CAUTION: Before installing make certain the AC power
is off and the LED lamp emergency backup unit connector
is disconnected.

PAGE 2 OF 4

EMERGENCY DRIVER 

INSTRUCTIONS

Installation

 

1. Specification of ESL-EMG-2DC Series

See the ESL-EMG-2DC SERIES SPECIFICATION chart below for the model selected.

 

2. Installing the ESL-EMG-2DC

The ESL-EMG-2DC should be mounted inside the luminaire and is a factory install only.

 

3. Installing the LED Test Switch

Select a convenient location for the LED Test Switch so that it can be seen after installation. Drill a 1/2" hole for
mounting. Connect the wires from the LED Test Switch to the ESL-EMG-2DC model according to the wiring
diagram on page 3.

ESL-EMG-2DC-5W

ESL-EMG-2DC-9W

ESL-EMG-2DC-15W

ESL-EMG-2DC-25W

MODEL

5 WATTS

9 WATTS

15 WATTS

25 WATTS

13-60 VDC

14-60 VDC

15-60 VDC

25-60 VDC

VOLTAGE OUTPUT

EMERGENCY OUTPUT (CONSTANT)

VOLTAGE OUTPUT

INSIDE THE LUMINAIRE

E

S

L-

EM

G-2

D

C

LED TEST SWITCH

MOUNTING HOLE - Ø0.47"

0.24"

0.98"

10.04"

This product contains a rechargeable nickel-metal hydride battery.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF
PROPERLY TO PREVENT FIRE.

Copyright © 2018 ESL Vision, LLC. All rights reserved. Rev: 08/15/2018

Summary of Contents for ESL-EMG-2DC Series

Page 1: ...ion when under the emergency mode 6 The ESL EMG 2DC are UL Component Recognized for factory installation 7 This product is suitable for use in dry or damp locations Do not mount it near gas heaters air outlets or other hazardous locations 8 Use this product in 32 F minimum to 122 F maximum ambient temperatures 9 The use of accessory equipment not recommended by the manufacturer may cause an unsafe...

Page 2: ...ED Test Switch so that it can be seen after installation Drill a 1 2 hole for mounting Connect the wires from the LED Test Switch to the ESL EMG 2DC model according to the wiring diagram on page 3 ESL EMG 2DC 5W ESL EMG 2DC 9W ESL EMG 2DC 15W ESL EMG 2DC 25W MODEL 5 WATTS 9 WATTS 15 WATTS 25 WATTS 13 60 VDC 14 60 VDC 15 60 VDC 25 60 VDC VOLTAGE OUTPUT EMERGENCY OUTPUT CONSTANT VOLTAGE OUTPUT INSID...

Page 3: ...D D R I V E R SELV BATTERY OUTPUT TO LED FROM LED DRIVER BATTERY RED BLACK RED WHITE LED TEST SWITCH N L DRIVER SWITCHED SWITCH HOT L EMERGENCY UNSWITCHED ESL EMG 2DC Terminal block with external battery pack choosing the different combination of the DIP switches and the corresponding battery pack to have different ESL EMG 2DC models with different emergency power outputs BATTERY MOUNTING BOX OPTI...

Page 4: ...est switch should switch off and LED loads should operate at reduced illumination 2 Preprogrammed scheduled Auto Test A Carry out first monthly auto test after initial power on for at least a full 24 hours or more Afterwards carryout a monthly auto test every 30 days B Carry out a annual auto test every 52 weeks after first power on C Auto test timing To reduce the conflict that auto test is execu...

Reviews: