RDT-43-0921
29
®
NORD
fire
|
FDMA-PM
Images are for illustrative purposes
We reserve the right to make changes
Fig. 35 Solid ceiling construction- Weichschott
EIS 90
* min. 110 - Concrete/ min. 125 - Aerated concrete
Position:
1 Fire damper
2 Solid ceiling construction
3 Fire resistant board
4 Fire stop coating thickness 1 mm
5 Duct
Used materials - example:*
3 Hilti CFS-CT B 1S 140/50
4 Hilti CFS-CT
** Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing
system for damper installation with equivalent material properties.
Shown schemes of incorporation and damper are illustrative only!