TMCM-1310 TMCL Firmware V1.11 Manual (Rev. 1.16 / 2014-MAR-19)
36
www.trinamic.com
6.8.14
SIO (set input / output)
SIO sets the status of the general digital output either to low (0) or to high (1). Bank 2 is used for this
purpose.
Internal function:
the passed value is transferred to the specified output line.
Related commands:
GIO, WAIT
Mnemonic:
SIO <port number>, <bank number>, <value>
Binary representation:
INSTRUCTION NO.
TYPE
MOT/BANK
VALUE
14
<port number>
<bank number>
2
<value>
0/1
Reply structure:
STATUS
VALUE
100 – OK
don’t care
Example:
Set OUT_7 to high (bank 2, output 7)
Mnemonic:
SIO 7, 2, 1
Binary:
Byte Index
0
1
2
3
4
5
6
7
Function
Target-
address
Instruction
Number
Type
Motor/
Bank
Operand
Byte3
Operand
Byte2
Operand
Byte1
Operand
Byte0
Value (hex)
$01
$0e
$07
$02
$00
$00
$00
$01
O
VERVIEW
I/O
CONNECTORS
0
AND
1
I/O
connector 1
I/O
connector 0
Figure 6.1 I/O connectors