7
FISt
fixed capacitor stages
Auto
Auto / oFF / on
CoCo
connection configuration
90
0° ... 330° in steps of 30°
rCPo
reactive power offset for regulation
0
0 ... 999.9 kVAr
ˉCoS
regulation to the average power factor
on
on / oFF / Auto
– off regulates on instant. cosφ
tACo
averaging time for APFR regulation
60
15, 30, 45, 60 minutes
C_St
saving the step operations and maxim to non volatile memory
oFF
on / oFF
E_IC
activation of inductive steps for de-compensation
oFF
on / oFF
C_IL
minimum current sensitivity
0
0 … 1000 mA in steps of 10 mA
uL.AL
under-voltage alarm
oFF
on / oFF
– off alarm does not operate
uL
voltage trigger value for an alarm activation
0
0 ... 750 V
t_uL
minimum event duration for an alarm activation
0
0 ... 3600 s
o_uL
alarm event disconnects compensation steps
oFF
on / oFF
uH.AL
over-voltage alarm
oFF
on / oFF
– off alarm does not operate
uH
voltage trigger value for an alarm activation
0
0 ... 750 V
t_uH
minimum event duration for an alarm activation
0
0 ... 3600 s
o_uH
alarm event disconnects compensation steps
oFF
on / oFF
IL.AL
under-current alarm
oFF
on / oFF
– off alarm does not operate
IL
current trigger value for an alarm activation
0
0 ... 5 A
t_IL
minimum event duration for an alarm activation
0
0 ... 3600 s
o_IL
alarm event disconnects compensation steps
oFF
on / oFF
IH.AL
over-current alarm
oFF
on / oFF
– off alarm does not operate
IH
current trigger value for an alarm activation
0
0 ... 8 A
t_IH
minimum event duration for an alarm activation
0
0 ... 3600 s
o_IH
alarm event disconnects compensation steps
oFF
on / oFF
Co.AL
alarm for cosφ, that is permanently over set limits
oFF
on / oFF
– off alarm does not operate
_Co
cosφ level value for an alarm activation
0
0.80 cap. ... 0.80 ind.
t_Co
minimum event duration for an alarm activation
0
0 ... 3600 s
o_Co
alarm event disconnects compensation steps
oFF
on / oFF
Hu.AL
alarm of voltage harmonic distortion
oFF
on / oFF
– off alarm does not operate
tHdu
THDU trigger value for an alarm activation
0
0 ... 50 %
t_Hu
minimum event duration for an alarm activation
0
0 ... 3600 s
o_Hu
alarm event disconnects compensation steps
oFF
on / oFF
HI.AL
alarm of current harmonic distortion
oFF
on / oFF
tHdI
THDI trigger value for an alarm activation
0
0 ... 300 %
t_HI
minimum event duration for an alarm activation
0
0 ... 3600 s
o_HI
alarm event disconnects compensation steps
oFF
on / oFF
ot.AL
alarm for high ambient temperature
oFF
on / oFF
– off alarm does not operate
tEPA
temperature level for alarm
55
10 ... 80°C
t_tE
minimum event duration for an alarm activation
0
0 ... 3600 s
o_tE
alarm event disconnects compensation steps
oFF
on / oFF
rS.AL
alarm for exceeding of maximum number of step closing
oFF
on / oFF
– off alarm does not operate
tEPV
temperature level for ventilator start
35
10 ... 80°C
Id
device ID number in RS485 network
0
0 ... 255
bAud
communication speed for data transmission
0
0 ... 38400 Bd