EVCO S.p.A.
c-pro 3 OEM HRV | Application handbook ver. 4.0 | Code 144CP3OHE404
page 68 of 138
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
PH13
ModBus slave parity (0=none, 1=odd, 2=even)
2
0
2
IS-M
H13
PH14
ModBus slave stop bit (0=1bit, 1=2bit)
0
0
1
IS-M
H14
VARIOUS PARAMETERS
PH03
Minimum value cooling setpoint
20.0
-15.0
PH04
°C
IS-V
H03
PH04
Maximum value cooling setpoint
28.0
PH03
70.0
°C
IS-V
H04
PH05
Enables machine switch on/switch off by pressing the
ESC/Stand-By key
YES (1)
NO (0)
YES (1)
IS-V
H05
PH08
Summer/winter changeover type
0: Manual
1: Automatic
2: Auto
0
0
2
IS-V
H08
PH09
Enables supervisor machine switch on/switch off
NO (0)
NO (0)
YES (1)
IS-V
H09
PH18
Delete alarm history
NO (0)
NO (0)
YES (1)
IS-V
Set YES (1) and wait
for the NO value (0)
H18
PH19
Enables machine start-up/shut-down on program
timing
NO (0)
NO (0)
YES (1)
IS-V
H19
PH20
Enables the program timing
NO (0)
NO (0)
YES (1)
IS-V
H20
PH21
Holiday unit status
0: Unit off
1: Unit on
1
0
1
IS-V
H21
PH25
Enables automatic daylight saving time
0: Disabled
1: Europe
2: North America
0
0
2
IS-V
H25
PH26
Minimum value heating setpoint
14.0
-15.0
PH27
°C
IS-V
H26
PH27
Maximum value heating setpoint
26.0
PH26
70.0
°C
IS-V
H27
PH32
Temperature measurement unit:
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
IS-V
H32
PH41
Meaning of summer/winter icon
0: Sun=Summer - Snow=Winter
1: Sun=Winter - Snow=Summer
0
0
1
IS-V
H41
PH42
Enables EVCO icon
NO (0)
NO (0)
YES (1)
IS-V
H42
DEFAULT
PH15
Reset manufacturer’s default parameters
NO (0)
NO (0)
YES (1)
IS-D
Wait for the NO (0)
value on reset com-
pletion
H15
PSd3
Installer level (3) password
-22
-999
9999
IS
PS3
Level 4
MANUFATURER MENU
FANS