OPERATING INSTRUCTIONS

PD-C180i KNX ECO 

EP10426452

PD-C180i KNX ECO DK 

EP10426476

PD-C180i KNX ECO CH 

EP10426490

www.esylux.com

5 /6

BESCHREIBUNG DER APPLIkATION

• Additional manual lighting control in “Fully automatic” mode

The lighting can be switched on or off manually using infrared remote 
control (Mobil-PDi/User, refer also to the separate Mobil-PDi/User 
instructions) or by telegrams, e.g. by pressing external KNX/EIB buttons.
If manual operation when persons are present is set, despite high ambient 
brightness conditions (ambient lighting level is higher than the pre-set light 
value), the artificial light will remain switched on for as long as the detector 
continues to detect movement. If no more movement is detected, the lighting 
is switched off after the set switch-off delay time has elapsed. The lighting 
can be subsequently switched back on manually at any time. If the artificial 
light is switched off manually, the lighting will remain switched off for as 
long as the detector continues to detect movement.
If manual operation during off-period is set, during this time the detector 
behaves in the same way as when set for manual operation when persons 
are present. The detector then switches to normal operating mode. In this 
way, the light can be switched on by the user despite the threshold value 
being exceeded, and then switched off automatically after the set time has 
elapsed.
If no more movement is detected, the detector will revert to the previous 
automatic mode after the set switch-off delay time has elapsed.

  NB: Applies to all light channel operating modes.

• “Semi-automatic” operating mode

If “semi-automatic” mode has been selected, the lighting must be switched 
on manually using infrared remote control (Mobil-PDi/User) or by 
telegrams, e.g. by pressing external KNX/EIB buttons. This means that the 
detector does not automatically switch “ON” the lighting when persons are 
present.
However, should the natural lighting level increase and the ambient lighting 
level exceed the pre-set light value, the detector will automatically switch 
the lighting off 5 minutes after reaching the pre-set light value, regardless of 
any presence.
The lighting can subsequently be switched back on manually at any time.
If manual operation during off-period is set, during this time the detector 
behaves in the same way as when set for manual operation when persons 
are present. The detector then switches to normal operating mode. In this 
way, the light can be switched on by the user despite the threshold value 
being exceeded, and then switched off automatically after the set time has 
elapsed.

  NB: External ON telegram, e.g. via kNX/EIB button, is essential in “semi-

automatic” mode. Applies to all light channel operating modes.

Default setting: Fully automatic

8.3 Switch-off delay time light channel

• Switch-off delay time channel light

Options: 0 seconds, 30 seconds - 30 minutes

Default setting: 5 minutes

8.5 Processing actuator acknowledgement

An actuator’s status object can be processed via objects 9 and 10. If the 
actuator is not only controlled by the detector, the light channel switches to 
standby mode if the status of the channel and actuator differ.

8.6 Sending in cycles

The light channel sends its current status in cycles according to set time 
intervals. At the same time a setting can be made to define whether it 
should repeatedly send ON or OFF telegrams in cycles. 