LUBE-MASTER R10
4(16)
Reel:SETUP ‡
EXIT STOP CE ENT
PASS:_
‡
Enter password
Adr:2???_
‡
Address[code]
PM:
‡
PM MainMenu
5. Configuration
An LUBE-Master configuration sheet
should
always be filled or altered during the configuration.
NOTE! To obtain technical support a copy of the configuration sheet for the complete installation must be
sent to Alentec & Orion AB at
E-mail:
Post:
Alentec & Orion AB
LUBE-Master Support Team
Grustagsvägen 4
SE-138 40 Älta
SWEDEN
5.1. Check before configuration
Check that the PM is working and communicating with the system according to the
LUBE-Master Manual
chapter "Testing modules".
NOTE! Do not forget to check and adjust the termination and BIAS according to LUBE-Master Manual.
5.2. Addressing the new module
A new module has no address on delivery. To address a new module or one with an unknown address you press and
hold the RESET-button for 5 seconds. This will give the module a temporary address. Next, enter SET-UP-mode on
a KeyPad and press 0 + ENTER to access the Main menu of the module. Find the menu to change module-address
(see below).
NOTE! You can only install one module at a time using this method. If you hold the RESET-button on
multiple units simultaneously only the most recently activated is active.
TIP!
Follow preferably ”Recommendation for setting addresses” when setting addresses.
5.3. Important information for modules equipped with FLASH chip.
When we changed from OTP chip (One Time Programmable, white label) to FLASH chip technology we also
added functions that could not be used with OTP chip.
5.3.1. Reports based on a time period.
If you have a printer module already equipped with a FLASH chip or is updating an old one to FLASH chip you
should also add the choices for setting Start Date and End Date in the Fast Menu of a suitable key pad. Fast
menu codes for this can be found in chapter “10. Fast Menu Codes”.
To be able to have report print out the Start Date and End Date must be set so the report period contain
something to print.
The Start Date and End Date could also be set from the basic PM graphic symbol on the PC.
5.3.2. Full report customisation possibility.
The possibility for report customisation was rather limited in the OTP chip version due to lack of program
memory. The FLASH version has a much larger program memory so for printer modules with FLASH chip the
support for report design has been improved a lot.
To make use of this the foundation for the report design must be initialized
properly. Clicking the “Load default” button of the basic PM graphic symbol
on the PC does this.
5.4. SET-UP mode
Type the word ”
SETUP
” on a Keypad and press
ENTER
.
Type the password and press
ENTER
.
Type the address of the LED you want to configure and press
ENTER
to access
its main menu.
You can add the 4-digit menu code to go directly to the desired menu.