10 seconds for the setting to stop blinking. 
Setting windows are numbered for convenient operation of the controller. 
The user can change the following parameters:

 

1.

 

Boiler target temperature

 

It is the temperature of the boiler to be maintained by the controller.

 

2.

 

Hysteresis of the blower operation

 

This is a temperature range in which the  controller linearly adjusts the blower power. 
The narrower the temperature range, the smaller the system temperature fluctuations. 
However, a too narrow range may result in the temperature oscillation 

 the controller 

will alternately heat up and cool down the boiler. 
At the time of installation, set the maximum hysteresis value. Then wait for the system 
to  reach  the  preset  temperature.  If,  under  such  conditions,  the  blower  operates  at  a 
power level between settings No. (3) and (4), the hysteresis may be reduced. 

 

3.

 

Minimum power of the blower

 

This is the lowest power at which the blower may operate. It should be set at minimum 
value  at  which  the  blower  rotor  starts  to  rotate.  This  value  should  be  selected 
experimentally using the blower test function (setting No. 11).

 

4.

 

Maximum power of the blower

 

This  is  the  highest  power  at  which  the  blower  may  operate.  The  value  should  be 
selected experimentally so that the boiler temperature maintained by the controller is 
as close to the preset temperature as possible.

 

5.

 

Blow-through time

 

This is a period of the blower operation in the blow-through mode. The blower is turned 
on in order to remove combustion gases from the boiler. The blow-through time should 
be  long  enough  to  effectively  exhaust  the  gases  via  the  stack  and  short  enough  to 
prevent the boiler temperature rise.

 

6.

 

Time interval between successive blow-throughs

 

This is the time passing between the end of the blow-through cycle and the start of a 
new cycle. It should be set so that to prevent  the boiler temperature rise, but on the 
other hand to avoid explosive combustion of the gases generated in the boiler.

 

7.

 

CH pump operation temperature

 

The conditions of turning the pump on and off are specified in section 12.

 

8.

 

CH pump hysteresis

 

This is a differential temperature at which the controller turns the pump on and off. 
The conditions of turning the pump on and off are specified in section 12.

 

9.

 

Temperature readings correction

 

This is a value added to or subtracted from the measured temperature value. It enables 
to compensate for the difference in readings between the sensor placed on the pipe and 
the thermometer installed on the boiler.

 

10.

 

Shutdown temperature

 

This is a temperature below which the controller turns the boiler off (the boiler furnace 
is most probably shut down). A too high shutdown temperature preset may cause the 
controller to turn the boiler off by mistake.

 

11.

 

Blower operation / test

 

Displays  the  current  status  of  the  blower  calculated  by  the  controller  (0-100 %). 
Press  the  knob  to  activate  testing  of  the  output.  Press  the  knob  again  or  leave  it 
inactive for 10 seconds to resume automatic operation.

 

12.

 

Pump operation / test

 

Displays the current status of the pump calculated by the controller (0 or 1).

 

Press the knob to activate testing of the output. Press the knob again or leave it 
inactive for 10 seconds to resume automatic operation.

 

ATTENTION: In case the set values preclude the correct operation of the controller, 
the alarm icon will appear on the display, and the colliding settings will be displayed 
alternately. After a few seconds the last correct configuration is restored.

 

 

Summary of Contents for 11W

Page 1: ...urnace and controls the operation of the CH circulation pump EUROSTER 11W controller is equipped with an ANTI STOP function that prevents seizing of an idle pump rotor It automatically turns the pump...

Page 2: ...n the boiler in a point specially designed for that purpose or on an unshielded outlet pipe of the CH boiler as close to the boiler as possible using hose clip tighten the sensor to the pipe and cover...

Page 3: ...ter displayed while previewing or changing the setting 2 Boiler temperature sensor icon 3 Manual operation mode icon lit while the temperature is manually adjusted 4 Alarm icon blinks in case of alarm...

Page 4: ...select the number 0 or 1 and confirm Selecting 0 enables to change screen backlight functions without restoring factory defaults Selecting 1 restores factory settings bl Backlight will be displayed an...

Page 5: ...gh to prevent the boiler temperature rise 6 Time interval between successive blow throughs This is the time passing between the end of the blow through cycle and the start of a new cycle It should be...

Page 6: ...t then press it and hold down until the blower is started turn the controller power off and on Firing up is terminated if the boiler temperature is lower than the set temperature 1 by at most a half o...

Page 7: ...The CH pump is turned off if the boiler temperature drops below the preset value by a half of the preset hysteresis T boiler TCH HCH 2 Power Alarm Temperature In case the temperature measured by the...

Page 8: ...oad 2 A 230 V 50 Hz Maximum blower output load 0 5 A 230 V 50 Hz Maximum power consumption 1 6 W Temperature measurement range from 5 C to 110 C CH temperature adjustment range from 20 C to 80 C Boile...

Page 9: ...e every effort to ensure that this controller lifetime is as long as possible However the device is subject to natural wear If the device would not meet your requirements any more you are kindly reque...

Page 10: ...y by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unauthor...

Reviews: