Operating Instructions Safety Systems
MGB-L..B-PN.-… (PROFINET) and With Data Structure Type A
14
(translation of the original operating instructions) 2114575-06-02/21
6.5.3. Case C
You have an MGB with a version number of V3.30.0 and a GSD file with a version number from ..._110026-20110815.
The guard locking solenoid is controlled if:
Ì
bit
SO 1 = 1
(factory setting)
Truth table
PROFINET bit
PROFIsafe bit
Guard locking with
O 16
Not relevant
SO 1
MGB-L1...
MGB-L2...
0
0
Active
Inactive
0
1
Inactive
Active
1
0
Active
Inactive
1
1
Inactive
Active
What must be observed?
You can define in the GSD file whether bit
O 16
may be used for control in addition to bit
SO 1
. The setting is specified in
the parameter
Locking module - solenoid control
.
If
O 16
is additionally used, the guard locking solenoid is controlled if
for MGB-L1...
Ì
bit
SO 1
AND
bit
O 16 = 1
for MGB-L2...
Ì
bit
SO 1
OR
bit
O 16 = 1
Truth table
PROFINET bit
PROFIsafe bit
Guard locking with
O 16
SO 1
MGB-L1...
MGB-L2...
0
0
Active
Inactive
0
1
Active
Active
1
0
Active
Active
1
1
Inactive
Active