Kuvamateriaali on havainnollistava
Pidätämme oikeuden muutoksiin
RDT-07-0121
33
®
NORD
fire
|
FDMB
Fig. 43 Gypsum wall construction- fire protection foam with stucco plaster
Maximum damper dimensions 400x400 mm
EIS 60
EIS 45
EIS 30
Position:
1 Fire damper
2 Gypsum plate
3 Mineral wool (type depending on the type of construction)
4 Fire protection foam
5 Stucco plaster
6 Duct
Used materials - example:
4 HILTI CFS-F FX - EIS 60
PROMAFOAM-C - EIS 45
SOUDAL, Soudafoam FR-B1 - EIS 30
DenBraven, Fire protection foam - EIS 30
The damper must be anchored to the fire wall construction!
Shown schemes of incorporation and damper are illustrative only!
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws
≥3,5 mm with corresponding
length. Distance between
screws ≤200 mm.