05. ALARMS
“NO ACC” alarm.
The alarm is triggered when the fume temperature does not increase by a gradient equal to 3 °C/min during the LOAD WOOD or FIRE ON phases and does not
reach the temperature set by PR13 within the time set by PR01:
• The switching-on phase is interrupted and the stove switches off.
• The display shows the message “ALAR/ No/ Acc”.
• Use the control panel or remote control to clear the alarm (hold on/off button down for at
least 2 seconds).
“NO FIRE” alarm.
If the stove switches off during the working mode (the fume temperature reaches a value below the PR13 parameter), the stove enters the switching-off phase.
• The display shows the message “ALAR/No/Fire”.
• Use the control panel or remote control to clear the alarm (hold on/off button down for at
least 2 seconds)
“COOL FIRE” alarm.
It is triggered only in case of power outage. When power resumes, the stove enters a switching off phase.
• The display shows the message “CooL Fire”.
• Upon completing the switching-off cycle, the stove automatically resumes operation.
“FAN FAIL” alarm.
The alarm is triggered when exhaust blower rotation is not detected. • The stove enters the switching-off phase.
• The display shows the message “Alar /Fan/Fail”.
• Use the control panel or remote control to clear the alarm (hold on/off button down for at least 2 seconds).
“SIC DEP FAIL” alarm.
The alarm is triggered when the pressure switch or the safety thermostat are activated:
• The stove enters the switching-off phase.
• The display shows the message “Alar /Dep/ Sic /FAiL”
• ALF and ALC LEDs flash
• Use the control panel or remote control to clear the alarm (hold on/off button down for at least 2 seconds).
Alarm Log
The system alarm log registers the last 5 alarms triggered and it is accessible by entering the “E9” code in the MN04 menu. Enter the password “99” in the MN04
menu to clear the alarms.
Alarm Display
•Enter the MN04 technical menu.
•Press buttons 1 and 2 repeatedly until message “E9” appears on the display. Hold the buttons down to move more rapidly.
•Press button 8 to confirm.
•The display shows the error number and the type of alarm alternatively. Press button 8 again to move to the other alarms.
Clearing Alarms.
• Enter the MN04 technical menu.
• Press buttons 1 and 2 repeatedly until the display shows “99”. Hold the buttons down to move more rapidly.
• Press button 8 to confirm and clear the log.
SERVICE MESSAGE
The stove will display the message SERVICE (or SER) during operation depending on the number of hours of operation. The wording does not lock operation of
the stove, but non-routine maintenance will be required by an authorised technician, who will reset the service hours.
6