Page 44: ...es if the alarm occurs when the device is on a Delta T and a core cooking cycle cannot be allowed if the alarm occurs during a Delta T or core cooking cycle the cycle will be interrupted Steam reducti...

Page 45: ...e cycle will be interrupted the vent will be open the technical compartment fan will be on and the remaining outputs will be off door micro switch input alarm solutions check the causes of the activat...

Page 46: ...device USB communication port more accessible To connect the cap to the device connection cable 0810500018 or 0810500020 must be used to be ordered separately 17 3 Connection cables 0810500018 0810500...

Page 47: ...ation 0026700005 Using the frame it is possible to aesthetically integrate the user interface when this is installed on the panel 17 6 Gasket 0027000007 According to the IEC standards using the gasket...

Page 48: ...interface control module IP40 IP65 in the case of installation on panel with gasket 0027000007 to be ordered separately for IEC type 1 enclosure for UL and CSA IP00 Connections user interface control...

Page 49: ...from 58 to 1 292 C Resolution 1 C 1 F Protection none thermocouple K type analogue inputs Type of sensor chromel alumel Field of measurement from 50 to 1 100 C from 58 to 2 012 C Resolution 1 C 1 F Pr...

Page 50: ...250 VAC type SPST K4 or environment light management 1 x 8 A res output 250 VAC type SPST K5 for management of the technical compartment fan 1 x 8 A res output 250 VAC SPST type K6 for management of l...

Page 51: ...r manual ver 1 2 PT 20 14 Code 144VC338SE124 This document is exclusive property of EVCO EVCO does not assume any liability regarding possible errors stated The customer manufacturer installer or fina...

Page 52: ...EVCO S p A Vcolor 338 S Installer manual ver 1 2 Code 144VC338SE124 page 52 of 52 EVCO S p A Via Feltre 81 32036 Sedico Belluno ITALY Phone 39 0437 8422 Fax 39 0437 83648 info evco it www evco it...

Reviews: