RS 485 Interface 

ET System electronic GmbH 

 

 

17 

Command 

Function 

Command example 

0x00 0x0C ending group number of Gradual-mode loop  
0x00 0xFF loop number  
0x88 CRC Checksum high byte  
0xF9 CRC Checksum low byte  

Answer from unit: 

0x02 0x50 0x01 0x00 0x00 0x1D  

Data collection

 

 

Data collection 

0x30/31 

Send command: 

0x02 address  
0x30 function code  
0x00 command length  
0xc4 CRC Checksum high byte  
0x00 CRC Checksum low byte  

Answer from unit (touch screen): 

0x02 address  
0x31 function code  
0x2C command length  
0x01 current operating loop number  
0x01 current operating group number  
0x08 0x98 current U-phase output voltage (220 V x 10) 
0x08 0x98 current V-phase output voltage (220 V x 100) 
0x08 0x98 current W-phase output voltage (220 V x 10) 
0x01 0xFC current U-phase output current (50 A x 10) 
0x01 0xFC current V-phase output current (50 A x 10) 
0x01 0xFC current W-phase output current (50 A x 10) 
0x13 0x88 current output frequency (50 Hz x 100) 
0x03 0xDE U-phase active power (99 kW x 10) 
0x03 0xDE V-phase active power (99 kW x 10) 
0x03 0xDE W-phase active power (99 kW x 10) 
0x03 0xE8 U-phase Apparent power (100 kVA x 10) 
0x03 0xE8 V-phase Apparent power (100 kVA x 10) 
0x03 0xE8 W-phase Apparent power(100 kVA x 10) 
0x00 0x63 U-phase Power Factor (0,99 x 100) 
0x00 0x63 V-phase Power Factor (0,99 x 100) 
0x00 0x63 W-phase Power Factor (0,99 x 100) 
0x00 0x00 0x00 0x00 current system failure 
0x00 0x00 0x00 0x0A Current execution time

10 second

  

0x00  0x01  Status 

Symbol  zur  Anzeige  der  Vollständigkeit  von  „STEP“

-od. 

„GRADUAL“ Modus: 

0 - unvollständig, 1 - vollständig 

0x02 CRC Checksum high byte 
0x4C CRC Checksum low byte 

Answer from unit (VFD): 

0x02 address  
0x31 function code  
0x1E command length  
0x08 0x98 current U-phase output voltage (220 V x 10) 
0x08 0x98 current V-phase output voltage (220 V x 10) 
0x08 0x98 current W-phase output voltage (220 V x 10) 
0x01 0x98 current U-phase output current

40.8A×10

  

0x01 0x98 current V-phase output current

40.8A×10

  

0x01 0x98 current U-phase output current

40.8A×10

  

0x08 0x98 current R-phase input voltage (220 V x 10)

 

0x08 0x98 current S-phase input voltage (220 V x 10)

 

0x08 0x98 current T-phase input voltage (220 V x 10) 
0x14 0x50 Bus voltage (250 V x 10) 
0x01 0xF4 current output frequency (50 Hz x 10) 
0x00 0x00 reserved for optional feature  
0x00 0x00 0x00 0x00 current system failure  
0x00 0x00 reserved for optional feature  
0x07 CRC Checksum high byte  
0x34 CRC Checksum low byte  

 
 
 
 
 

Summary of Contents for EAC/AFV

Page 1: ...ET System electronic GmbH Telefon 06205 3948 0 Fax 06205 37560 Hauptstra e 119 121 info et system de 68804 Altlu heim www et system de EAC AFV...

Page 2: ...Software version January 2015...

Page 3: ...Block Diagram 5 Structure of the Main Control Unit 6 Description of cable connections 6 Cable Wiring 6 General Settings 7 Initial State Splash Screen 7 Main Menu 7 Application 7 System 7 Event 7 Menu...

Page 4: ......

Page 5: ...c are flexibly carried out by qualified personnel The approval procedures are performed within the scope of development planning and thus do not negatively impact the start of manufacturing Permanent...

Page 6: ...OUTPUT SPECIFICATIONS Number of Phases 3 Wave Form Sine Low Voltage 0 150 V L N High Voltage 150 1 300 V L N Frequency 45 500 Hz Frequency Stability 0 01 Max high voltage current LO 83 3 A Max low vo...

Page 7: ...ystem electronic GmbH 3 TECHNICAL DRAWING 1 Touchscreen 2 AC Output terminal row U V W Nu Nv Nw 3 Emergency stop button 4 Door handle 5 Input air switch 6 Maintenance socket 7 AC input terminal row R...

Page 8: ...ted in case it needs to be transported in the future or claims for compensation need to be asserted SETTING UP To avoid electric shocks and product failure the device should be installed in a temperat...

Page 9: ...to the output terminal disk through the contactor 9 Lightning Protection Device overvoltage protection lightning protection restraining surge current absorbing spike pulse etc 10 Voltage Sampling inp...

Page 10: ...be selected according to the cables recommended in the following tables Input distribution cables Input Current A Input live wire mm Input zero line mm Input ground wire mm A B C 70 8 A 25 mm 25 mm 2...

Page 11: ...and the input switch connected Before the user should ensure that no electrical current is flowing at the input terminal row When switching on the unit the splash screen and the initialization graphi...

Page 12: ...ing the values are the arrow buttons besides the slide control By clicking these buttons the value changes by 0 1 interval Volt Range After clicking the button LOW the unit is on low voltage After cli...

Page 13: ...H 9 Mode Step Download Parameter Starts the download of the adjusted parameters Operation Mode Step is activated after button RUN was clicked and deactivated after button STOP was clicked RESET sets t...

Page 14: ...electronic GmbH The button in the upper right field of the display switches between adjustment function and graphical display of the mode Step Mode Gradual Download Parameter Starts the download of t...

Page 15: ...cked RESET sets the unit back to its initial state The button in the upper right field of the display switches between adjustment function and graphical display of the mode Gradual Mode Meas Operation...

Page 16: ...Main Menu 12 ET System electronic GmbH Error Message Operation A click on the button RESET resets the error meassage Clicking OK switches to the previous display MENU SYSTEM...

Page 17: ...ead but cannot be changed by the user In case that adjustments shall be made please contact our service Language Setting Adjusts the menu language The button Back saves these settings and switches to...

Page 18: ...CTIONS Control 0x00 0x0F Adjustment 0x10 0x1F Adjustment Data Functions 0x20 0x2F Data Enquiry 0x30 0x31 Application parameter 0x16 0x17 Command for standard address 0x02 ANSWER COMMANDS 0 x 02 Addres...

Page 19: ...from unit 0x02 0x50 0x01 0x00 0x00 0x1D Reset 0x03 Send command 0x02 address 0x03 function code 0x00 command length 0xD0 CRC Checksum high byte 0xF0 CRC Checksum low byte Answer from unit 0x02 0x50 0x...

Page 20: ...ge of this group 110 V x 10 0x01 0xF4 output frequency of this group 50 Hz x 10 0x08 0x98 output voltage of this group 220 V x 10 0x02 0x58 output frequency of this group 60 Hz x 10 0x00 0x00 0x00 0x0...

Page 21: ...100 kVA x 10 0x03 0xE8 V phase Apparent power 100 kVA x 10 0x03 0xE8 W phase Apparent power 100 kVA x 10 0x00 0x63 U phase Power Factor 0 99 x 100 0x00 0x63 V phase Power Factor 0 99 x 100 0x00 0x63 W...

Page 22: ...0 0x41 0x00 0xC1 0x81 0x40 static unsigned char auchCRCLo 256 0x00 0xC0 0xC1 0x01 0xC3 0x03 0x02 0xC2 0xC6 0x06 0x07 0xC7 0x05 0xC5 0xC4 0x04 0xCC 0x0C 0x0D 0xCD 0x0F 0xCF 0xCE 0x0E 0x0A 0xCA 0xCB 0x0...

Page 23: ...4 IGBT Phase W is damaged Check and replace IGBT Err 13 Radiator over temperature Fan malfunction Check fan Err 14 Transformer over temperature Fan malfunction Check fan Err 15 Emergency stop button E...

Page 24: ...Notes 20 ET System electronic GmbH NOTES...

Page 25: ...Notes ET System electronic GmbH 21...

Reviews: