EUCHNER NZ.W Series Operating Instructions Manual Download Page 4

4

Operating Instructions

Safety Switch NZ.D.../NZ.W.../NZ.R...

Correct use

Safety switches series NZ are interlocking devices 

without guard locking (with safety function). The 

actuator is uncoded (e.g. dog). In combination with 

a movable safety guard and the machine control, 

this safety component prevents dangerous machine 

functions from occurring while the safety guard is 

open. A stop command is triggered if the safety 

guard is opened during the dangerous machine 

function.
This means:

 

f

Starting commands that cause a dangerous ma-

chine function must become active only when the 

safety guard is closed.

 

f

Opening the safety guard triggers a stop com-

mand.

 

f

Closing a safety guard must not cause automatic 

starting of a dangerous machine function. A 

separate start command must be issued. For 

exceptions, refer to EN  ISO  12100 or relevant 

C-standards.

Devices from this series can be used as safe position 

encoders.
Before the device is used, a risk assessment must 

be performed on the machine, e.g. in accordance 

with the following standards:

 

f

EN ISO 13849-1, Safety of machinery – Safety-re-

lated parts of control systems – Part 1: General 

principles for design

 

f

EN  ISO  12100, Safety of machinery – General 

principles for design – Risk assessment and risk 

reduction

 

f

IEC  62061, Safety of machinery – Functional 

safety of safety-related electrical, electronic and 

programmable electronic control systems

Correct use includes observing the relevant require-

ments for installation and operation, particularly 

based on the following standards:

 

f

EN ISO 13849-1, Safety of machinery – Safety-re-

lated parts of control systems – Part 1: General 

principles for design

 

f

EN ISO 14119, Safety of machinery – Interlocking 

devices associated with guards – Principles for 

design and selection

 

f

EN  60204-1, Safety of machinery – Electrical 

equipment of machines.

Important!

 

f

The user is responsible for the proper integration 

of the device into a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. in accordance with EN ISO 13849-2.

 

f

If the simplified method according to section 6.3 

of EN ISO 13849-1:2015 is used for determining 

the Performance Level (PL), the PL might be re-

duced if several devices are connected in series.

 

f

Logical series connection of safe contacts is 

possible up to PL  d in certain circumstances. 

More information about this is available in 

ISO TR 24119.

 

f

If a product data sheet is included with the prod-

uct, the information on the data sheet applies 

in case of discrepancies with the operating 

instructions.

Safety precautions

 WARNING

Danger to life due to improper installation or due 

to bypassing (tampering). Safety components 

perform a personal protection function.

 

f

Safety components must not be bypassed, 

turned away, removed or otherwise rendered 

ineffective. On this topic pay attention in partic-

ular to the measures for reducing the possibility 

of bypassing according to EN ISO 14119:2013, 

section 7.

 

f

Mounting, electrical connection and setup only 

by authorized personnel possessing special 

knowledge about handling safety components.

Function

Precision single limit switches are used for posi-

tioning and control applications in mechanical and 

systems engineering. 
The switching contacts are actuated when the actu-

ating element is moved from the free position to the 

end position. The safety contacts   are positively 

opened in this process (see Figure 2).

Switching states

The detailed switching states for your switch can be 

found in Figure 2. All available switching elements 

are described there.
Actuating element in free position
The safety contacts   are closed.
Actuating element in end position
The safety contacts   are open.

Mounting

NOTICE

Device damage due to improper mounting and 

unsuitable ambient conditions.

 

f

Safety switches and actuators must not be used 

as an end stop.

 

f

Observe EN ISO 14119:2013, sections 5.2 and 

5.3, for information about fastening the safety 

switch and the actuator.

 

f

Observe EN  ISO  14119:2013, section 7, for 

information about reducing the possibilities for 

bypassing an interlocking device.

 

f

Protect the switch head against damage.

Changing the actuating direction

Figure 1:  Changing the actuating direction

1.  Remove the screws from the actuating head.
2.  Set the required direction.
3.  Tighten the screws with a torque of 1.2 Nm.

Electrical connection

 WARNING

Loss of the safety function due to incorrect 

connection.

 

f

Use only safe contacts ( ) for safety functions.

Use of the safety switch as an interlocking 

device for personnel protection
At least one contact   must be used. This signals 

the position of the safety guard (for terminal assign-

ment, see Figure 2).
The following information applies to devices 

with plug connector:

 

f

Check that the plug connector is sealed.

The following information applies to devices 

with cable entry:
1.  Use a suitable tool to open the desired inser-

tion opening.

2.  Fit the cable gland with the appropriate degree 

of protection.

3.  Connect and tighten the terminals with 0.5 Nm 

(1 Nm on ES511) (for terminal assignment, 

see Figure 3).

4.  Check that the cable entry is sealed.
5.  Close the switch cover and screw in place 

(tightening torque 1.2 Nm).

Function test

 WARNING

Fatal injury due to faults during the function test.

 

f

Before carrying out the function test, make sure 

that there are no persons in the danger area.

 

f

Observe the valid accident prevention regula-

tions.

Check the device for correct function after installa-

tion and after every fault.
Proceed as follows:
Mechanical function test
The actuating element must move easily. Close the 

safety guard several times to check the function.
Electrical function test
1.  Switch on operating voltage.
2.  Close all safety guards.

¨

¨

The machine must not start automatically.

3.  Start the machine function.
4.  Open the safety guard.

¨

¨

The machine must switch off and it must not be 

possible to start it as long as the safety guard 

is open.

Repeat steps 2 - 4 for each safety guard.

Inspection and service

 WARNING

Danger of severe injuries due to the loss of the 

safety function.

 

f

If damage or wear is found, the complete switch 

must be replaced. Replacement of individual 

parts or assemblies is not permitted.

 

f

Check the device for proper function at regular 

intervals and after every fault. For informa-

tion about possible time intervals, refer to 

EN ISO 14119:2013, section 8.2.

Inspection of the following is necessary to ensure 

trouble-free long-term operation:

 

f

correct switching function

 

f

secure mounting of all components

 

f

damage, heavy contamination, dirt and wear

 

f

sealing of cable entry

 

f

loose cable connections or plug connectors.

Information: The year of manufacture can be seen 

in the bottom, right corner of the rating plate.

Exclusion of liability and warranty

In case of failure to comply with the conditions for 

correct use stated above, or if the safety instruc-

tions are not followed, or if any servicing is not 

performed as required, liability will be excluded and 

the warranty void.

Notes about 

The following information applies to devices 
with cable entry:
For use and applications as per the requirements 
of 

, a copper wire for the temperature range 

60/75 °C is to be used.
The following information applies to devices 

with plug connector:
For use and applications as per the requirements of 

, a class 2 power supply according to UL1310 

must be used. Connection cables for safety switches 

installed at the place of use must be separated 

from all moving and permanently installed cables 

and un-insulated active elements of other parts 

of the system which operate at a voltage of over 

150 V. A constant clearance of 50.8 mm must be 

maintained. This does not apply if the moving cables 

Summary of Contents for NZ.W Series

Page 1: ... Die Sicherheitskontakte sind geöffnet Montage HINWEIS Geräteschäden durch falschen Anbau und ungeeig nete Umgebungsbedingungen f f Sicherheitsschalter und Betätiger dürfen nicht als Anschlag verwendet werden f f Beachten Sie EN ISO 14119 2013 Abschnitte 5 2 und 5 3 zur Befestigung des Sicherheitsschalters und des Betätigers f f Beachten Sie EN ISO 14119 2013 Abschnitt 7 zur Verringerung von Umgeh...

Page 2: ... RG RS RL RK 10 m min 20 m min 50 m min Anfahrgeschwindigkeit min 0 1 m min Betätigungskraft bei 20 C 30 N Betätigungshäufigkeit 7000 h Kontaktwerkstoff Silberlegierung hauchvergoldet NZ1 NZ2 Anschlussart Leitungseinführung M20 x 1 5 Steckverbinder Leiterquerschnitt flexibel starr 0 34 1 5 mm 0 34 0 75 mm mit LED Anzeige SR6 0 5 1 5 mm SR11 0 5 mm NZ1 M NZ2 SR6 NZ2 SR11 NZ2 SVM5 Bemessungsisolatio...

Page 3: ...ffrolle RS Stahlrolle RL Rollenstößel lang Endstellung Ruhestellung Endstellung Ruhestellung Kontakte offen geschlossen Bild 3 Schaltelemente und Steckerbelegung Steckverbinder SR6 Pinbelegung Stiftdose Ansicht auf Geräteseite Steckverbinder SR11 Pinbelegung Stiftdose Ansicht auf Geräteseite Steckverbinder SVM5 Pinbelegung Stiftdose Ansicht auf Geräteseite 4 3 1 2 Kontaktbelegung Schaltelemente Ko...

Page 4: ...g and unsuitable ambient conditions f f Safety switches and actuators must not be used as an end stop f f Observe EN ISO 14119 2013 sections 5 2 and 5 3 for information about fastening the safety switch and the actuator f f Observe EN ISO 14119 2013 section 7 for information about reducing the possibilities for bypassing an interlocking device f f Protect the switch head against damage Changing th...

Page 5: ...tor Conductor cross section flexible rigid 0 34 1 5 mm 0 34 0 75 mm with LED indicator SR6 0 5 1 5 mm SR11 0 5 mm NZ1 M NZ2 SR6 NZ2 SR11 NZ2 SVM5 Rated insulation voltage Ui 250 V Ui 50 V Ui 50 V Rated impulse withstand voltage Uimp 2 5 kV Uimp 1 5 kV Uimp 1 5 kV Conditional short circuit current 100 A Operating voltage for optional LED indicator only for switching elements ES511 ES528H ES538H L06...

Page 6: ...ic roller RS Steel roller RL Extended roller plunger End position Free position End position Free position Contacts open closed Figure 3 Switching elements and connector assignment Plug connector SR6 Pin assignment for male socket view of device side Plug connector SR11 Pin assignment for male socket view of device side Plug connector SVM5 Pin assignment for male socket view of device side 4 3 1 2...

Reviews: