5. Statement of installations
5.1 Installation method list
Tab 5.1.1.Installation method list
Fire separating constru.
Wall/Ceiling
Installation
Fire
resist.
Page
Min.thickness
[mm]
Solid wall construction
100
Mortar or gypsum
EIS 120
EIS 90
12
100
Battery - mortar or gypsum
EIS 90
13
100
Installation next to wall - mortar or
gypsum and mineral wool
EIS 90
14
100
Installation next to wall - mortar or
gypsum
EIS 90
14
100
Stuffing box with fire protection
mastic and cement lime plate
EIS 90
15
100
Weichschott
EIS 90
16
Outside solid wall
construction
100
Mineral wool - mortar or gypsum
EIS 45
17
100
Mineral wool - stuffing box and fire
protection mastic
EIS 45
18
100
Mineral wool, stuffing box, fire
protection mastic and cement lime
plate
EIS 90
19
Gypsum wall
construction
100
Mortar or gypsum
EIS 120
EIS 90
20
100
Battery - mortar or gypsum
EIS 90
21
100
Installation next to wall - mortar or
gypsum and mineral wool
EIS 90
22
100
Installation next to wall - mortar or
gypsum
EIS 90
22
100
Stuffing box with fire protection
mastic and cement lime plate
EIS 90
23
Outside gypsum wall
construction
100
Mineral wool - mortar or gypsum
EIS 45
24
100
Mineral wool - stuffing box and fire
protection mastic
EIS 45
25
100
Mineral wool, stuffing box, fire
protection mastic and cement lime
plate
EIS 90
26
Solid ceiling
construction
110 - Concrete
125 - Aerated
concrete
Mortar or gypsum
EIS 120
EIS 90
27
Battery - mortar or gypsum
EIS 90
28
Stuffing box with fire protection
mastic and cement lime plate
EIS 90
29
Weichschott
EIS 90
30
Mineral wool - mortar or gypsum
EIS 90
31
Outside solid ceiling
construction
Concrete
EIS 90
32