15
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
EN
9.2.1. Carrying out teach-in for first actuator (default setting on delivery)
To trigger the first teach-in operation, the user must perform the following actions in the stipulated order:
1. Start teach-in operation
-Switch on operating voltage (STATE LED flashes at approx. 4 Hz)
-Close door to be monitored (the actuator must be in the operating distance of the read head)
-Teach-in operation starts (STATE LED flashes at approx. 1 Hz)
-Wait for acknowledgment of the teach-in operation (STATE LED goes out after approx. 60 seconds)
2. End teach-in operation
-Interrupt operating voltage for at least 10 seconds (code for the actuator taught-in is activated)
3. Check safety guard for effectiveness
9.2.2. Carrying out teach-in for a new actuator
A maximum of 8 teach-in operations can be undertaken. The number of teach-in operations already undertaken is signaled
after step 6 via the flashing sequence on the STATE LED (see
10. System status table on page 17
, section
State indication
).
Faulty actuators can be replaced. Then a complete teach-in operation must be performed as per this section.
To trigger a further teach-in operation, the user must perform the following actions in the stipulated order:
1. Start teach-in operation
-Switch on operating voltage
-Close door to be monitored (the new actuator must be in the operating distance of the read head)
-Teach-in operation starts (STATE LED flashes at approx. 1 Hz)
-Wait for acknowledgment of the teach-in operation (STATE LED goes out after approx. 60 seconds)
2. End teach-in operation
-Interrupt operating voltage for at least 10 seconds (code for the new actuator taught-in is activated)
The newly taught-in actuator is saved and the old actuator deactivated.
3. Check safety guard for effectiveness