Maintenance table
Cleaning and maintenance
2.3
Maintenance table
Tasks
Regular
ly
Every
2500 h
or
1 year
Every
5000 h
or
3 years
to be
performed by
Empty the ash box
•
Remove excess ash from secondary combustion chamber
•
Empty the ash box
•
Check the seals
X
X
X
Customer
Check the pressure of the heating system
X
X
X
Customer
Check safety devices
•
Visual check of the safety valves
•
Visual check of the thermal relief valve
X
X
Customer or
specialist
Chimney
•
Clean the flue tube
•
Flush the chimney's condensate drain
X
X
Customer or
specialist
Clean combustion chamber
•
Clean inside of the secondary combustion chamber
•
Clean tilting grate
•
Clean secondary air openings
•
Clean ignition tubes
•
Check firebed button and firebed switch
•
Check refractory lining
X
X
Customer or
specialist
Clean heat exchanger
•
Clean heat exchanger and downdraft channel
•
Clean lambda probe
•
Check heat exchanger tubes
•
Check heat exchanger cleaner
•
Clean the housing of the frequency converter
•
Inspect seals on heat exchanger covers
X
X
Customer or
specialist
Clean flue gas recirculator
•
Clean flue gas recirculation piping
•
Inspecting seals on maintenance covers
X
X
Customer or
specialist
Clean the draught fan
X
Specialist
Clean the temperature sensor
X
Specialist
Check air valve for primary and secondary air
X
Specialist
Lubricate the grate drive
X
Specialist
Check the ash box position switch
X
Specialist
Check de-ashing system
X
Specialist
Check boiler doors
X
Specialist
Check the stoker unit
•
Check the stoker drive chains
X
Specialist
Clean ignition
X
Specialist
Check the pellet hopper
•
Clean the fill level sensor
•
Clean the strainer
X
Specialist
Calibrate the lambda probe
X
Specialist