Operating Instructions Safety Systems
MGB2-I-BP.-… / MGB2-I-BR.-…
30
(translation of the original operating instructions) 2530674-02-03/21
12.9. Terminal assignment and contact description
X6
X5
SLOT 1
SLOT 2
X3
X2
X1
X4
Fig. 24: Connections and LEDs
Terminal
Designation
Description
X1.1
UB
BR electronics operating voltage, 24 V DC
X1.2
FI1A
Enable input for channel A
If operated separately (BP), set DIP switch as per operating instructions.
X1.3
FI1B
Enable input for channel B
If operated separately (BP), set DIP switch as per operating instructions.
X1.4
OT/C
Bolt tongue monitoring output
ON when the door is closed and the bolt tongue is inserted into the interlocking module.
Optional: BR diagnostic output
X1.5
OD
Door monitoring output
ON when the door is closed.
X1.6
n.c.
X1.7
OI
Monitoring output DIA
ON when the device is in the fault state.
X1.8
FO1A
Safety output, channel A
ON when door is closed and interlocked.
Attention: Pay attention to the DIP switch position.
X2.1
0 V UB
BR electronics operating voltage, 0 V
X2.2
S2 1.2
See the enclosed data sheet for the submodule
X2.3
S2 2.2
X2.4
S1 LED
X2.5
S2 LED
X2.6
S3 LED
X2.7
RST
Reset input, device is reset if 24 V DC is applied to RST for min. 3 s.
X2.8
FO1B
Safety output, channel B
ON when door is closed.
Attention: Pay attention to the DIP switch position.
X3.1
n.c.
X3.2
n.c.
X3.3 - X3.8
See the enclosed data sheet for the submodule
X4.1 - X4.8
See the enclosed data sheet for the submodule
X5
Connection for optional accessories; see enclosed data sheet
X6
Connection for optional accessories; see enclosed data sheet
Table 2: Terminal assignment and contact description