14
Sensor IQ Installation Manual
.
Compliance
• UL/cUL Listed to UL67
• FCC: This device complies with part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
• Complies with ANSI E1.11 USITT DMX512-A
- Breakers occupy one DMX slot each, freely assignable to any slot, and respond only to null start
code packets.
Parts and Tools
The following parts and tools are needed, but not supplied, for this installation:
• 10 mm (3/8 in) fasteners for mounting the Sensor IQ panel
• Torque wrench with 3/16 in, 5/16 in, and 3/8 in Allen wrench sockets for feed wiring
• Lineman’s pliers
• Screwdrivers: a small 3 mm (1/8 in) flatblade screwdriver for data terminations, a 3/16 in
flatblade screwdriver for ground and neutral terminations, and a #2 Phillips screwdriver for
breaker load and panel screws
• A drill and conduit punch or hole saw for conduit holes in the enclosure
• Insulation stripping tool
240/277 V Sensor IQ Panel Dimensions
Model
Height
Width
Depth
12 breaker, panel only
1.245 m (49 in)
0.508 m (20 in)
13.3 cm (5.25 in)
12 breaker with recess mounted door
1.295 m (51 in)
0.559 m (22 in)
15.2 cm (6 in)
12 breaker with surface mount door
1.245 m (49 in)
0.508 m (20 in)
15.2 cm (6 in)
24 breaker, panel only
1.397 m (55 in)
0.508 m (20 in)
13.3 cm (5.25 in)
24 breaker with recess mount door
1.448 m (57 in)
0.559 m (22 in)
15.2 cm (6 in)
24 breaker with surface mount door
1.397 m (55 in)
0.508 m (20 in)
15.2 cm (6 in)
48 breaker, panel only
1.854 m (73 in)
0.508 m (20 in)
13.3 cm (5.25 in)
48 breaker with recess mount door
1.905 m (75 in)
0.559 m (22 in)
15.2 cm (6 in)
48 breaker with surface mount door
1.854 m (73 in)
0.508 m (20 in)
15.2 cm (6 in)
Note:
The NEC requires a minimum 0.914 m (3 ft) distance (NEC 110.26(A)(1)) in front of
a Sensor IQ panel. The NEC requires that the handle of the highest circuit breaker in
a breaker panel be no more than 2.0 m (6 ft 7 in) above the floor (NEC 240.24(A)).
Check other electrical and safety codes for additional requirements.
Note:
Both the installation location and the mounting hardware must support a fully
populated panel, including conduit and cable, which weighs approximately 54.5 kg
(120 lb).