![eta PelletsCompact Installation Manual Download Page 21](http://html.mh-extra.com/html/eta/pelletscompact/pelletscompact_installation-manual_2430177021.webp)
Information for installation
Chimney
21
Cleaning opening in flue pipe
Easily accessible cleaning openings must be available
for cleaning the flue pipe.
Fig. 7-2: Cleaning opening
Fit the chimney connection just under the ceiling
Even if the current boiler can be connected to the
chimney at a low height, it is better if you fit the
chimney connection just below the ceiling. The flue
pipe is easier to install, and the vertical connecting pipe
is long enough for an emission measurement.
A second chimney connection below the first one
enables simple installation of a draught limiter, if
this is required.
Measurement opening for the emissions
measurement
Create a self-locking and sealing measurement
opening in the flue pipe for the emissions measure-
ment. The measurement opening must be
implemented in accordance with national directives.
Fig. 7-3: Measurement opening
The measurement opening must be created in the
vertical portion of the flue pipe. A straight section of a
suitable length must be present before and after the
measurement opening because, otherwise, turbulence
at the measurement points will prevent meaningful
measurements. The clearance from the boiler's flue
duct connection or from a pipe bend must be at least
twice the diameter of the flue duct.
No draught limiter and no deflagration damper
with external air supply
For operation with external air supply, the chimney
must be absolutely airtight with respect to the room. No
draught limiters or deflagration dampers (often also
called blowback flaps) may be installed in the flue gas
line.
Deflagration damper
The boiler is designed with safety routines in the
control system to prevent deflagrations. Thus, no def-
lagration damper (also often called an explosion flap)
is required for a boiler output up to 50 kW if the flue
pipe is short and ascends to the chimney.
Fig. 7-4: Example: deflagration damper with draught limiter
We recommend using a deflagration damper for boiler
outputs of 60 kW and up. A deflagration damper is
required for boiler outputs of 100 kW and up. While the
most that can happen in smaller boilers in the event of
a deflagration is that the flue pipe to the chimney can
be pulled apart, in larger boilers the gas volume is
already so large that a boiler door can be blown off.
For high points before descending sections or at the
beginning of a long horizontal section (L > 20 x D), a
deflagration damper is required regardless of the boiler
output.
DANGER!
Position of the deflagration damper
Position the deflagration damper so that no people
are endangered.
Summary of Contents for PelletsCompact
Page 1: ...2020 07 21 EN 0000000061 V 022 1513 93003 003 PelletsUnit 7 15 kW Installation ...
Page 41: ...Installation Network connection 41 ...
Page 45: ...Electrical connections Overview of circuit boards 45 ...
Page 49: ...Electrical connections PE C4 circuit board 49 ...
Page 66: ...www eta co at ...
Page 67: ......
Page 68: ...www eta co at www eta co at downloads DOWNLOAD ...