Prepare to Install
15
Cable Routing and Conduit Access
When planning conduit entry and cable routing to the Sensor IQ Breaker Panel, pay special attention to
the recommendations shown in the figure below. Arrows indicate acceptable conduit entry locations.
The low-voltage wiring trough is located between the edge of the panel and the User Interface. The
panel can be mounted with the trough on the top or the bottom, allowing for data and low-voltage
cable routing flexibility.
Cable Routing Options
Purpose
Top Entry
Bottom Entry
Top
Side Entry
Bottom
Side Entry
Feed wiring
Outside of low-voltage
cable trough only
Outside of low-voltage
cable trough only
Yes
Yes
Load wiring
Yes
Yes
Control wiring (DMX,
Network, option cards, etc.)
Through low-voltage
cable trough only
Through low-voltage
cable trough only
No
No
Note:
Control wiring (DMX, Ethernet, etc.) and power wiring must be run in separate
conduit in accordance with local code.
Panel mounted with
low-voltage cable
trough on the bottom
Panel mounted
with
low-voltage
cable trough on
the top
The User Interface can
be rotated depending
on rack installation
orientation.
Take care when
disconnecting wire
harnesses behind the
User Interface as to not
break any wire
connections.
Control
wiring
Control
wiring
Data
access
panel
Data access
panel
Bottom-Feed Mounting
Top-Feed Mounting