background image

E25 / E29

7

EN

cod. 3541M540  -  Rev. 01  -  06/2017

Connection with separate pipes

fig. 17 - Examples of connection with separate pipes (

 = Air / 

 = Fumes)

Table. 4 - Typology

For connection of the separate ducts, fit the unit with the following starting accessory:

fig. 18 - Starting accessory for separate ducts

Before proceeding with installation make sure the maximum permissible length has not
been exceeded, by means of a simple calculation:
1.

Completely establish the layout of the system of split flues, including accessories
and outlet terminals.

2.

Consult the table 6 and identify the losses in meq (equivalent metres) of every com-
ponent, according to the installation position.

3.

Check that the sum total of losses is less than or equal to the maximum permissible
length in table 5.

Table. 5 - Baffles for separate ducts

A

The horizontal flue section to be installed with a minimum 3° (55mm per
meter) fall back to the boiler

.

The air intake pipe should be installed level (or with a slight fall away from the
boiler to prevent rain ingress).
The air intake terminal must be below or to the side of the flue outlet terminal,

NOT above

.

Table. 6 - Accessories

Position of terminals

fig. 19

Type

Description

C1X

Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be 
undergo similar wind conditions (within 50 cm)

C3X

Roof vertical exhaust and intake. Inlet/outlet terminals like for C12

C5X

Wall or roof  exhaust and intake separate or in any case in areas with different pressures. The exhaust and 
intake must not be positioned on opposite walls.

C6X

Intake and exhaust with separately certified pipes (EN 1856/1)

B2X

Intake from installation room and wall or roof exhaust

 IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION

Model E25

Separate ducts

Max. permissible length

60 m

eq

Baffle to use

0 ÷ 20 m

eq

Ø 45

20 ÷ 45 m

eq

Ø 50

45 ÷ 60 m

eq

No baffle

Model E29

Separate ducts

Max. permissible length

55 m

eq

Baffle to use

0 ÷ 35 m

eq

Ø 50

35 ÷ 55 m

eq

No baffle

C

5x

C

3x

B

2x

C

1x

max 50 cm

Ø 81

Ø 81

Ø 

65

Ø 

87

Ø 

65

041039X0

Losses in m

eq

Air

inlet

Fume exhaust

Vertical

Horizontal

Ø 80

PIPE

1 m M/F

1KWMA83W

1.0

1.6

2.0

BEND

45° M/F

1KWMA65W

1.2

1.8

90° M/F

1KWMA01W

1,5

2.0

PIPE SECTION

with test point

1KWMA70W

0.3

0.3

TERMINAL

air, wall

1KWMA85A

2.0

-

fumes, wall with antiwind

1KWMA86A

-

5.0

FLUE

Split air/fumes 80/80

010027X0

-

12.0

Fume outlet only Ø80

01
1KWMA86U

-

4.0

  

Ø 60

PIPE

1 m M/F

1KWMA89W

6.0

BEND

90° M/F

1KWMA88W

4.5

REDUCTION

80/60

041050X0

5.0

TERMINAL

fumes, wall with antiwind

1KWMA90A

7.0

ATTENTION: CONSIDER THE HIGH PRESSURE LOSSES OF Ø60 ACCESSORIES; 
USE THEM ONLY IF NECESSARY AND AT THE LAST FUME EXHAUST SECTION.

Minimum dimensions of fume exhaust terminals

A

Directly under an opening, air inlet, openable window, etc.

300 mm

B

Above an opening, air inlet, openable window, etc.

300 mm

C

Horizontally to an opening, air inlet, openable window, etc.

300 mm

D

Under gutters, drain pipes

75 mm

E

Under cornices or under eaves

200 mm

F

Under balconies or garages

200 mm

G

From a drain pipe or a vertical drain pipe

150 mm

H

From an internal or external corner

100 mm

I

Above ground level, a roof or balcony

300 mm

J

From a surface facing the terminal

600 mm

K

From a terminal facing the terminal

1200 mm

litres

From a garage opening (e.g. door, window) with access to the home

1200 mm

M

Vertically from a terminal on the same wall

1500 mm

No

Horizontally from a terminal on the same wall

300 mm

O

From the wall on which the terminal is fitted

N/A

P

From a vertical structure on the roof

150 mm

Q

Above the intersection with the roof

300 mm

NOTES

N/A = Not applicable

Also, the terminal must be at least 150 mm (in case of forced intake) from an opening made 
in the structure of the building to house a fitted element such as a window frame.

Positions of condensate drain terminals: if the fume exhaust is provided for at a low level, 
the potential effect of the flue gas cloud must be considered. Special flue gas management 
kits are available by request.

The flue gas cloud must not be directed towards:
-

A frequented approach

-

A window or door

-

An adjacent property

P

D, E

Q

Q

l

B

C

A

G

F

L

J

H

H

K

N

N

M

M

Q

Summary of Contents for E25

Page 1: ...cod 3541M540 Rev 01 06 2017 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...g 14 Heating symbol 15 Burner lit and actual power level flashing during combustion fault function 16 Service Tool connection 17 Water gauge Indication during operation Heating A heating demand generated by the Room Thermostat or Remote Timer Control is in dicated by flashing of the hot air above the radiator on the display The display detail 11 fig 1 shows the actual heating delivery temperature ...

Page 3: ...e boiler the above ad justments are managed according to that given in table 1 Table 1 Water system pressure regulation The filling pressure read on the boiler water gauge with the system cold must be approx 1 0 bar If the system pressure falls to values below minimum the boiler stops and fault F37 is displayed 3 INSTALLATION 3 1 General Instructions B This unit must only be used for its intended ...

Page 4: ...e system delivery and return pipes follow a path where air pockets can form in certain places it is advisable to install vent valves at these points Also type A drain cocks must be installed at the lowest points in the system to allow complete emptying B An automatic bypass with flow rate of at least 6 l min must be installed con nected as far away as possible from the boiler if radiators with the...

Page 5: ...e gas must be connected to the relevant connection see fig 29 in conformity with the current standards using a rigid metal pipe or a continuous surface flexible s steel tube and installing a gas cock between the system and boiler Make sure all the gas connec tions are tight 3 5 Electrical connections Important B The unit must be connected to an efficient earthing system in conformity with current ...

Page 6: ...he terminal length to size ensuring that the external pipe pro trudes from the wall by between 10 and 60 mm Remove the cutting burrs 5 Connect flue to the boiler positioning the seals correctly Seal the flue into the wall with silicone or sand cement and cover with wall seals provided A Flue seals should be lubricated with a silicone type grease to prevent damage grease not supplied Other coaxial ...

Page 7: ...meq No baffle C5x C3x B2x C1x max 50 cm Ø 81 Ø 81 Ø 65 Ø 87 Ø 65 041039X0 Losses in meq Air inlet Fume exhaust Vertical Horizontal Ø 80 PIPE 1 m M F 1KWMA83W 1 0 1 6 2 0 BEND 45 M F 1KWMA65W 1 2 1 8 90 M F 1KWMA01W 1 5 2 0 PIPE SECTION with test point 1KWMA70W 0 3 0 3 TERMINAL air wall 1KWMA85A 2 0 fumes wall with antiwind 1KWMA86A 5 0 FLUE Split air fumes 80 80 010027X0 12 0 Fume outlet only Ø80 ...

Page 8: ...to the disposal system fig 20 Condensate drain The condensate should be run inside as far as is practicably possible For that purpose use a pipe of at least 22 mm diameter and a trap with flexible connection supplied with the unit to facilitate connection of the condensate drain pipe The pipe must be in solvent weld plastic and not in copper since the condensate has a pH of 4 slightly acid If the ...

Page 9: ... integrity of the boiler combustion circuit and the relevant seals TEST mode activation Press the heating buttons details 3 and 4 fig 1 together for 5 seconds to activate the TEST mode The boiler lights at the maximum heating power set as described in the fol lowing section The heating and DHW symbols fig 22 flash on the display the heating power will be displayed alongside fig 22 TEST mode heatin...

Page 10: ...on system must be efficient with no leakage or obstructions The burner and exchanger must be clean and free of scale When cleaning do not use chemical products or wire brushes The electrode must be free of scale and properly positioned The gas and water systems must be leak free The water pressure in the heathing system must be about 1 bar otherwise bring it to that value The circulation pump must...

Page 11: ...pressures F07 Card parameter fault Wrong card parameter setting Check the card parameter and mod ify it if necessary A09 Gas valve fault Wiring disconnected Check the wiring Faulty gas valve Check the gas valve and replace it if necessary F10 Delivery sensor 1 fault Sensor damaged Check the wiring or replace the sen sor Wiring shorted Wiring disconnected F11 DHW sensor fault Sensor damaged Check t...

Page 12: ...et Ø 1 2 42 DHW temperature sensor 10 System delivery Ø 3 4 44 Gas valve 11 System return Ø 3 4 56 Expansion tank 14 Safety valve 81 Ignition and detection electrode 16 Fan 95 Diverter valve 19 Combustion chamber 114 Water pressure switch 22 Burner 126 Flue gas safety thermostat 27 Copper exchanger for heating and hot water 194 DHW exchanger 28 Fume manifold 241 Automatic bypass 32 Heating circula...

Page 13: ... 31 General view 5 3 Hydraulic circuit fig 32 Heating circuit fig 33 DHW circuit 277 27 19 14 36 114 81 32 11 38 37 9 39 7 44 8 42 10 95 194 22 278 28 56 16 5 126 16 277 126 56 27 14 32 38 11 10 8 9 95 241 42 114 36 194 278 16 277 126 56 27 14 32 38 11 10 8 9 95 241 42 114 36 194 278 ...

Page 14: ... 30 Hs 95 7 Hi 106 3 Hs 95 7 Hi 106 3 Burner nozzles G20 no x Ø 11 x 1 35 11 x 1 35 Gas inlet pressure G20 mbar 20 20 Max pressure at burner G20 mbar 11 13 5 Min pressure at burner G20 mbar 1 2 1 4 Nominal gas rate G20 m3 h 2 65 2 96 Minimum gas rate G20 m3 h 0 79 0 88 Burner nozzles G31 no x Ø 11 x 0 82 11 x 0 82 Gas inlet pressure G31 mbar 37 37 Max pressure at burner G31 mbar 29 35 Min pressure...

Page 15: ...ůů ůŽĂĚ ƚ ƉĂƌƚ ůŽĂĚ Ŷ ƐƚĂŶĚďLJ ŵŽĚĞ ƚĂŶĚďLJ ŚĞĂƚ ůŽƐƐ ŐŶŝƚŝŽŶ ďƵƌŶĞƌ ƉŽǁĞƌ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞŶĞƌŐLJ ĐŽŶƐƵŵƉƚŝŽŶ ŽƵŶĚ ƉŽǁĞƌ ůĞǀĞů ŵŝƐƐŝŽŶƐ ŽĨ ŶŝƚƌŽŐĞŶ ŽdžŝĚĞƐ ĞĐůĂƌĞĚ ůŽĂĚ ƉƌŽĨŝůĞ tĂƚĞƌ ŚĞĂƚŝŶŐ ĞŶĞƌŐLJ ĞĨĨŝĐŝĞŶĐLJ ĐůĂƐƐ ĂŝůLJ ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ tĂƚĞƌ ŚĞĂƚŝŶŐ ĞŶĞƌŐLJ ĞĨĨŝĐŝĞŶĐLJ ĂŝůLJ ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ dƌĂĚĞŵĂƌŬ hZKd ZD ŽŶĚĞŶƐŝŶŐ ďŽŝůĞƌ z ŽǁͲƚĞŵƉĞƌĂƚƵƌ...

Page 16: ...ůů ůŽĂĚ ƚ ƉĂƌƚ ůŽĂĚ Ŷ ƐƚĂŶĚďLJ ŵŽĚĞ ƚĂŶĚďLJ ŚĞĂƚ ůŽƐƐ ŐŶŝƚŝŽŶ ďƵƌŶĞƌ ƉŽǁĞƌ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞŶĞƌŐLJ ĐŽŶƐƵŵƉƚŝŽŶ ŽƵŶĚ ƉŽǁĞƌ ůĞǀĞů ŵŝƐƐŝŽŶƐ ŽĨ ŶŝƚƌŽŐĞŶ ŽdžŝĚĞƐ ĞĐůĂƌĞĚ ůŽĂĚ ƉƌŽĨŝůĞ tĂƚĞƌ ŚĞĂƚŝŶŐ ĞŶĞƌŐLJ ĞĨĨŝĐŝĞŶĐLJ ĐůĂƐƐ ĂŝůLJ ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ tĂƚĞƌ ŚĞĂƚŝŶŐ ĞŶĞƌŐLJ ĞĨĨŝĐŝĞŶĐLJ ĂŝůLJ ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ dƌĂĚĞŵĂƌŬ hZKd ZD ŽŶĚĞŶƐŝŶŐ ďŽŝůĞƌ z ŽǁͲƚĞŵƉĞƌĂƚƵƌ...

Page 17: ... losses A Boiler pressure losses 1 2 e 3 Circulating pump speed A B A B 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 35 30 25 20 15 10 5 kW mbar 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 35 30 25 20 15 10 5 kW mbar E29 MODEL E25 MODEL 0 0 5 1 1 5 2 2 5 6 5 4 3 2 1 0 A B Q l h H m H2O ...

Page 18: ...witch 42 DHW temperature sensor 44 Gas valve 62 Time clock not fitted 72 Room thermostat not fitted 81 Ignition and detection electrode 95 Diverting valve 114 Water pressure switch 126 Contact fume thermostat 138 External probe optional 139 Remote timer control not fitted 193 Trap 278 Double sensor Safety Heating 62 230V AUX 81 1kW L N 230V 50 Hz 16 N L 32 L N T T 278 T 42 4 3 2 1 44 38 114 ABM01 ...

Page 19: ......

Page 20: ...RQ WKH FRPPLVVLRQLQJ FKHFNOLVW DUH FRPSOHWHG LQ IXOO 7R YDOLGDWH WKH ERLOHU JXDUDQWHH WKH ERLOHU QHHGV WR EH UHJLVWHUHG ZLWK WKH PDQXIDFWXUHU ZLWKLQ RQH PRQWK RI WKH LQVWDOODWLRQ 7R PDLQWDLQ WKH ERLOHU JXDUDQWHH LW LV HVVHQWLDO WKDW WKH ERLOHU LV VHUYLFHG DQQXDOO E D DV 6DIH UHJLVWHUHG HQJLQHHU ZKR KDV EHHQ WUDLQHG RQ WKH ERLOHU LQVWDOOHG 7KH VHUYLFH GHWDLOV VKRXOG EH UHFRUGHG RQ WKH HQFKPDUN 6HUY...

Page 21: ...ed 1RW UHTXLUHG RLOHU LQWHUORFN 3URYLGHG ALL SYSTEMS 7KH V VWHP KDV EHHQ ÀXVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG ERLOHU PDQXIDFWXUHU V LQVWUXFWLRQV Yes KDW V VWHP FOHDQHU ZDV XVHG KDW LQKLELWRU ZDV XVHG 4XDQWLW OLWUHV DV D SULPDU ZDWHU V VWHP OWHU EHHQ LQVWDOOHG Yes 1R CENTRAL HEATING MODE PHDVXUH DQG UHFRUG DV UDWH Pñ KU OR IWñ KU XUQHU RSHUDWLQJ SUHVVXUH LI DSSOLFDEOH mbar OR DV LQOHW SUHVVX...

Page 22: ... 2 SSP AND 2 W PLQ UDWH 2 SSP AND 2 0 0 3BUJP NJO SBUF RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH 2 SSP AND 2 0 0 3BUJP NJO SBUF RPPHQWV 6LJQDWXUH SERVICE 05 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH 2 SSP AND 2 0 0 3BUJP NJO SBUF RPPHQWV 6LJQDWXUH SERVI...

Page 23: ... PUFT OO LQVWDOODWLRQV LQ QJODQG DQG DOHV PXVW EH QRWL HG WR RFDO XWKRULW XLOGLQJ RQWURO HLWKHU GLUHFWO RU WKURXJK D RPSHWHQW 3HUVRQV 6FKHPH XLOGLQJ 5HJXODWLRQV RPSOLDQFH HUWL FDWH ZLOO WKHQ EH LVVXHG WR WKH FXVWRPHU HDWLQJ DQG RWZDWHU QGXVWU RXQFLO ...

Page 24: ...Centre on 0843 479 0479 Calls to these numbers are charged at National Rate from BT landlines Calls made from mobile networks may be considerable more Phone numbers Installer Service Engineer BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS ALL SPECIFICATIONS SUBJECT TO CHANGE Please note to avoid incurring unnecessary expense in t...

Reviews: