EUCHNER STP-TW AS1 Series Operating Instructions Manual Download Page 6

6

Operating Instructions

Safety Switch STP-TW…AS1 (Twin) 

Correct use

Safety switches series STP‑TW…AS1 are operated 

as slaves on the safety bus AS‑Interface Safety 

at Work and function as interlocking devices with 

guard locking (separate actuator). The actuator has 

a low coding level. In combination with a movable 

safety guard and the machine control, this safety 

component prevents the safety guard from being 

opened while a dangerous machine function is 

being performed.
This means:

 

f

Starting commands that cause a dangerous ma‑

chine function must become active only when the 

safety guard is closed and locked.

 

f

The guard locking device must not be unlocked 

until the dangerous machine function has ended.

 

f

Closing and locking a safety guard must not cause 

automatic starting of a dangerous machine func‑

tion. A separate start command must be issued. 

For exceptions, refer to EN ISO 12100 or relevant 

C‑standards.

Devices from this series are also suitable for process 

protection.
Before the device is used, a risk assessment must 

be performed on the machine, e.g. in accordance 

with the following standards:

 

f

EN ISO 13849‑1, Safety of machinery – Safety‑re‑

lated parts of control systems – Part 1: General 

principles for design

 

f

EN  ISO  12100, Safety of machinery – General 

principles for design – Risk assessment and risk 

reduction

 

f

IEC  62061, Safety of machinery – Functional 

safety of safety‑related electrical, electronic and 

programmable electronic control systems

Correct use includes observing the relevant require‑

ments for installation and operation, particularly 

based on the following standards:

 

f

EN ISO 13849‑1, Safety of machinery – Safety‑re‑

lated parts of control systems – Part 1: General 

principles for design

 

f

EN ISO 14119 (supersedes EN 1088), Safety of 

machinery – Interlocking devices associated with 

guards – Principles for design and selection

 

f

EN  60204‑1, Safety of machinery – Electrical 

equipment of machines – Part 1: General re‑

quirements

Important!

 

f

The user is responsible for the proper integration 

of the device into a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. in accordance with EN ISO 13849‑2.

 

f

If the simplified method according to section 6.3 

of EN ISO 13849‑1:2008 is used for determining 

the Performance Level (PL), the PL might be re‑

duced if several devices are connected in series.

 

f

Logical series connection of safe contacts is 

possible up to PL  d in certain circumstances. 

More information about this is available in 

ISO TR 24119.

 

f

If a product data sheet is included with the prod‑

uct, the information on the data sheet applies 

in case of discrepancies with the operating 

instructions.

Safety precautions

 WARNING

Danger to life due to improper installation or due 

to bypassing (tampering). Safety components 

perform a personal protection function.

 

f

Safety components must not be bypassed, 

turned away, removed or otherwise rendered 

ineffective. On this topic pay attention in partic‑

ular to the measures for reducing the possibility 

of bypassing according to EN ISO 14119:2013, 

section 7.

 

f

The switching operation must be triggered only 

by actuators designated for this purpose.

 

f

Prevent bypassing by means of replacement 

actuators. For this purpose, restrict access to 

actuators and to keys for releases, for example.

 

f

A complete safety‑oriented system generally 

consists of several signaling devices, sensors, 

evaluation units and concepts for safe shutdown. 

The manufacturer of a machine or installation is 

responsible for correct and safe overall function.

 

f

All safety precautions and requirements stated 

in the operating instructions of the AS‑Interface 

safety monitor used must be observed.

 

f

Mounting, electrical connection and setup only 

by authorized personnel possessing special 

knowledge about handling safety components.

 CAUTION

Danger due to high housing temperature at ambi‑

ent temperatures above 40 °C.

 

f

Protect switch against touching by personnel or 

contact with inflammable material.

Function

Safety switches series STP‑TW...AS1 (Twin) have 

two actuator heads. They permit the simultaneous 

locking or unlocking of two movable safety guards.
Both actuators must be inserted in order to activate 

guard locking.
In the switch head there is a rotating cam that is 

blocked/released by the guard locking pin.
The guard locking pin is moved on the insertion/

removal of the actuators and on the activation/

release of the guard locking. During this process 

the switching contacts are actuated.
If the cam is blocked (guard locking active), the 

actuators cannot be pulled out of the switch head. 

