Operating Instructions
Non-Contact Safety Switch CES-I-BR-.-C07-…
12
(translation of the original operating instructions) 2510145-05-08/21
9. Connection of a single CES-I-BR (separate operation)
If a single CES-I-BR is used, connect the device as shown in
. The monitoring output OD can be connected to a control
system.
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì
To ensure safety, both safety outputs FO1A and FO1B must always be evaluated.
Important!
The example shows only an excerpt that is relevant for the connection of the CES system. The example
illustrated here does not show complete system planning. The user is responsible for safe integration
into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter
the order number of your switch in the search box. You will find all available connection examples for
the device in
Downloads
.
Safety
Outputs
Monitoring
Output
Read Hea
d
Safety Inputs
Connected
load
24 V DC
GND
-F1
+UB
2
FI1A
6
FI1B
1
0V
7
OD/C
5
FO1A
3
FO1B
4
nc
8
CES
Fig. 2:
Connection example for separate operation of a CES-I-BR-…