18
Echo Relay Panel Feedthrough Installation Manual
Install Option Cards
Each option card is packaged separately and comes with its own installation
instructions.
Option card installation location
Primary/Secondary switch
When using two of either the 0-10V or DALI control
option cards in an ERP48-FT you will need to position
the primary secondary prior to startup. The primary
secondary switch controls which set of relays responds
to which option card.
• When using two different option cards, move the
switch to position 1.
• When using two of the same option cards, move
the switch to position 2.
With the switch in position one, each card will control
the circuits assigned to it, up to 24 circuits.
With the switch in position two, the card connected to
the “option 1” connector will control circuits 1-24.
The card connected to “option 2” connector will
control circuits 25-48.
Option Card 1
Option Card 2
Primary/Secondary Switch
Position
0-10V (outputs 1-24
0-10V (outputs 25-48)
Secondary
DALI (outputs 1-24
DALI (outputs 25-48)
Secondary
0-10V (outputs 1-24)
Contact Input
Primary
DALI (outputs 1-24)
Contact Input
Primary
DALI Option Card or
0-10V Option Card
Contact Input
Option Card
Network
Option Card
Ride Thru
Option
Option
card 1
Option
card 2
Primary/
Secondary
switch
pos. 1
pos. 2