For design reasons, guard locking can be activated 

only when the safety guard is closed (failsafe locking 

mechanism).
Position monitoring of the safety guard and monitor‑

ing of interlocking are performed via two separate 

switching elements (door monitoring contact SK and 

solenoid monitoring contact ÜK).
When the safety guard is closed and guard locking 

effective, each STP‑TW...AS1 transmits a switch‑spe‑

cific, unique safety code sequence with 8 x 4 bits 

via the AS‑Interface bus. This code sequence is 

evaluated by an AS‑Interface safety monitor. The 

positively driven contact SK for door monitoring is 

represented by the AS‑Interface input bits D0 and 

D1. The solenoid monitoring contact ÜK is repre‑

sented by the AS‑Interface input bits D2 and D3.
The safety switch must be correspondingly config‑

ured in the AS‑Interface safety monitor (refer to the 

operating instructions of the AS‑Interface safety 

monitor used and the status table).
The safety switch is designed so that fault exclusions 

for internal faults in accordance with EN ISO 13849 

2:2013, Table A4, can be assumed.

Version STP-TW3…AS1

(guard locking actuated by spring force and released 

by energy ON)

Important!
For the purpose of the protection of people against 

dangerous over‑traveling movements, it can also 

be necessary to switch the black AS‑Interface 

cable (auxiliary power), which is connected to 

the AS‑Interface distribution box and the switch, 

via a standstill monitor or via the safe switch‑on 

delay feature in a dual‑channel AS‑Interface safety 

monitor (e.g. door locking for duration of the time 

delay).

 

f

Activating guard locking: Close safety guard; no 

voltage at the solenoid and/or clear AS‑Interface 

output bit D0

 

f

Releasing guard locking: Apply voltage to the 

solenoid and set AS‑Interface output bit D0

The spring‑operated guard locking functions in 

accordance with the closed‑circuit current princi‑

ple. If voltage is interrupted at the solenoid, guard 

locking remains active and the safety guard cannot 

be opened directly.
If the safety guard is open when the power supply 

is interrupted and the guard is then closed, guard 

locking is activated. This can lead to persons being 

locked in unintentionally.

Version STP-TW4…AS1

(guard locking actuated by energy ON and released 

by spring force)

Important!
Use as guard locking for personnel protection is 

possible only in special cases, after strict assess‑

ment of the accident risk (see EN ISO 14119:2013, 

section 5.7.1)!

 

f

Activating guard locking: Apply voltage to the 

solenoid and set AS‑Interface output bit D0

 

f

Releasing guard locking: Disconnect voltage from 

the solenoid or clear AS‑Interface output bit D0

The magnetically actuated guard locking operates in 

accordance with the open‑circuit current principle. If 

the voltage at the solenoid is interrupted, the guard 

locking is released and the safety guard can be 

opened directly!

Switching states

The detailed switching states and code sequences 

for your switch can be found in the status table.

Selection of the actuator

NOTICE

Damage to the device due to unsuitable actuator. 

Make sure to select the correct actuator (see 

table in Figure 4).
Additionally pay attention to the door radius and 

the fastening options (see Figure 5).

The following versions are available:

 

f

Actuator S for safety switches without insertion 

funnel.

Manual release

Some situations require guard locking to be released 

manually (e.g. malfunctions or an emergency). A 

function test should be performed after release.
More information on this topic can be found in the 

standard EN ISO 14119:2013, section 5.7.5.1. The 

device can feature the following release functions:

Auxiliary release

In the event of malfunctions, the guard locking can 

be released with the auxiliary release irrespective 

of the state of the solenoid.
The half‑sequence is sent with the auxiliary release 

actuated.

Summary of Contents for STP-TW AS1 Series

Page 1: ...egeln von zwei be weglichen Schutzeinrichtungen Zum Aktivieren der Zuhaltung müssen beide Betätiger eingeführt werden Im Schalterkopf befindet sich eine drehbare Schalt walze die durch den Zuhaltebolzen blockiert freigegeben wird Beim Einführen Herausziehen der Betätiger und beim Aktivieren Entsperren der Zuhaltung wird der Zuhaltebolzen bewegt Dabei werden die Schaltkon takte betätigt Bei blockie...

Page 2: ...kverbinder Sicherheitsschalter 4 3 1 2 Bild 3 Anschlussbelegung M12 Steckverbinder Für Geräte mit Steckverbinder gilt f f Auf Dichtheit des Steckverbinders achten Inbetriebnahme Einstellen der AS Interface Adresse Das Einstellen der Adresse ist vor oder nach der Montage möglich Die AS Interface Adresse des Sicherheitsschalters wird mit einem AS Interface Programmiergerät ein gestellt Adresse 1 bis...

Page 3: ...ng gemäß den Anforderungen von UL muss ein Trenntransfor mator oder eine Spannungsversorgung mit sekundär em Überstromschutz 3 A verwendet werden EG Konformitätserklärung Der nachstehende Hersteller erklärt hiermit dass das Produkt in Übereinstimmung mit den Bestimmungen der nachfolgend aufgeführten Richtlinie n ist und dass die jeweiligen Normen zur Anwendung gelangt sind EUCHNER GmbH Co KG Kohlh...

Page 4: ...lten Halbfolge 00 Rot Ungültiger Zustand Schutzeinrichtung offen Zuhaltung aktiv 00 Halbfolge Rot Schutzeinrichtung geöffnet 00 00 Rot Adresse 0 oder Kommunikation gestört Grau 2 kanalig abhängig Synchronisationszeit unendlich Schutzeinrichtung geschlossen und zugehalten Codefolge Grün wenn Schutzeinrichtung zuvor geöffnet war oder nach Anlauf gelb blinkend wenn nur Zuhaltung geöffnet war Schutzei...

Page 5: ...3 2x für M5 x 35 mm ISO 1207 ISO 4762 M 0 8 Nm Ø 5 3 2x für M5 x 35 mm ISO 1207 ISO 4762 Diese Befestigungs bohrungen nicht verwenden Schlüsselhilfsentriegelung Sicherungs schraube Hilfsentriegelung Hilfsentriegelung mit Dreikant 2 Dreikantschlüssel beigelegt 1 0 0 0 26 38 33 Mit Bowdenzugentriegelung Bild 5 Minimale Türradien Betätiger Türradius min mm Betaetiger S G 300 Betaetiger S W 300 Radius...

Page 6: ...locking of two movable safety guards Both actuators must be inserted in order to activate guard locking In the switch head there is a rotating cam that is blocked released by the guard locking pin The guard locking pin is moved on the insertion removal of the actuators and on the activation release of the guard locking During this process the switching contacts are actuated If the cam is blocked g...

Page 7: ... 4 Auxiliary voltage24V View of safety switch plug connector 4 3 1 2 Figure 3 Terminal assignment M12 plug connector The following information applies to devices with plug connector f f Check that the plug connector is sealed Setup Setting the AS Interface address The address can be set prior to or after assembly The AS Interface address of the safety switch is set using an AS Interface programmin...

Page 8: ... declaration of conformity The manufacturer named below herewith declares that the product fulfills the provisions of the direc tive s listed below and that the related standards have been applied EUCHNER GmbH Co KG Kohlhammerstr 16 D 70771 Leinfelden Echterdingen Directives applied f f Machinery directive 2006 42 EC Standards applied f f EN 60947 5 1 2004 Cor 2005 A1 2009 f f EN 1088 1995 A2 2008...

Page 9: ...t locked Half sequence 00 Red Invalid state safety guard open guard locking active 00 Half sequence Red Safety guard open 00 00 Red Address 0 or communication disrupted Gray Dual channel dependent Synchronization time infinite Safety guard closed and locked Code sequence Green if safety guard was previously open or yellow flashing after startup if only the guard locking was open Safety guard close...

Page 10: ...ard locking ready for operation Guard locking released Ø 5 3 2x for M5 x 35 mm ISO 1207 ISO 4762 M 0 8 Nm Ø 5 3 2x for M5 x 35 mm ISO 1207 ISO 4762 Do not use these mounting holes Mechanical key release Locking screw Auxiliary release Auxiliary release with triangular key 2 triangular keys included 1 0 0 0 26 38 33 With wire front release Figure 5 Minimum door radii Actuator Door radius min mm Act...

Reviews: