background image

 

Electrical Installation 

 

17

 

5.0   Electrical Installation 

 

Before assembling, installing, or connecting any components, 
follow the safety information in the ETS-Lindgren 
Product Information Bulletin included with your shipment. 

 

Electrical installation must be performed by a qualified 
electrician, and in accordance with local and national electrical 
standards. 

 

Make sure the power is off and secured before proceeding. 

The Model 2187 Turntable is configured to operate using 208-230 VAC, 
single phase, 50/60 Hz service. It is recommended to operate at this voltage level 
to reduce the surge currents necessary to power an electric motor. 

1. 

The branch circuit supplying power to the motor base should be 
protected from excess current according to local electrical codes. An 
integral circuit breaker is mounted inside the main bearing on one of the 
bearing support blocks. The circuit breaker is specifically designed for 
the inductive load presented by the electric motor. 

2. 

Make sure the conductor size is adequate for the motor load and the 
distance from the mains source. Improperly sized conductors will lead to 
a high voltage drop in the power conductors and cause reduced starting 
torque and premature motor failure. 

3. 

The motor base assembly is provided with a non-terminated flexible 
conduit with input power leads exposed. The flexible conduit is to be 
terminated into a junction box fitted on or near the motor base. Terminate 
the power leads of the motor base assembly according to local electrical 
code requirements. Following is the conductor color code: 

Brown: 

AC high 

Blue: 

AC neutral 

Green/Yellow: 

Protective earth/safety ground 

 

18   

 

Electrical Installation

 

Connect the fiber optic control cable and install the power connection according 
to local electrical code. See the controller manual for information on connecting 
the fiber optic cable. After the fiber optic cable is installed, secure it with a wire tie 
to one of the leveling screws. 

To feed the fiber optic connectors through a waveguide in the chamber, cables 
are included to connect from the feedthroughs on the penetration panel to the 
controller and motor base. 

 

Assembly and Installation  

19

 

6.0   Assembly and Installation 

 

Before assembling, installing, or connecting any components, 
follow the safety information in the ETS-Lindgren 

Product Information Bulletin

 included with your shipment. 

 

Prior to assembly and installation, review the drawings located in the back 
pocket of this manual. 

Proper installation of the turntable directly affects performance. The installation of 
turntables two meters and larger will be performed by factory installation 
specialists or individuals authorized by ETS-Lindgren to perform such work. The 
following installation information is included only to provide an informational 
overview of the installation process. 

1. 

Uncrate all parts and check for shipping damage. Create a clear area to 
safely assemble the turntable unit. Do not discard any packing material 
until unit is fully assembled. 

2. 

Remove the bolts that attach the top onto the turntable drive assembly. 
Make note of the placement of each top section as it is removed. 

 

Only qualified personnel should use a forklift or other lifting 
machinery to lift the turntable assembly. 

3. 

Using a forklift or other appropriate lifting machinery, place the turntable 
bottom or bearing support section into position. If the turntable is to be 
installed in a pit, center and level the assembly. 

 

Make sure power is off and secured before proceeding. 

4. 

The drawings in the

 

back of this manual show the placement of floor 

plates and leveling screws to anchor and level the turntable. Anchor the 
turntable through the attachment holes using the concrete expansion 
bolts provided. After installing the floor plates and leveling screws, level 
the entire turntable by adjusting all the leveling screws between and 
under the casters, and in the center section of the turntable. 

5. 

Tighten all lock nuts accompanying the leveling screws to lock the height 
of the turntable into place. 

 

20   

 

Assembly and Installation

 

6. 

Connect the fiber optic control cable and install the power connection 
according to local electrical code. The standard power configuration is 
230 VAC 50/60 Hz. 

 

Keep all body parts away from the drive pinion when the 
turntable is energized. 

7. 

Follow the instructions in the next section, 

Floor Flange Installation in a 

Paneled Floor

, to install the ground ring assembly. 

8. 

Reinstall the top section removed in step 2 of these instructions. 

Floor Flange Installation in a Paneled Floor 

 

 

 

The ground ring assembly includes a floor flange with a mounted brush ring that 
interfaces with the contact ring mounted beneath the turntable top. The floor 
flange provides constant electrical contact with the ground plane. 

Mounting methods vary according to user specifications. Clearance holes are 
provided at evenly-spaced intervals along the outside perimeter of the floor 
flange to attach to a customer-supplied ground plane. These instructions 
describe installation for a paneled floor. For concrete pit mounting instructions, 
see 

Floor Flange Installation in Concrete Pit

 on page 22. 

Summary of Contents for 2187

Page 1: ... Contents Notes Cautions and Warnings v 1 0 Introduction 7 Standard Configuration 7 Turntable Assembly 7 Shield Room Feed through 8 Optional Items 8 Infrared Remote Controller 8 Slip Ring 8 EUT Power Outlets 9 Mounted Line Impedance Stabilization Network 9 Additional Fiber Optic Cables 9 ETS Lindgren Product Information Bulletin 9 2 0 Maintenance 11 Recommended Maintenance Schedule 11 6 Month Serv...

Page 2: ...o accommodate customer supplied cabling to and from the EUT To prevent over travel of the turntable in either direction of movement hard limits are provided in the form of pins that actuate switches located below the tabletop These pins allow limits to be set and allow as much as two full rotations Rotation speed can be varied from a controller not included or through the IEEE 488 interface bus St...

Page 3: ...oints within the instrument that could if contacted cause personal injury Only trained service personnel should perform adjustments and or service procedures upon this instrument Capacitors inside this instrument may still be charged even when the instrument is disconnected from the power source Recommended Maintenance Schedule Regular maintenance will prolong the effective operation and reliabili...

Page 4: ...Regularly inspect all equipment for loose fasteners and wear Conduct scheduled maintenance in accordance with the factory recommendations provided Only use replacement parts and fasteners ordered directly from the factory Stay clear of all moving components on this equipment Do not operate turntable while someone is physically on the turntable top Do not at any time place hands or feet in the vici...

Page 5: ...r installation of the turntable directly affects performance The installation of turntables two meters and larger will be performed by factory installation specialists or individuals authorized by ETS Lindgren to perform such work The following installation information is included only to provide an informational overview of the installation process 1 Uncrate all parts and check for shipping damag...

Page 6: ...e Installation in a Concrete Pit Installing in a concrete pit is the same as a paneled floor with the exception of the mounting hardware Instead of the 14 x 1 in square socket flat head screws use 1 4 x 1 75 in Phillips flat head concrete anchors These tools are required for the next stage of installation 1 2 in hammer drill 3 16 x 3 5 in hammer drill bit at minimum Vacuum to clean inside the dril...

Page 7: ...ation on connecting the fiber optic cable and operating the controller A manual is included with each controller and is also available for download from www ets lindgren com 26 Operation This page intentionally left blank List of Assembly Drawings 27 Appendix A List of Assembly Drawings Following is a list of the assembly drawings located in the back of this manual Prior to assembly and installati...

Page 8: ...Point Drive Cedar Park TX USA 78613 Cedar Park TX USA 78613 The products listed below are eligible to bear the CE mark Model 2187 Electric Powered Turntable 2 Meter and 3 Meter with 2088 style motor base APPLICABLE REQUIREMENTS Standard Criteria EN 55011 Group 1 Class B EN 61000 4 2 1995 Level 2 3 4 8 kV EN 61000 4 3 1997 Level 2 3 V m EN 61000 4 4 Level 2 1 0 5 kV ENV 50204 1996 Level 2 3 V m EN ...

Page 9: ...8 11 X 1 3 4 HEX GR5 ZN 33 10 910619 SCREW 5 8 11 X 1 25 SH FLAT SS 32 32 910616 SCREW LEVELING 1 2 13 X 3 SQ HD CU 31 32 910615 NUT 3 8 16 HEX ZINC SERRATED FLANGE 30 4 910603 SCREW 1 4 20 X 7 8 PHIL FLAT SS 29 2 910599 BOLT 3 8 16 X 2 1 2 HEX SS 28 10 910539 WASHER 5 8 LOCK STL ZN SPLIT 27 8 910456 WASHER 1 4 LOCK SS SPLIT 26 8 910436 BOLT 1 4 20 X 1 2 HEX SS 25 2 910411 WASHER 3 8 LOCK STL ZN S...

Page 10: ... 6 3 RMS OR B ETTER FINISH TOLERANC ES ARE DECIMALS ANGLES DRAFTING PERMISSION OF ETS LINDGREN IS PROHIB ITED ANY DUPLIC ATION OF THIS PROPRIETARY INFORMATION WITHOUT EXPRESS WRITTEN DOC UMENT WHOLE OR IN PART DATE TITLE OF SHEET DWG NO An ESCO Technologies Company SC ALE D TM REV 5 19 0 A RELEASED 1 0 2 7 0 6 RB G RB G 117 22 TABLE TOP 121 82 REF 119 12 25 PIT OPENING DIMENSION REF A A REFER TO S...

Page 11: ...34 FLOOR FLANGE TURNTABLE 3 0m AL 14 6 112133 TIEBAR INSIDE TOP 2187 3 0 13 1 111988 TOP SECT4 TURNTABLE 2187 3 0 12 1 111987 TOP SECT3 TURNTABLE 2187 3 0 11 2 111986 TOP SECT2 TURNTABLE 2187 3 0 10 2 111985 TOP SECT1 TURNTABLE 2187 3 0 9 2 111333 RING SPLIT 2187 TURNTABLE 8 12 110405 CONTACTFLAT BRUSH TURNTABLE 7 6 110059 PLUG HOLE TABLETOP 6 1 108925 COVER ACCESS 5 12 106789 FLOOR PLATESPACER 20...