100/180 MM GRAPHICS RECORDER: USER GUIDE
HA261742
Issue 16 Nov 04
User Guide
Page 96
Operator Note
Signed
Frederick Bloggs
Authorised
Engineer
Config
Password
Appears only if 'Requires Authorising' enabled
***
******
Appears only if 'Requires Signing' enabled
Ok Cancel
Note cannot be empty.
Ok
Pop-up appears only if 'Ok'
operated without an operator
note having been entered.
Password
4.4.2 MANAGEMENT (Cont.)
CONFIGURABLE PARAMETERS (Cont.)
Notes:
1.
The Configuration Revision (and for changes in the Security menus - the Security Revision) are
incremented every time the recorder configuration (security configuration) is changed. The current val-
ues can be viewed in the System/About menu (section 4.6.5).
2.
All configuration and security changes must be made either at the recorder operator interface, or using
the Remote Viewer. Use of the configuration editor is not permitted if traceability is to be maintained.
3.
If fitted, Event buttons (section 4.3.7) are not included in the Require Signing/Require Authorization
regime described above. Instead, each individual button can be configured to require signing or to re-
quire both signing and authorization.
Figure 4.4.2b Signature page
Enable Audit trail
If this field is enabled, then all changes to configuration are displayed on the 'chart' and
become part of the history file for each enabled group. The following is an example of how
these changes would appear on the screen for an imaginary set up for channel 8. 'New T/C
type chan 8' is the note entered in the Signature page, and 'Kiln8 temp' is the channel descrip-
tor
.
19/10/03 11:53:01 Configuration Revision 486,144 was 486,143
19/10/03 11:52:57 Kiln8 temp Alarm Number 1, Job Number 1 Drive Relay 1 on board 7 while Unacknowledged was No action
19/10/03 11:52:57 Kiln8 temp Alarm Number 1 Threshold 530.0 ˚C was 500
19/10/03 11:52:57 Kiln8 temp Alarm Number 1 Type Absolute Low was Absolute High
19/10/03 11:52:57 Kiln8 temp Cold Junction Type Internal was External
19/10/03 11:52:57 Kiln8 temp Scale High 1000.0˚C was 900.0
19/10/03 11:52:57 Kiln8 temp Scale Low 450.0˚C was 300.0
19/10/03 11:52:57 Kiln8 temp Lin Type Type K was Type J
19/10/03 11:52:57 Config,Signed:Engineer,Authorized:Engineer,New T/C type chan 8