20 of 52
V 1.7
PASRW040-D-BP
compressor will start up. Make sure that there are no strange
noises coming from it. If the compressor sounds abnormal,
stop the unit immediately and check the compressor. If the
compressor runs well please check the pressure of the
refrigerant.
Following the above, check whether the power input and
running current being drawn by the unit is in line with this
manual. If not please stop the unit and check for any
problems.
If the unit is supplying a heating manifold, adjust the
actuators on the manifold(s) to balance the heating being
received in all areas of the system.
Check that the outlet water temperature is stable and
increasing smoothly towards the target temperature. The
return water temperature should move in line with the flow
temperature with around a 4 deg C. difference between the
flow and return water temperatures.
The parameters of the unit controller are factory set and you
must not change them without consulting your installer or
ESP. The exceptions to this are the running temperature (or
flow temperature) of the system and the time. Section 10
explains how to view the various parameters although the
default view will show the current status of the system (see
10.1).
Summary of Contents for Varimax I ASHP
Page 1: ...ESP VARIMAX I ASHP Installation and Operation Manual...
Page 22: ...22 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 23: ...23 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 24: ...24 of 52 V 1 7 www esavep com PASRW040 D BP 10 3 Main Menu...
Page 25: ...25 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 26: ...26 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 27: ...27 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 28: ...28 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 29: ...29 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 30: ...30 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 31: ...31 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 32: ...32 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 33: ...33 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 34: ...34 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 35: ...35 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 36: ...36 of 52 V 1 7 www esavep com PASRW040 D BP...
Page 37: ...37 of 52 V 1 7 www esavep com PASRW040 D BP 10 4 Frequency Control...
Page 43: ...43 of 52 V 1 7 www esavep com PASRW040 D BP 13 0 Wiring Diagram...
Page 49: ...49 of 52 V 1 7 www esavep com PASRW040 D BP 17 0 Weather Compensation...
Page 50: ...50 of 52 V 1 7 www esavep com PASRW040 D BP 18 0 Performance 18 Varimax Performance...
Page 51: ...51 of 52 V 1 7 www esavep com PASRW040 D BP 19 Parameter List...