[Buffer] function block
ETAtouch controller
9.4
[Buffer] function block
Buffer storage tank overview screen
1
Operating condition and information.
A description of the operating conditions can be
found in the integrated Help menu by pressing the
button.
2
Producer for the buffer.
Currently, the buffer is charged by the burner at a
flow temperature of 72 °C.
3
Temperatures of the buffer for individual areas
(top, middle and bottom)
4
Buffer consumers.
Currently, the consumers are charged with a flow
temperature of 64 °C.
5
[Settings] button.
In this menu, the charge times are set.
Mode of operation
In the settings menu (
button), the time window for
buffer charging can be set, and therefore the charge
times (see chapter
9.4.1 "Setting the buffer charging
times"
). The buffer only requests heat from the boiler
during charge times. Within the charge times, it will
continue to be loaded by the boiler until the required
temperature [Buffer target] has been exceeded in the
upper part of the buffer and the adjustable shutdown
temperature [Buffer bottom off] is reached in the lower
part. The operating mode then changes to [Charged].
If (within the loading times) there is no heat demand
from the consumer, the buffer is charged only to the
adjustable minimum temperature [Buffer top min.]. The
consumers connected to the buffer (for example,
heating circuit or hot water tank) can also request heat
from the buffer outside the charging times. The
charging times of the consumers are independent of
the charging times of the buffer.
Buffer charging times that are too brief can cause
the temperatures in the buffer to fall too far and
prevent individual consumers from being supplied with
heat. For this reason, it is advisable to set generous
charging times.
A solar heating system connected to the buffer can
charge it at any time, regardless of the set buffer
charging times.
When the buffer is the only heat producer in the
heating system, the buffer charging times also
indirectly determine the operating hours of the boiler.
Because it can only switch to heating mode within the
buffer charging periods.
Summary of Contents for TWIN 20 kW
Page 1: ...2016 04 02 EN 0000000302 V 001 X 36 0 2303 93412 001 TWIN pellet burner 20 26 kW Operation ...
Page 39: ...ETAtouch controller TWIN function block 39 ...
Page 49: ...ETAtouch controller Buffer function block 49 ...
Page 53: ...ETAtouch controller Hot water tank function block 53 ...
Page 57: ...ETAtouch controller Fresh water module function block 57 ...
Page 81: ......
Page 82: ...www eta co at ...
Page 83: ......
Page 84: ...www eta co at ...