HA249928
Issue 15 Jly 06
Page 36
100 MM RECORDER USER GUIDE
600
Ω
6000
Ω
0
Ω
0
Ω
22m
Ω
148m
Ω
0.045% input + 0.065% range
0.049% input + 0.035% range
35ppm of input per deg C
35ppm of input per deg C
Low
Range
High
Range
Resolution
Maximum error
(Instrument at 20˚C)
Worst case temperature
performance
JPT100
Ni100
Ni120
Pt100
Pt100A
Pt1000
-220 to + 630
- 60 to + 250
-50 to + 170
-200 to + 850
-200 to + 600
-200 to + 850
JIS C1604:1989
DIN43760:1987
DIN43760:1987
IEC 751
Eurotherm Recorders SA
IEC 751
RTD Type
Overall range (˚C)
Standard
Max linearisation error
0.01 ˚C
0.01 ˚C
0.01 ˚C
0.01 ˚C
0.09 ˚C
0.01 ˚C
6.1 TECHNICAL SPECIFICATION (Recorder) (Cont.)
Resistance inputs
Ranges (including lead resistance)
0 to 600
Ω
, 0 to 6k
Ω
Linearisation accuracy
0.05% of user entered span.
Influence of lead resistance
Error = negligible; Mismatch = 1
Ω
/
Ω
Temperature scale
ITS90
Ranges and tempreature performance
RTD ranges and standards