Bench-top type temperature(humidity) chamber
Installation guide
14
ESPEC CORP.
7. Power supply work
Primary power supply requirements
Notice
・
Always take care to comply with your national regulations for power supply
installations. If a drainage pit is not located near the chamber, drain in a container.
・
External power supply cables shall be of approved type and in compliance
with IEC/EN60227 or IEC/EN60245 or any other applicable national regulation.
Prepare the power supply and power cable satisfying the following requirements.
◆
Note
◆
The following table shows the supply voltage ranges for power supply voltage fluctuation
that the chamber can operate in, but keep the range within ±5% as much as possible.
Selection
Power
supply
100V AC 1Ø
2W 50/60Hz
115V AC 1Ø
2W 60Hz
200V AC 1Ø
2W 50/60Hz
220V AC 1Ø
2W 50/60Hz
230V AC 1Ø
2W 50Hz
Power supply
voltage
fluctuation
90V to 110V
103V to 126V 190V to 220V 198V to 242V 219V to 241V
(±10%)
(±10%)
(-5%
、
+10%)
(±10%)
(±5%)
Maximum current per voltage specification, minimum cable diameter and fuse capacity
must be as below. Prepare a power supply that meets with chamber power supply voltage
specifications.
Power supply voltage (V AC) Max. current (A)
Min. power
cable size
(mm
2
)
Fuse capacity
(A)
SH-222,242
100V 50Hz/60Hz 1Ø 2W
11.3 (11.8)
2
15
115V 60Hz 1Ø 2W
12.8 (13.3)
14AWG
15
220V 50Hz/60Hz 1Ø2W
5.4 (5.7)
0.75
10
230V 50Hz 1Ø2W
5.3 (5.6)
0.75
10
SU-222,242
100V 50Hz/60Hz 1Ø 2W
9.3 (9.8)
2
15
115V 60Hz 1Ø2W
11.0 (11.5)
14AWG
15
220V 50Hz/60Hz 1Ø2W
4.5 (4.8)
0.75
10
230V 50Hz 1Ø2W
4.4 (4.7)
0.75
10
SH/SU-262
100V 50Hz/60Hz 1Ø 2W
15.0 (16.0)
2
20
200V 50Hz/60Hz 1Ø 2W
14.0 (14.5)
2
15
220V 50Hz/60Hz 1Ø 2W
13.5 (14.0)
1.5
15
230V 50Hz 1Ø 2W
13.5 (14.0)
1.5
15