6.3 Vertical installation
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the
suspension system depend on weight of the fire damper.
Damper can be suspended from the ceiling construction or supported above the ceiling con-
struction.
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Fig. 40 Suspension- vertical duct
Notice:
Damper must be firmly connected with extension piece by screws or rivets.
Position:
1 Fire damper
2 Damping pad
3 Extension piece
4 Threaded rod
5 Mounting rail
6 Nut
7 Washer
8 Screw connection
9 Mounting profile
10 Bolt
11 Screw or rivet
Actuating mechanism is placed under the ceiling construction
Examples of using materials -
HILTI, SIKLA, MÜPRO etc.
Shown schemes of incorporation and damper are illustrative only!