Electrical function test

1.  Switch on operating voltage.
2.  Close all guards.

 

¨

The machine must not start automatically.

3.  Start the machine function.
4.  Open the guard.

 

¨

The machine must switch off and it must not be 

possible to start it as long as the guard is open.

Repeat steps 2 - 4 for each guard.

Inspection and service

 WARNING

Danger of severe injuries due to the loss of the 

safety function.

 

f

If damage or wear is found, the complete switch 

and actuator assembly must be replaced. Re-

placement of individual parts or assemblies is 

not permitted.

 

f

Check the device for proper function at regular 

intervals and after every fault. For informa-

tion about possible time intervals, refer to 

EN ISO 14119:2013, section 8.2.

Inspection of the following is necessary to ensure 

trouble-free long-term operation:

 

f

correct switching function

 

f

secure mounting of all components

 

f

damage, heavy contamination, dirt and wear

 

f

sealing of cable entry

 

f

loose cable connections or plug connectors.

Info

: The year of manufacture can be seen in the 

bottom, right corner of the type label.

Exclusion of liability and warranty

In case of failure to comply with the conditions for 

correct use stated above, or if the safety regula-

tions are not followed, or if any servicing is not 

performed as required, liability will be excluded and 

the warranty void.

Notes about 

The following information applies to devices 
with cable entry:

For use and application as per the requirements 
of 

 a copper wire for the temperature range 

60/75 °C must be used.

The following information applies to devices 

with plug connector:

This device is intended to be used and applied with 

a Class 2 power source in accordance with UL1310. 

Connecting cables for safety switches installed at 

the place of use must be separated from all moving 

and permanently installed cables and un-insulated 

active elements of other parts of the system that 

operate at a voltage of over 150  V. A constant 

clearance of 50.8 mm must be maintained. This 

does not apply if the moving cables are equipped 

with suitable insulation materials that possess an 

identical or higher dielectric strength compared to 

the other relevant parts of the system.

EU declaration of conformity 

The declaration of conformity is part of the operating 

instructions, and it is included as a separate sheet 

with the device. 
The original EU declaration of conformity can also 

be found at: www.euchner.com

Service

If servicing is required, please contact:
EUCHNER GmbH + Co. KG

Kohlhammerstraße 16

70771 Leinfelden-Echterdingen

Service telephone

:

+49 711 7597-500

E-mail

:

[email protected]

Internet

:

www.euchner.com

Technical data

Parameter

Value

Housing material

Reinforced thermoplastic

Degree of protection  

acc. to IEC 60529

SGP1… (cable entry)

SGP2… (plug connector)

IP67

IP65

Mechanical life

2 x 10

6

 operating cycles

Ambient temperature

-20 … +80 °C

Degree of contamination

(external, acc. to EN 60947-1) 3 (industrial)
Installation orientation

Any

Approach speed, max.

20 m/min

Extraction force

25 N

Retention force

10 N

Actuating force, max.

25 N

Actuation frequency

6,700/h

Switching principle

Slow-action switching contact

Contact material

Silver alloy, gold flashed

Connection

SGP1…

SGP2…SR6

SGP2…SR11

Cable entry M20 x 1.5

Plug connector SR6, 6-pin+PE

Plug connector SR11, 11-pin+PE

Conductor cross-section 

(flexible/rigid)

SGP1…

SGP2…SR6

SGP2…SR11

0.34 … 1.5 mm²

0.5 … 1.5 mm²

0.5 mm²

Operating voltage for optional 

LED indicator

(only SGP…538H)

L060  12 - 60 V

L110  110 V

L220  230 V

Conditional short-circuit 

current

100 A

Switching voltage, min.,

at 10 mA

12 V

Switching current, min., at 24 V 1 mA
Short circuit protection 

(control circuit fuse)  

