background image

Trouble shooting 

1. Fire will not burn - check 

a)  the air inlet is not obstructed in any way, 
b)  that chimneys and flueways are clear, 
c)  that a suitable fuel is being used, 
d)  that there is an adequate air supply into the room, 
e)  that an extractor fan is not fitted in the same room as the 

fire.

 

2. Fire blazing out of control - check

 

a) 

the doors are tightly closed, 

b)  the air control is turned down to the minimum setting, 
c)  the air inlet damper is closed and that it is not prevented from closing completely by a piece of ash, 
d)  a suitable fuel is being used, 
e)  the door seals are in good condition. 
f)  the chimney draft may be too strong 
g)  ash pan seal   
h) for ash below ash pan causing pan to not seat correctly and clean out. 

3) Soot forms on the window 

a)

 

The firewood may be too wet 

b)

 

the intake of secondary air may be insufficient 

c)

 

fire not hot enough 

4) The stove fails to heat fully 

a)

 

The firewood may be too wet 

b)

 

the intake of secondary air may be insufficient 

5) Smoke or odour 

a)

 

Weak chimney draft 

b)

 

check for blockages in the flue pipe/chimney 

c)

 

check the height of the chimney in relation to the surroundings 

6) Soot in the chimney 

a)

 

The firewood may be too wet 

b)

 

intake of secondary air may be insufficient 

 
Chimney Fires 

If the chimney is thoroughly and regularly swept, chimney fires should not occur.  However, if a chimney 
fire does occur turn the air control setting to the minimum, and tightly close the doors of the stove.  This 
should cause the chimney fire to go out in which case the control should be kept at the minimum setting 
until the fire in the stove has gone out.  The chimney and flue ways should then be cleaned.  If the chimney 
fire does not go out when the above action is taken then the fire brigade should be called immediately. 
After a chimney fire the chimney should be carefully examined for any damage.  Expert advice should be 
sought if necessary 
 

Permanent air vent 

The stove requires a permanent air vent to the room or a direct connection to the closed air port at the 
rear  of  the  stove.  This  is  to  provide  adequate  air  supply  in  order  for  the  stove  to  operate  safely  and 
efficiently. 
In accordance with current Building Regulations the installer may have fitted a permanent air supply vent 
into the room in which the stove is installed to provide combustion air. This air vent should not under any 
circumstances be shut off or sealed. 

 

 

 

Summary of Contents for WESTFIRE UNIQ 32

Page 1: ...ng operation a glove is provided for use when the stove is hot We recommend that a guard should be used for the protection of the young elderly and vulnerable Do not burn rubbish or pre sawn treated t...

Page 2: ...rent Building Regulations Local Authority Byelaws and other specifications or regulations as they affect the installation of the stove It should be noted that the Building Regulations requirements may...

Page 3: ...ore than 160 mm x 160 mm Remedial action should be taken if required seeking expert advice If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be used in accord...

Page 4: ...WF 23 UNIQ 23 BUILDERS APERTURE SIZE WF 32 UNIQ 32 BUILDERS APERTURE SIZE WF23 UNIQ 23 WF 32 UNIQ 32 DOOR REMOVAL Narrow frame model Wide frame model 420mm...

Page 5: ...e back and sides with a 6 1 vermiculite to cement mix or any other good quality non combustible insulation material It is important that the back and sides of the stove are well insulated VII Connect...

Page 6: ...guidance on the separation of combustible material given in Building Regulations Approved Document J and also in these stove instructions WF32 UNIQ32 INSET WF23 UNIQ23 INSET Distance to combustible ma...

Page 7: ...to each side measuring from the door of the combustion chamber Combustion air supply In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in w...

Page 8: ...WESTFIRE WF23 UNIQ 23 INSET MODEL...

Page 9: ...WESTFIRE WF32 UNIQ 32 INSET NARROW FRAMED MODEL 405mm 810 00mm...

Page 10: ...WESTFIRE WF32 UNIQ 32 INSET WIDE FRAMED MODEL...

Page 11: ...be replaced Commissioning and handover Ensure loose parts are fitted in accordance with the instructions given in the instruction booklet On completion of the installation allow a suitable period of...

Page 12: ...using paper To light your stove 1 Place a few smaller pieces of dry wood kindling in the stove on top of the non toxic firelighters place one or two small dry split split logs on top 2 Fully slide op...

Page 13: ...to nominal temperature Basic Positions of dampers during operation nominal Secondary air Primary air WF23 UNIQ 23 60 open closed WF 32 UNIQ 32 30 open closed You will need to become familiar with you...

Page 14: ...n WESTFIRE WF 32 UNIQ32 INSET CONTROLS on WESTFIRE WF 23 UNIQ 23 INSET Door operation When opening the door of your Westfire stove always wear the glove that is provided to protect your hand from poss...

Page 15: ...stoves need to have the ash removed from the stove at regular intervals Make sure the stove is completely cold before cleaning out ash embers can remain hot for over 24 hours To clean the outside of t...

Page 16: ...wn Brick 1 is held in place with a steel pin Left right mid baffle bricks 2 3 positioned with full angled edge at front and part angled edge on the outside Bricks 2 3 need to be fitted lower down and...

Page 17: ...is then supported by left side brick 6 Front base brick 11 fitted Right base brick 7 positioned Right side brick 8 positioned on top of right base brick 7 Right mid baffle brick 3 must be held up to e...

Page 18: ...FIRE BRICK INSTALLATION SEQUENCE WESTFIRE UNIQ 23 continued Grate 13 fitted Log retainer 14 fitted Grate support 12 fitted...

Page 19: ...1 Outer Top Baffle Brick 2 Left Angled Side Brick 3 Right Angled Side Brick 4 Rear Brick 5 Left Side Brick 6 Right Side Brick 7 Left Base Brick 8 Right Base Brick 9 Rear Base Brick 10 Front Base Brick...

Page 20: ...ck 7 fitted Right base brick 8 fitted Rear base brick 9 fitted Front base brick 10 fitted Base grate 11 fitted Log retainer 12 fitted Inner top baffle brick 13 Angled parallel edge at rear resting on...

Page 21: ...n relation to the surroundings 6 Soot in the chimney a The firewood may be too wet b intake of secondary air may be insufficient Chimney Fires If the chimney is thoroughly and regularly swept chimney...

Page 22: ...prior to lighting up after a prolonged shutdown period If the stove is fitted in place of an open fire then the chimney should be swept one month after installation to clear any soot falls which may...

Reviews: