Evco EVRS 200 Series Manual Download Page 2

EVCO S.p.A. | Codice 104RS200E214 | Page 2 of 8 | PT 24/13 | version 2.1

3.4

Evaporator temperature display

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the 

 key down for 1 s: the display will show the

first label available.

3.

Press and release the 

 key or the 

 key to select

Pb2

”.

4.

Press and release the key 

.

To exit the procedure:
5.

Press and release the 

 key or do not operate for

60 sec.

6.1 Press and release the 

 or 

 key until the display

shows the cell temperature or do not operate for 60
sec.

Alternatively:
6.2 Press and release the 

 key.

If the evaporator probe is absent (parameter P3 = 0), the
label “

Pb2

” will not be displayed.

3.5

Condenser temperature display

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the 

 key down for 1 s: the display will show the

first label available.

3.

Press and release the 

 key or the 

 key to select

Pb3

”.

4.

Press and release the 

 key.

To exit the procedure:
5.

Press and release the 

 key or do not operate for

60 sec.

6.1 Press and release the 

 or 

 key until the display

shows the cell temperature or do not operate for 60
sec.

Alternatively:
6.2 Press and release the 

 key.

If the third input function is that of the digital input (parameter
P4 = 0), the label “

Pb3

” will not be displayed.

3.6

Activation/deactivation of “overcooling”
function

1.

Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evaporator fan
is off.

2.

Hold the 

 key down for 4 s: the Overcooling LED will

light up.

During the “overcooling” function the working setpoint is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if
the defrosting interval expires when the function is in
progress, defrosting will be activated at the end of the
function.

3.7

Defrosting activation in manual mode

1.

Make sure that the keyboard is not locked and that no
other operation is in progress; ensure that the
“overcooling” function is not in progress

2.

Hold the 

 key down for 4 s.

If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that
established with parameter d2, the defrosting function will
not be activated.

3.8

Switch-on/off of the cell light in manual
mode (only if parameter u1
and/or parameter u11 is set at 0)

1.

Make sure no procedures are in progress

2.

Press and release the 

 key: the “

AUX

” LED will

switch on/off.

Using the door digital inputs it is also possible to switch on/
off the cell light by remote; see also parameter u2.
If parameter u1 is set at 0 (i.e. the utility managed by the
fourth output is the cabinet light) and parameter u11 is set
at 2 (i.e. the utility managed by the fifth output is the
auxiliary output), holding the 

 key down for 2 s will

cause the switch-on/off of the “

AUX

” LED and of the auxil-

iary output.

3.9

Demister resistors switch-on (only if the
parameter u1 and/or parameter u11 is set at
1)

1.

Ensure that the device is switched on and that no other
procedure is in progress.

2.

Hold the 

 key down for 2 s: the “

AUX

” LED will

light up and the resistors will be switched on, both
for the amount of time established with parameter
u6.

Manually switching off the demisting resistors is not permitted
(that is, before the time established with parameter u6
expires).

3.10

Switch-on/off of the auxiliary output in
manual mode (only if parameter u1 and/or
parameter u11 is set at 2)

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Press and release the 

 key: the “

AUX

” LED will

switch on/off.

Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If parameter u1 is set at 2 (i.e. the utility managed by the
fourth output is the auxiliary output) and parameter u11 is
set at 0 (i.e. the utility managed by the fifth output is the
cabinet light), holding the 

 key down for 2 s will cause

the switch-on/off of the “

AUX

” LED and of the cabinet

light.
If the auxiliary output has been switched on manually,
then it can also be switched off manually (similarly, if the
auxiliary output has been remotely switched on, then it
can only be switched off in the same manner); see also
parameter u2.

3.11

Locking/unlocking the keyboard

To lock the keyboard:
1.

Make sure no procedures are in progress

2.

Hold the 

 and 

 keys down for 1 s:

the display will show “

Loc

”.

If the keyboard is locked, the following are not permitted:
-

device switch-on/off in manual mode

-

display of evaporator temperature (via the procedure
explained in paragraph 3.4)

-

display of the condenser temperature (via the procedure
indicated in paragraph 3.5)

-

activation/deactivation of “overcooling” function

-

manual activation of defrosting

-

manual switch on/off of the auxiliary output

-

activation of operation for low of high percentage of
relative humidity and learning the kind of operation

-

see information regarding the HACCP alarms

-

cancellation of HACCP alarm list

-

display of compressor operation hours

-

cancellation of compressor operation hours

-

changing the working setpoint (with the procedure
described in 9.1).

The operations cause the display of the label “

Loc

” per 1

sec.
To unlock the keyboard:
1.

Hold the 

 key and thee 

 key down for 1 s: the

display will show the message “

UnL

” for 1 sec.

3.12

Silencing the buzzer

To lock the keyboard:
1.

Make sure no procedures are in progress

2.

Press a key (the first pressing of the key will not cause
the effect associated with that key).

If the parameter u1 and/or the parameter u11 is set at 3
(i.e. the utility managed by the fourth output and/or the
utility managed by the fifth output is the alarm output) and
parameter u4 is set at 1, pressing the key will also cause the
deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be acti-
vated.

4

OPERATION DUE TO LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGE (ONLY IF PARAMETER
F0 IS ISET AT 5)

4.1

Preliminary notes

During operation for low percentage of relative humidity, the
evaporator ventilator will be switched on if the compressor is
switched off (parameter F4 determines the amount of time
it is switched off while parameter F5 determines the amount
of time it is switched on).
During operation for a high percentage of relative humidity
the evaporator fan is always on.

4.2

Activation of operation for low or high
percentage relative humidity in manual
mode.

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the 

 and 

 keys down for 4 s: the display will

show “

rhL

” (operation for low percentage of relative

humidity) or “

rhH

” (operation for high percentage of

relative humidity) for 10 sec.

To restore the normal display before the operation is
complete:
3.

Press a key.

Activation of the operation for a low or high percentage of
relative humidity can be done using parameter F6.
If the parameter F0 is not set at 5, pressing the 

 and

 keys will cause the display of the “

- - -

“ indication

for 1 s.

4.3

Learning the type of operation in progress

1.

Make sure no procedures are in progress

2.

Press and release the 

 and 

 keys: the display

will show “

rhL

” (operation for low percentage of rela-

tive humidity) or “

rhH

” (operation for high percentage

of relative humidity) for 10 sec.

To restore the normal display before the operation is com-
plete:
3.

Press a key.

If parameter F0 is not set at 5, pressing the 

 and 

keys will cause:
-

the display of the message “

- - - -

“ for 1 sec if the

keyboard is not locked

-

display of the label “

Loc

” for 1 sec if the keyboard is

locked..

5

ENERGY SAVING

5.1

Preliminary notes

Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
cell temperature has reached the work set-point) the “en-
ergy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working setpoint is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically, on condition
that parameter F0 has value 1 or 2 (parameter F13 sets the
time the fan remains turned off and parameter F14 the time
it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).

6

“HACCP” FUNCTION

6.1

Preliminary notes

The device can memorise the following HACCP alarms:
-

minimum temperature alarm (code “

AL

”)

-

maximum temperature alarm (code “

AH

”)

-

door micro switch input alarm (code “

id

”)

The device supplies the following information for every
alarm:
-

the critical value

-

the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).

Code Critical value

AL

the minimum temperature of the cell during any
alarm of this type

AH

the maximum temperature of the cell during any
alarm of this type

iD

the maximum cell temperature during any alarm
of this type; see also parameter i4

The device stored the minimum temperature alarm on
condition that the temperature associated to the alarm is
that of the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “

HACCP

” LED provides information regarding the storage

status of the alarms; see paragraph 10.1.

6.2

Display of HACCP alarm information

To begin the procedure:
1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the 

 key down for 1 s: the display will show the

first label available.

3.

Press and release the 

 or 

 key to select “

LS

”.

4.

Press and release the 

 key: the display will show

one of the codes included in the table in paragraph
6.1.

If the device does not have any alarms stored, the label

LS

” will not be displayed.

To select an alarm:
5.

Press and release the 

 or 

  key (to select, for

example, “

AH

”).

To see information regarding the alarm:
6.

Press and release the 

 key: the 

HACCP

 LED will

stop flashing and remain on permanently and the dis-
play will show, for example, the following information
in succession (for example):

Inform. Part

8.0

the critical value is 8.0 °C/8 °F

dur

the display is about to show the alarm duration

h01

the alarm lasted for 1 hour (other data continues)

n15

the alarm lasted 1 hour and 15 min

AH

the alarm selected

the displays each piece of information for 1 s.

Summary of Contents for EVRS 200 Series

Page 1: ...ELECTRIC CONNECTION 2 1 Warnings for the electric connection do not use electric or pneumatic screwdrivers on the device terminal board if the device has been taken from a cold to hot place humidity...

Page 2: ...on of compressor operation hours changing the working setpoint with the procedure described in 9 1 The operations cause the display of the label Loc per 1 sec To unlock the keyboard 1 Hold the key and...

Page 3: ...e the or key within 15 s to set 149 5 Press and release the key or do not operate for 15 sec 6 Hold the and keys down for 4 s the display will show dEF 7 Press and release the key 8 Press and release...

Page 4: ...e COH will not be activated the compressor blocked alarm CSd code will never be activated the alarm output will be activated provided that parameter u1 and or parameter u11 is set at 3 the condenser f...

Page 5: ...3 3 compressor 2 switch on delay from compressor 1 switch on only if u1 and or u11 7 10 PARAM MIN MAX U M EVRS204 EVRS205 DEFROSTING d0 0 99 h 8 8 if d8 0 1 or 2 defrosting interval 11 0 interval def...

Page 6: ...evaporator fan will remain switched off F4 0 240 s 60 60 time duration that evaporator fan is switched off during operation for a low percentage of relative humidity when the compressor is switched of...

Page 7: ...er fan will be switched on the display will show the flashing code iA and the buzzer will be activated until the input is deactivated when the input has been activated the number of times established...

Page 8: ...will function as if parameter d8 were set at 0 14 if when defrosting is activated the operating dura tion of the compressor is less than the time estab lished with parameter d5 the compressor will re...

Reviews: