Evco EVRS 200 Series Manual Download Page 4

EVCO S.p.A. | Codice 104RS200E214 | Page 4 of 8 | PT 24/13 | version 2.1

id

Door micro switch input alarm (HACCP alarms)
Solutions:
-

check the causes of the activation of the in-
put; see parameters i0, i1, i5 and i6

Main consequences:
-

the effect established with the parameters i0
and i5

-

if parameter is set at 1, the device will store
the alarm, provided parameter i2 is not set at
-1

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

iA

Multifunction input alarm
Solutions:
-

check the causes of the activation of the in-
put; see parameters i0, i1, i5 and i6

Main consequences:
-

the effect established with the parameters i0
and i5

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

iSd

Pressure switch alarm
Solutions:
-

check the causes of the activation of the
input; see parameters i0, i1, i5, i6, i7, i8
and i9

-

switch off and re-start the device or suspend
the power supply

Main consequences:
-

the regulators will switch off

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

COH

Condenser overheated alarm.
Solutions:
-

check the condenser temperature; see pa-
rameter C6

Main consequences:
-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

-

the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)

CSd

Condenser overheated alarm.
Solutions:
-

check the condenser temperature; see pa-
rameter C7

-

switch the device off and back on again: if
when the device is switched back on, the
temperature of the condenser is still higher
than that established in parameter C7, dis-
connect the power supply and clean the con-
denser

Main consequences:
-

the compressor and the evaporator fan will be
switched off

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

-

the condenser fan will be on (only if parameter
u1 and/or parameter u11 is set at 6)

dFd

Defrosting alarm switched off because maximum
time has been reached
Solutions:
-

heck the integrity of the evaporator probe;
see parameters d2, d3 and d11

-

press a key to restore normal display

Main consequences:
-

the device will continue to operate normally.

When the cause of the alarm disappears, the device restores
normal operation, except for the following alarms:
-

pressure switch alarm (code “

iSd

”) which requires the

switching off of the device or the temporary suspension
of the power supply

-

compressor blocked by condenser temperature alarm
(code “

CSd

”) which requires the switching off of the

device or the temporary suspension of the power supply

-

Defrosting alarm switched off because maximum time
has been reached (code “

dFd

”) which requires the

pressing of a key.

12

ERRORS

12.1

Errors

Code Part

Pr1

Cell probe error
Solutions:
-

check that the probe is the PTC or NTC type;
see parameter P0

-

-

check the device-probe connection

-

check the cell temperature

Main consequences:
-

compressor activity will depend on param-
eters C4 and C5

-

the defroster will not be activated

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

-

the door resistors will be switched off (only
and provided parameter u1 and/or parameter
u11 is set at 4)

-

the neutral area operating resistors will be
deactivated (only if parameter u1 and/or pa-
rameter u11 is set at 5)

Pr2

Evaporator probe error
Solutions:
-

the same as the preceding case but with re-
spect to the evaporator probe

Main consequences:
-

if parameter P3 is set at 1, the defrosting
period will last for the amount of time set with
parameter 3

-

if parameter P3 is set at 1and parameter d8 is
set at 2 or to 3, the device will operate as if
parameter d8 were set at 0

-

if parameter F0 is set at 3 or 4, the device will
operate as if the parameter were set at 2

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

Pr3

Condenser probe error.
Solutions:
-

the same as the preceding case but with re-
spect to the condenser probe

Main consequences:
-

condenser overheated alarm (code “

COH

”)

will not be activated

-

the compressor blocked alarm (“

CSd

” code)

will never be activated

-

the alarm output will be activated (provided
that parameter u1 and/or parameter u11 is
set at 3)

-

the condenser fan will operate parallel to the
compressor (only if parameter u1 and/or
parameter u11 is set at 6)

ErC

User interface-control module compatibility error.
Solutions:
-

check the compatibility of the user interface
with the control module (check the data stated
on the labels)

Main consequences:
-

the control module will continue to operate
regularly.

ErL

User interface-control module communication er-
ror.
Solutions:
-

check user interface-control module control
module

Main consequences:
-

the control module will continue to operate
regularly.

When the problem that caused the alarm disappears, the
device is restored to normal operation.

13

TECHNICAL DATA

13.1

Technical data

Purpose of the command device:

 operating command

device.

Construction of the command device:

 built-in electronic

device.

User interface container:

-

user interface: grey self-extinguishing

-

control module:  without cover.

User interface dimensions:

-

user interface: 180.0 x 38.0 x 28.0 mm (7.086 x 1.496
x 1.102 in; L x H x D)

-

control module: 134,0 x 108.0 x 24.0 mm (5.275 x
4.251 x 0.944 in; L x H x D).

Method of mounting the command device:

-

user interface: panel, with elastic retaining wings

-

control module: on flat surface, with spacers.

Protection rating:

-

user interface: IP55

-

control module: IP00.

Connections:

-

user interface: removable screw terminal board (con-
trol module).

-

control module: fixed screw terminal board (inputs),
6.3 m faston (0.248 in, power supply, equipment earth
and outputs), removable screw terminal board (user
interface) 6 pole connector (serial port).

The maximum length of the analogue inputs and digital
outputs connection cables must be less than 10 m
(32,808 ft).
The maximum length of the user interface-control module
connection cables must be less than 20 m (65,616 ft).

Operating temperature:

 from 0 to 55 °C (from 32 to

131 °F).

Storage temperature:

from -25 to 70 °C (from -13 to

158 F).

Humidity for use:

 from 10% to 90% relative humidity

without condensate.

Command device pollution situation:

 2.

Power supply: 

115... 230 VAC (+10% -15%), 50/60 Hz,

5.5 VA max.

Rated impulse voltage:

 4K V.

Overvoltage category:

 II

.

Class and structure of software:

 A.

Analogue inputs:

 2 inputs (cabinet probe and evaporator

probe), can be set via configuration parameter for PTC/NTC
probes
PTC type analogue inputs (990 

 @ 25°C, 77°F)

Type of sensor:

KTY 81-121.

Measurement field:

from -50 to 150 °C
 (from -58 to 302°F).

Resolution:

0.1 ° (1 °F).

Protection:

none.

PTC type analogue inputs NTC (10K 

 @ 25°C, 77°F)

Type of sensor:

ß3435.

Measurement  field:

from -50 to 105 ° (from -40 to
220 °).

Resolution:

0.1 ° (1 °F).

Protection:

none.

Digital inputs:

 1 input (door micro/multi-function 2 switch),

which can be set via configuration parameter due to normally
open contact/normally closed contact (free of voltage contact,
5 VDC, 2 mA)
Digital inputs
Power:

none.

Protection:

none.

Other inputs:

 1 input that can be set via configuration

parameter for analogue input (condenser probe)/digital input
(door micro switch/multifunction 1), with the same technical
features illustrated previously.

Displays:

 custom 3 digit display with function icon.

Digital outputs:

4 outputs (electro-mechanical relays) in the EVRS204 model,
5 outputs (electro-mechanical relays) in the EVRS205 model
-

1 x 30 A res. output @ 250 VAC SPST type (K2) for
compressor management

-

1 x 16 A res. output @ 250 VAC type SPST (K4) for
defrosting management

-

1 x 8 A res. output @ 250 VAC type SPST (K5) for
management of the evaporator fan

-

1 x 16 A res. output @ 250 VAC type SPST (K3) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, neutral area
operation resistors, condenser fan of compressor 2 fan.

-

1 x 30 A res. output @ 250 VAC type SPST (K1) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, neutral area
operation resistors, condenser fan of compressor 2 fan.

The maximum load current allowed is 20 A.

Type 1 or Type 2 actions:

 Type 1.

Complementary features of Type 1 or Type 2 actions:

 C.

Communication port:

 1 x TTL serial port with MODBUS

communication protocol (for EVKEY programming key and
other EVCO products).

Signal buzzer and alarm:

on request.

Summary of Contents for EVRS 200 Series

Page 1: ...ELECTRIC CONNECTION 2 1 Warnings for the electric connection do not use electric or pneumatic screwdrivers on the device terminal board if the device has been taken from a cold to hot place humidity...

Page 2: ...on of compressor operation hours changing the working setpoint with the procedure described in 9 1 The operations cause the display of the label Loc per 1 sec To unlock the keyboard 1 Hold the key and...

Page 3: ...e the or key within 15 s to set 149 5 Press and release the key or do not operate for 15 sec 6 Hold the and keys down for 4 s the display will show dEF 7 Press and release the key 8 Press and release...

Page 4: ...e COH will not be activated the compressor blocked alarm CSd code will never be activated the alarm output will be activated provided that parameter u1 and or parameter u11 is set at 3 the condenser f...

Page 5: ...3 3 compressor 2 switch on delay from compressor 1 switch on only if u1 and or u11 7 10 PARAM MIN MAX U M EVRS204 EVRS205 DEFROSTING d0 0 99 h 8 8 if d8 0 1 or 2 defrosting interval 11 0 interval def...

Page 6: ...evaporator fan will remain switched off F4 0 240 s 60 60 time duration that evaporator fan is switched off during operation for a low percentage of relative humidity when the compressor is switched of...

Page 7: ...er fan will be switched on the display will show the flashing code iA and the buzzer will be activated until the input is deactivated when the input has been activated the number of times established...