Pellet store
Ventilation
65
Example for ventilating the pellet store
Fig. 12-18: Filling nozzle in open air
1
ventilated sealing caps
If the filling nozzles lead inside a building, a
separate air line is to be set up from the pellet
store into the open. This must be designed so that no
dust escapes during filling and also no water can
penetrate from outside into the pellet store.
Fig. 12-19: Filling nozzle inside building
1
Sealed, unventilated sealing cover
2
Ventilation opening outside
Even if the filling nozzles protrude into a room in which
ventilation is available, ÖNORM M 7137 recommends
using only sealed, unventilated sealing covers.
Fig. 12-20: Filling nozzles in the boiler room
1
Ventilating the room
2
Sealed, unventilated sealing cover
3
Ventilation opening outside
If the pellets are stored in a bag that positioned in the
same room as the boiler, ventilation must be available
in this room. Operation of the boiler with external air
supply (as long as this is supported) is then not
possible.
Fig. 12-21: Bag in boiler room
1
Ventilating the room
2
Bag
3
Filling nozzle
Summary of Contents for PelletsCompact
Page 1: ...2020 07 21 EN 0000000061 V 022 1513 93003 003 PelletsUnit 7 15 kW Installation ...
Page 41: ...Installation Network connection 41 ...
Page 45: ...Electrical connections Overview of circuit boards 45 ...
Page 49: ...Electrical connections PE C4 circuit board 49 ...
Page 66: ...www eta co at ...
Page 67: ......
Page 68: ...www eta co at www eta co at downloads DOWNLOAD ...