acc. to IEC 60269-1

4 A gG

Convent. thermal current I

th

4 A

Utilization category  

acc. to EN 60947-5-1

SGP1…/ 

SGP2…SR6

SGP2…SR11

AC-15

4 A 230 V

4 A 50 V

DC-13

4 A 24 V

4 A 24 V

Rated insulation voltage

U

i

 = 250 V

U

i

 = 50 V

Rated impulse withstand 

voltage

U

imp

 = 2.5 kV

U

imp

 = 1.5 kV

Reliability values acc. to EN ISO 13849-1

B

10D

at DC-13 100 mA/24 V

3 x 10

6

Summary of Contents for SGP Series

Page 1: ...die Schaltkontakte betätigt Schaltzustände Die detaillierten Schaltzustände für Ihren Schalter finden Sie in Bild 2 Dort sind alle verfügbaren Schal telemente beschrieben Schutzeinrichtung geöffnet Die Sicherheitskontakte sind geöffnet Schutzeinrichtung geschlossen Die Sicherheitskontakte sind geschlossen Auswahl des Betätigers HINWEIS Schäden am Gerät durch ungeeigneten Betätiger Achten Sie darau...

Page 2: ...schlussleitungen von Si cherheitsschaltern müssen räumlich von beweglichen und fest installierten Leitungen und nicht isolierten aktiven Teilen anderer Anlagenteile die mit einer Span nung von über 150 V arbeiten so getrennt werden dass ein ständiger Abstand von 50 8 mm eingehalten wird Es sei denn die beweglichen Leitungen sind mit geeigneten Isoliermaterialien versehen die eine gleiche oder höhe...

Page 3: ...2 12 12 22 42 34 14 22 42 34 11 12 22 21 22 12 21 11 41 42 34 33 33 41 21 11 22 21 11 12 12 11 21 22 11 21 41 33 33 34 42 41 14 13 21 22 13 21 41 33 33 34 42 41 Tür geschlossen Tür offen Kontaktbelegung mit Steckverbinder SR6 freiverdrahtbare LED Anzeige optional Ordungsziffer der Schaltelemente Ordungsziffer der Schaltelemente Steckerbild Steckverbinder SR6 Ansicht Steckseite Sicherheitsschalter ...

Page 4: ...200 28 5 5 16 4 30 35 50 R 200 20 26 12 24 5 5 35 50 R 200 20 R 200 35 24 5 5 R 200 4 39 29 5 5 Bild 3 Maßzeichnung SGP ohne Einführtrichter und SGP mit Einführtrichter 40 30 31 3 4 1 5 1 V M 0 5Nm 16 35 5 41 5 123 42 4 32 30 22 16 M 0 6Nm h 0 5 A 0 5 B 28 A B 4 9 V 4 19 19 4 h 0 5 35 5 45 5 30 127 4 16 9 4 M 1 5Nm 0 5 L fixierte Positionierung für Sicherheitsanwendungen Schraube M5 optionale LED ...

Page 5: ...be found in Fig 2 All available switching elements are described there Guard open The safety contacts are open Guard closed The safety contacts are closed Selection of the actuator NOTICE Damage to the device due to unsuitable actuator Make sure to select the correct actuator see table in Fig 4 Additionally pay attention to the door radius and the mounting options see Fig 4 The following versions ...

Page 6: ...er parts of the system that operate at a voltage of over 150 V A constant clearance of 50 8 mm must be maintained This does not apply if the moving cables are equipped with suitable insulation materials that possess an identical or higher dielectric strength compared to the other relevant parts of the system EU declaration of conformity The declaration of conformity is part of the operating instru...

Page 7: ... 14 22 42 34 11 12 22 21 22 12 21 11 41 42 34 33 33 41 21 11 22 21 11 12 12 11 21 22 11 21 41 33 33 34 42 41 14 13 21 22 13 21 41 33 33 34 42 41 Door closed Door open Terminal assignment with plug connector SR6 LED indicator with full wiring options optional Ordinal numbers of switching elements Ordinal numbers of switching elements Connector illustration Plug connector SR6 View of safety switch c...

Page 8: ... 200 Hinged actuator S LR 200 28 5 5 16 4 30 35 50 R 200 20 26 12 24 5 5 35 50 R 200 20 R 200 35 24 5 5 R 200 4 39 29 5 5 Fig 3 Dimension drawing for SGP without insertion funnel and SGP with insertion funnel 40 30 31 3 4 1 5 1 V M 0 5Nm 16 35 5 41 5 123 42 4 32 30 22 16 M 0 6Nm h 0 5 A 0 5 B 28 A B 4 9 V 4 19 19 4 h 0 5 35 5 45 5 30 127 4 16 9 4 M 1 5Nm 0 5 L Fixed positioning for safety applicat...

Page 9: ...os de conmutación Estados de conmutación Los estados de conmutación detallados de los interruptores se muestran en la Fig 2 También se describen todos los elementos de conmutación disponibles Resguardo abierto Los contactos de seguridad están abiertos Resguardo cerrado Los contactos de seguridad están cerrados Selección del actuador AVISO Daños en el dispositivo si se utiliza un actuador inadecuad...

Page 10: ...0 8 mm respecto a los cables móviles o fijos y los componentes activos no aislados de otras piezas de la instalación que funcionen con más de 150 V de tensión a menos que los cables móviles cuenten con un aislante adecuado que tenga una rigidez dieléctrica igual o superior en comparación con las demás piezas relevantes de la instalación Declaración de conformidad UE La declaración de conformidad f...

Page 11: ...2 34 14 22 42 34 11 12 22 21 22 12 21 11 41 42 34 33 33 41 21 11 22 21 11 12 12 11 21 22 11 21 41 33 33 34 42 41 14 13 21 22 13 21 41 33 33 34 42 41 Puerta cerrada Puerta abierta Asignación de contactos con conector SR6 indicador LED de cableado libre opcional Cifras asignadas a los elementos de conexión Cifras asignadas a los elementos de conexión Imagen de contactos conector SR6 Vista del lado d...

Page 12: ...al S OU 200 Actuador radial S LR 200 28 5 5 16 4 30 35 50 R 200 20 26 12 24 5 5 35 50 R 200 20 R 200 35 24 5 5 R 200 4 39 29 5 5 Fig 3 Plano de dimensiones SGP sin embudo de entrada y SGP con embudo de entrada 40 30 31 3 4 1 5 1 V M 0 5Nm 16 35 5 41 5 123 42 4 32 30 22 16 M 0 6Nm h 0 5 A 0 5 B 28 A B 4 9 V 4 19 19 4 h 0 5 35 5 45 5 30 127 4 16 9 4 M 1 5Nm 0 5 L Posicionamiento fijo para aplica cio...

Page 13: ...rouverez les états de commutation détaillés pour votre interrupteur à la Fig 2 Tous les éléments de commutation disponibles y sont décrits Protecteur ouvert Les contacts de sécurité sont ouverts Protecteur fermé Les contacts de sécurité sont fermés Choix de l élément d actionnement AVIS Endommagement de l appareil par un élément d actionnement non approprié Veillez à sélection ner l élément d acti...

Page 14: ...s ou fixes et des autres composants actifs non isolés d une distance minimale de 50 8 mm si ceux ci présentent une tension supérieure à 150 V Ceci n est pas nécessaire si les câbles mobiles sont munis de matériaux isolants adaptés présentant une résistance diélectrique égale ou supérieure aux autres composants importants de l installation Déclaration UE de conformité La déclaration de conformité f...

Page 15: ...2 22 42 34 14 22 42 34 11 12 22 21 22 12 21 11 41 42 34 33 33 41 21 11 22 21 11 12 12 11 21 22 11 21 41 33 33 34 42 41 14 13 21 22 13 21 41 33 33 34 42 41 Porte fermée Porte ouverte Affectation des contacts avec connecteur SR6 indication par LED à câblage libre en option Numéro ordinal des éléments de commutation Numéro ordinal des éléments de commutation Brochage connecteur Connecteur SR6 vue côt...

Page 16: ...00 28 5 5 16 4 30 35 50 R 200 20 26 12 24 5 5 35 50 R 200 20 R 200 35 24 5 5 R 200 4 39 29 5 5 Fig 3 Dimensions SGP sans module d insertion et SGP avec module d insertion 40 30 31 3 4 1 5 1 V M 0 5Nm 16 35 5 41 5 123 42 4 32 30 22 16 M 0 6Nm h 0 5 A 0 5 B 28 A B 4 9 V 4 19 19 4 h 0 5 35 5 45 5 30 127 4 16 9 4 M 1 5Nm 0 5 L Positionnement fixe pour applica tions de sécurité vis M5 Indication par LE...

Reviews: