Evco EVRS 200 Series Manual Download Page 7

EVCO S.p.A. | Codice 104RS200E214 | Page 7 of 8 | PT 24/13 | version 2.1

9

=

MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u1 and/or u11
= 6 the condenser fan will be switched on, the display will show the flashing code 

iA

” and the buzzer will be activated (until

the input is deactivated): when the input has been activated the number of times established with parameter i8 the
regulators will be switched off, if u1 and/or u11 = 6 the condenser fan will be switched on, the display will show the flashing
code “

iSd

” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or

until the power supply is interrupted); see also i7 and i9

10 =

MULTIFUNCTION - SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u1 and/or u11
= 2, until the input is deactivated)

11 =

MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)

i1

0

1

- - -

0

0

type of door micro switch/multifunction 1 input contact
0

=

normally open (active input with closed contact)

1

=

normally closed (active input with open contact)

i2

-1

120

min

30

30

delay in signalling of door micro switch input alarm (code “

id

”)

-1

=

the alarm will not be signalled

i3

-1

120

min

15

15

maximum duration of the effect caused by the activation of the door micro switch input on the compressor and the evaporator
-1

=

the effect will last until the input is deactivated

i4

0

1

- - -

0

0

storage of door micro switch input alarm (code “

id

”) (28)

1

=

YES

i5

0

11

- - -

5

5

effect caused by the activation of the door micro switch/multifunction 2 input; see also i4 (26)
0

=

no effect

1

=

DOOR MICROSWITCH - COMPRESSOR AND EVAPORATOR FAN SWITCH-OFF - the compressor and the evaporator fan will
be switched off (at maximum for time i3 or until the input is deactivated) (27)

2

=

DOOR MICROSWITCH - EVAPORATOR FAN SWITCH-OFF - the evaporator fan will be switched off (at maximum for time
i3 or until the input is deactivated)

3

=

DOOR MICROSWITCH - CELL LIGHT SWITCH-ON - the cell light will be switched on (only if u1 and/or u11 = 0, until the input
will be deactivated)

4

=

DOOR MICROSWITCH - SWITCH-OFF OF THE COMPRESSOR, EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the
compressor and the evaporator fan will be switched off (at maximum for time i3 or until the input is deactivated) and the
cell light will be switched on (only if u1 = 0, until the input is deactivated) (27)

5

=

DOOR MICROSWITCH - SWITCH-OFF OF THE EVAPORATOR FAN, SWITCH-ON OF CELL LIGHT - the evaporator fan will be
switched off (at maximum for time i3 or until the input is deactivated) and the cell light will be switched on (only if u1 and/
or u11 = 0, until the input is deactivated)

6

=

MULTIFUNCTION - SYNCHRONISATION OF DEFROSTING PERIODS - the activation of defrosting will cause activation of the
input (at maximum for time d24 or until the conclusion of predripping): if the input is connected in parallel to the input of
other devices configured in the same way, the activation of the input will cause activation of defrosting in the other devices.
The devices will start dripping simultaneously on conclusion of predripping of the last device to conclude the same

7

=

MULTIFUNCTION - ACTIVATION OF “ENERGY SAVING” FUNCTION - the “energy saving” function will be activated (just with
effect on the compressor, until the input is deactivated), provided the “overcooling” function is not running; see also r4

8

=

MULTIFUNCTION - ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the
flashing code “

iA

” and the buzzer will be activated (until the input is deactivated)

9

=

MULTIFUNCTION- ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u1 and/or u11
= 6 the condenser fan will be switched on, the display will show the flashing code 

iA

” and the buzzer will be activated (until

the input is deactivated): when the input has been activated the number of times established with parameter i8 the
regulators will be switched off, if u1 and/or u11 = 6 the condenser fan will be switched on, the display will show the flashing
code “

iSd

” and the buzzer will be activated (until the input is deactivated and the device is switched off and re-started or

until the power supply is interrupted); see also i7 and i9

10 =

MULTIFUNCTION - SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u1 and/or u11
= 2, until the input is deactivated)

11 =

MULTIFUNCTION - SWITCHING OFF THE DEVICE - the device will be switched off (until the input is deactivated)

i6

0

1

- - -

0

0

type of door micro switch/multifunction 2 input contact
0

=

normally open (active input with closed contact)

1

=

normally closed (active input with open contact)

i7

0

120

min

0

0

if i0 and/or i5 = 8, multifunction input alarm delay (code “

iA

”)

if i0 and/or i5 = 9, delay in compressor switching on after the deactivation of the multifunction input (29)

i8

0

15

- - -

0

0

number of multifunction input alarms (code “

iA

”) such to cause a pressure switch alarm (code “

iSd

”) (only if i0 and/or i5 = 9)

0

=

alarm absent

i9

1

999

min

240

240

time that must pass in absence of multifunction output alarms (code “

iA

”) so that the alarm counter is reset (only if i0 and/or i5 =

9)

i10

0

999

min

0

0

time without activations of the door switch input (on condition that the cabinet temperature has reached the working setpoint) in
order that function “energy saving” is activated (it has effect on the evaporator fan only if F0 = 1, 2, 3 or 4)
0

=

the function will never be activated due to the effect of this condition

i13

0

240

- - -

180

180

number of door switch input activations such as to provoke the defrost activation
0

=

defrosting will never be activated due to the effect of this condition

i14

0

240

min

32

32

minimum duration of the door switch input activation such as to provoke the defrost activation
0

=

defrosting for this condition will never be activated

PARAM.

MIN.

MAX.

U.M.

EVRS204 EVRS205 DIGITAL OUTPUTS

u1

0

7

- - -

0

0

operation controlled by fourth output (30)
0

=

CELL LIGHT - in this case the    key and parameters i0, i5 AND u2 will be activated

1

=

DEMISTER RESISTORS - in this case the   key and parameter u6 will be activated

2

=

AUXILIARY OUTPUT - in this case the   key and parameters i5 and u2 will be activated

3

=

ALARM OUTPUTS - in this case parameter u4 will be activated

4

=

DOOR RESISTORS - in this case parameter u5 will be activated

5

=

RESISTORS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated

6

=

CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated

7

=

COMPRESSOR 2 - in this case, parameter C11 will assume significance of

u2

0

1

-  -  -

0

0

enabling of manual switch on/switch off of the cell light or the auxiliary output when the device is switched off(only if u1 and/or u11=
0 or 2) (31)
1

=

YES

u4

0

1

- - -

1

1

enabling of alarm output deactivation with the silencing of the buzzer (only if u1 and/or u11 = 3)
1

=

YES

u5

-99

99,0 °C/°F (1)

-1,0

-1,0

temperature of the cell below which the door resistors are switched on (“u5 - 2,0 °C/4 °F, only if u1 and/or u11 = 4) (8)

u6

1

120

min

5

5

operating time of demister resistors (only if u1 and/or u11 = 1)

u7

-99

99,0 °C/°F (1)

-5,0

-5,0

neutral area value (relative to the work set-point, i.e. “work set-point + u7) (only if u1 and/or u11 = 5) (32)

u8

- - -

- - -

- - -

- - -

- - -

reserved

u9

0

1

- - -

1

1

enabling the buzzer
1

=

YES

u11

0

7

- - -

not avail.

3

operation controlled by fifth output (30)
0

=

CELL LIGHT - in this case the    key and parameters i0 and u2 will be activated

1

=

DEMISTER RESISTORS - in this case the   key and parameter u6 will be activated

2

=

AUXILIARY OUTPUT - in this case the   key and parameters i0 and u2 will be activated

3

=

ALARM OUTPUTS - in this case parameter u4 will be activated

4

=

DOOR RESISTORS - in this case parameter u5 will be activated

Summary of Contents for EVRS 200 Series

Page 1: ...ELECTRIC CONNECTION 2 1 Warnings for the electric connection do not use electric or pneumatic screwdrivers on the device terminal board if the device has been taken from a cold to hot place humidity...

Page 2: ...on of compressor operation hours changing the working setpoint with the procedure described in 9 1 The operations cause the display of the label Loc per 1 sec To unlock the keyboard 1 Hold the key and...

Page 3: ...e the or key within 15 s to set 149 5 Press and release the key or do not operate for 15 sec 6 Hold the and keys down for 4 s the display will show dEF 7 Press and release the key 8 Press and release...

Page 4: ...e COH will not be activated the compressor blocked alarm CSd code will never be activated the alarm output will be activated provided that parameter u1 and or parameter u11 is set at 3 the condenser f...

Page 5: ...3 3 compressor 2 switch on delay from compressor 1 switch on only if u1 and or u11 7 10 PARAM MIN MAX U M EVRS204 EVRS205 DEFROSTING d0 0 99 h 8 8 if d8 0 1 or 2 defrosting interval 11 0 interval def...

Page 6: ...evaporator fan will remain switched off F4 0 240 s 60 60 time duration that evaporator fan is switched off during operation for a low percentage of relative humidity when the compressor is switched of...

Page 7: ...er fan will be switched on the display will show the flashing code iA and the buzzer will be activated until the input is deactivated when the input has been activated the number of times established...

Page 8: ...will function as if parameter d8 were set at 0 14 if when defrosting is activated the operating dura tion of the compressor is less than the time estab lished with parameter d5 the compressor will re...