Operating Instructions
Safety Switch NZ.H/P
Electrical function test
1. Switch on operating voltage.
2. Close all guards.
¨
The machine must not start automatically.
3. Start the machine function.
4. Open the guard.
¨
The machine must switch off and it must not be
possible to start it as long as the guard is open.
Repeat steps 2 - 4 for each guard.
Inspection and service
WARNING
Danger of severe injuries due to the loss of the
safety function.
f
If damage or wear is found, the complete switch
must be replaced. Replacement of individual
parts or assemblies is not permitted.
f
Check the device for proper function at regular
intervals and after every fault. For informa-
tion about possible time intervals, refer to
EN ISO 14119:2013, section 8.2.
Inspection of the following is necessary to ensure
trouble-free long-term operation:
f
correct switching function
f
secure mounting of all components
f
damage, heavy contamination, dirt and wear
f
sealing of cable entry
f
loose cable connections or plug connectors.
Info
: The year of manufacture can be seen in the
bottom, right corner of the type label.
Exclusion of liability and warranty
In case of failure to comply with the conditions for
correct use stated above, or if the safety regula-
tions are not followed, or if any servicing is not
performed as required, liability will be excluded and
the warranty void.
Notes about
The following information applies to devices
with cable entry:
For use and application as per the requirements
of
a copper wire for the temperature range
60/75 °C must be used.
The following information applies to devices
with plug connector:
This device is intended to be used and applied with
a Class 2 power source in accordance with UL1310.
Connecting cables for safety switches installed at
the place of use must be separated from all moving
and permanently installed cables and un-insulated
active elements of other parts of the system that
operate at a voltage of over 150 V. A constant
clearance of 50.8 mm must be maintained. This
does not apply if the moving cables are equipped
with suitable insulation materials that possess an
identical or higher dielectric strength compared to
the other relevant parts of the system.
EU declaration of conformity
The declaration of conformity is part of the operating
instructions, and it is included as a separate sheet
with the device.
The original EU declaration of conformity can also
be found at: www.euchner.com
Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Germany
Service telephone
:
+49 711 7597-500
:
Internet
:
www.euchner.com
Technical data
Parameter
Value
Housing material
Anodized die-cast alloy
NZ1... Cable entry
NZ2... Plug connector M12/SVM5
NZ2... Plug connector SR6/SR11
Degree of protection
IP67
IP65
Mech. operating cycles
30 x 10
6
Ambient temperature
-25 to +80 °C
Degree of contamination (external, according to
EN 60947-1)
3 (industrial)
Installation orientation
Any
Actuator
HB
HS
PB
PS
Approach speed, max.
300 m/min
60 m/min
120 m/min
30 m/min
Approach speed, min.
0.1 m/min
0.1 m/min
0.5 m/min
0.5 m/min
Actuation frequency
10,000/h
7,000/h
Actuating force at 20 °C
15 N
Contact material
Silver alloy, gold flashed
NZ1...
NZ2...
Connection
Screw terminal
Plug connector
Conductor cross-section (rigid/flexible)
0.34 ... 1.5 mm²,
0.34 ... 0.75 mm² with LED indicator
SR6: 0.5 ... 1.5 mm²
SR11: 0.5 mm²
NZ1...M / NZ2...SR6
NZ2...SR11
NZ2...SVM5
Rated insulation voltage
U
i
= 250 V
U
i
= 50 V
U
i
= 50 V
Rated impulse withstand voltage
U
imp
= 2.5 kV
U
imp
= 1.5 kV
U
imp
= 1.5 kV
Conditional short-circuit current
100 A
Indicator LED
L060
L110
L220
Only for switching elements ES511, ES528H, ES538H
AC/DC 12 - 60 V
AC 110 V ±15%
AC 230 V ±15%
Rated data for the switching elements
ES511
ES528H/ES538H
SK2121H/SK2131H/
SK3131H
Switching principle
Snap-action contact
element
Slow-action contact
element
Slow-action contact
element
Utilization category acc. to IEC 60947-5-1
with cable entry
AC-12
I
e
10 A U
e
230 V
-
-
AC-15
I
e
6 A U
e
230 V
I
e
4 A U
e
230 V
I
e
4 A U
e
230 V
DC-13
I
e
6 A U
e
24 V
I
e
4 A U
e
24 V
I
e
4 A U
e
24 V
with plug connector SR6
1)
AC-15
I
e
6 A U
e
230 V
I
e
4 A U
e
230 V
-
DC-13
I
e
6 A U
e
24 V
I
e
4 A U
e
24 V
-
with plug connector SR11
1)
AC-15
-
-
I
e
4 A U
e
50 V
DC-13
-
-
I
e
4 A U
e
24 V
with plug connector SVM5
AC-15
I
e
4 A U
e
30 V
I
e
4 A U
e
30 V
-
DC-13
I
e
4 A U
e
24 V
I
e
4 A U
e
24 V
-
Short circuit protection (control circuit fuse)
1)
See
Utilization category
4 A gG
4 A gG
Conventional thermal current I
th
1)
4 A
4 A
Switching current, min., at
10 mA
1 mA
10 mA
1 mA
10 mA
switching voltage
DC 24 V
DC 24 V
DC 12 V
DC 24 V
DC 12 V
1) Limitation for NZ2... at ambient temperature > 70 ... 80 °C:
NZ2...SR6
NZ2...SR11
Utilization category acc. to IEC 60947-5-1 AC-15
I
e
2 A U
e
230 V
I
e
2 A U
e
50 V
DC-13
I
e
2 A U
e
24 V
I
e
2 A U
e
24 V
Short circuit protection (control circuit fuse)
2 A gG
2 A gG
Conventional thermal current I
th
2 A
2 A
Reliability values acc. to EN ISO 13849-1
depending on the switching current at 24 V DC
At DC-13 100 mA/24 V
≤ 0.1 A
B
10D
ES511
-
ES528H/ES538H
2 x 10
7
SK2121H/SK2131H/SK3131H
2 x 10
7