18.0 Parameter List:
Please note that the changing any one of the parameters in this list may:
1.
Be dangerous.
2.
Invalidate the warranty on the unit.
3.
Invalidate the MCS registration (where applicable).
4.
Invalidate any Government grant claimed for the installation.
Parameter
Number
Description
Default
Value
Units
A01
High Pressure protection delay
0
Secs
A01
Low Pressure protection delay
300
Secs
A03
Outlet water antifreeze
5
°C
A04
Return differential antifreeze
2
°C
A05
Exhaust temperature maximum
105
°C
A06
Frequency reduction of exhaust overtemp
10
Hz
A07
Frequency reduction cycle for exhaust overtemp
60
Secs
A08
Return differential of exhaust over temp
25
°C
C01
Compressor on-delay
180
Secs
C02
Compressor off-delay
120
Secs
C04
Minimum compressor frequency
30
Hz
C05
Maximum compressor frequency
90
Hz
D01
Defrost start trigger pressure
5.0
bar
D02
Defrost end trigger pressure
27
bar
D03
Defrost cycle
45
mins
D04
Defrost maximum
8
mins
D05
4-way valve switching delay
55
Secs
D06
Slide defrosting set on
1
(logic)
D07
Slide defrosting trigger temp
2
°C
D08
Ambient temp defrosting trigger
17
°C
D09
Pressure differential for defrost
2.7
bar
E01
Manual mode for EEV set on
0
(logic)
E02
Overtemp protection for EEV (Heating)
1
°C
E03
Overtemp protection for EEV (Cooling)
0.5
°C
E04
Opening of EEV Valve during heating
250
Steps
E05
Opening of EEV Valve during cooling
250
Steps
E06
Opeinging of EEV Valve during defrost
450
Steps
F01
Max fan speed trigger (Cooling)
27
bar
F02
Min fan speed trigger (Cooling)
15
bar
F03
Max fan speed trigger (Heating)
4
bar
F04
Min fan speed trigger (Heating)
3
bar
F05
Air valve voltage min
3
V
F06
Air valve voltage max
10
V
F07
Pressure differential fan trigger (Cooling)
3
bar
F08
Pressure differential fan trigger (Heating)
2
bar
F09
Rated rotate speed
6.5
V
H01
Power-off memory set on
1
(logic)