EVCO S.p.A.
c-pro 3 OEM HRV | Application handbook ver. 4.0 | Code 144CP3OHE404
page 80 of 138
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
HCF5
Frequency/period PWM AO5
10
1
2000
Hz/Sec
CO-AO
CF5
Available
only
if
PG15=1
HCF6
Frequency/period PWM AO6
10
1
2000
Hz/Sec
CO-AO
CF6
Available
only
if
PG15=1
HCV1
Maximum Volt AO1 output
10.00
1.00
10.00
V
CO-AO
CV1
HCV2
Maximum Volt AO2 output
10.00
1.00
10.00
V
CO-AO
CV2
HCV3
Maximum Volt AO3 output
10.00
1.00
10.00
V
CO-AO
CV3
HCV4
Maximum Volt AO4 output
10.00
1.00
10.00
V
CO-AO
CV4
HCV5
Maximum Volt AO5 output
10.00
1.00
10.00
V
CO-AO
CV5
Available
only
if
PG15=1
HCV6
Maximum Volt AO6 output
10.00
1.00
10.00
V
CO-AO
CV6
Available
only
if
PG15=1
DO HARDWARE PARAMETERS
HD01
DO1 allocation
(see table in section 6.4)
0
-44
47
CO-DO
d01
HD02
DO2 allocation
0
-44
47
CO-DO
d02
HD03
DO3 allocation
0
-44
47
CO-DO
d03
HD04
DO4 allocation
0
-44
47
CO-DO
d04
HD05
DO5 allocation
0
-44
47
CO-DO
d05
HD06
DO6 allocation
0
-44
47
CO-DO
d06
HD07
DO1 allocation expansion
0
-44
47
CO-DO
d07
Available
only
if
PG15=1
HD08
DO2 allocation expansion
0
-44
47
CO-DO
d08
Available
only
if
PG15=1
HD09
DO3 allocation expansion
0
-44
47
CO-DO
d09
Available
only
if
PG15=1
HD10
DO4 allocation expansion
0
-44
47
CO-DO
d10
Available
only
if
PG15=1
HD11
DO Open Collector allocation expansion
0
-44
47
CO-DO
d11
Available
only
if
PG15=1
PSd4
Manufacturer level password (4)
-33
-999
9999
CO
PS4
Once the machine parameters have been configured and any changes made to the configuration parameters, it is advisable to switch the machine off and restart the
system to allow the board to configure itself correctly.
If to the analog outputs of the expansion two PWM sensors are connected, make sure they have the same frequency because the parameter for the configuration is the
same for both the outputs.
**
For a PWM the parameter is expressed in Hz and will be limited to between 10Hz and 2000Hz, for a slow PWM the parameter is expressed in seconds and will
be limited to between 1 and 255 seconds.