7. VENTILATION
Purpose provided ventilation of 100cm
2
is required for this heater. This ventilation must never be blocked or
partially blocked. An openable window or equivalent is also required. Ventilation fitted under, or within immedi-
ate vicinity of the heater must not be used as it may adversely effect performance of the combustion monitor-
ing system (ODS) system. The requirements of other appliances operating in the space or room must be
taken into consideration when assessing ventilation requirements, this will have been carried out by your
CORGI registered installer. A supply of fresh air into the room is advisable to maintain temperatures within
limits. The heater MUST NOT be installed in a bedroom, bathroom or any sleeping area. Additionally for
L.P.G. – the heater must not be used in cellars or basements.
8. BURNER ARRANGEMENT
The burner should only be used with vermiculite granules as shown in the Installation Instructions. The heater
must only be fitted with the vermiculite supplied. DO NOT add any extra logs or coals.
9. CONTROL FOR THE HEATER
The heater is fitted with a pilot light which is also an oxygen depletion sensor (ODS), piezo spark and flame
sensing device. The control is located behind the front panel on the lower right hand side (Fig 2). The pilot light
is located at the right hand end of the burner. Should the heater be extinguished for any reason wait 3 minutes
before re-ignition is attempted. The heater should not be used at a lower setting than the ‘LOW’ position.
Fig 5. Side View of Valve
Page 7
Fig 5a
Fig 5b
ON/OFF
Switch