ETC Installation Guide
Pro One-Cell
Pro One-Cell
Page 4 of 29
ETC
For more information on installation of standard or emergency system drivers, see
or
Emergency System One-Cell Installation on page 19
Note:
ArcSystem Pro One-Cell Micro and ArcSystem Pro One-Cell standard luminaires
are not interchangeable. One-Cell Micro luminaires require a D2 driver to function; One-
Cell and One-Cell Small luminaires require a D1 driver or D4 driver to function.
Note:
All ArcSystem wireless luminaires require a TX1 Transmitter and commissioning
tool to set DMX addresses for both wired DMX and wireless installations. Contact your ETC
Service Technician for more information.
Emergency System Overview
ArcSystem drivers and luminaires can be purchased in UL924 listed variants. Each of the luminaires
can be configured to be UL924 listed when wired into an existing emergency response system. See
Emergency System One-Cell Installation on page 19
.
Install the ArcSystem D1, D2, or D4 Series driver in a location that is accessible by qualified
personnel for testing of the emergency operation.
Note:
Luminaires must be hard-wired to emergency certified drivers to be considered for
UL924 certification.
Note:
The number of designated emergency lamps and their height is the responsibility of
the specifier and installer in order to achieve the minimum FC levels of NFPA101.
Installation scenarios should be evaluated by the AHJ to confirm illuminance and
performance requirements of ANSI/NFPA 101 and the IBC.
Note:
ArcSystem Pro One-Cell Micro luminaires in emergency installations must be
installed with a maximum mounting height of 23.2 ft (7.07 m).
Note:
Installation must follow all national and local codes for electrical equipment.
Note:
Normal and emergency wiring cannot be contained in the same conduit according
to NEC 700.10(B).