Wiring

1.

The ESL-EMG-2DC requires an unswitched AC power supply of 120-277 VAC, 50/60Hz.

2.

The ESL-EMG-2DC and AC driver must be on the same branch circuit. Ensure the output current of the AC
driver does not exceed 5A.

3.

Refer to the wiring diagram below or contact factory for additional information or help.

Wiring Configuration

++

LED DRIVER

LED

-

N

L

LED LOAD

LED (+)

LED (

-

)

N

LL
SW LIVE IN

SW LIVE OUT

+ RED

-

 WHITE

ON

ESL-EMG-2DC

E M E R G E N C Y

L E D   D R I V E R

SELV

BATTERY

OUTPUT
TO LED

FROM LED
DRIVER

+

-

+

-

+

-

BATTERY

+ RED

-

 BLACK

RED (+)

WHITE (

-

)

LED TEST SWITCH

N

L DRIVER (SWITCHED)

SWITCH

HOT

L EMERGENCY (UNSWITCHED)

ESL-EMG-2DC

Terminal block with external battery pack, choosing the different combination of the DIP switches and the 

corresponding battery pack to have different ESL-EMG-2DC models with different emergency power outputs.

BATTERY MOUNTING BOX (OPTIONAL)*

*Contact factory for information

ON

OFF

1

OFF

ON

OFF

ON

OFF

OFF

ON

ON

5W

9W

15W

25W

9.6V, 1.5AH

10.8V, 2.1AH

10.8V, 3.8AH

14.4V, 4.5AH

ESL-EMG-2DC-5W

ESL-EMG-2DC-9W

ESL-EMG-2DC-15W

ESL-EMG-2DC-25W

2

MODEL

POWER

BATTERY

Copyright © 2018 ESL Vision, LLC. All rights reserved. Rev: 08/15/2018

Summary of Contents for ESL-EMG-2DC Series

Page 1: ...ion when under the emergency mode 6 The ESL EMG 2DC are UL Component Recognized for factory installation 7 This product is suitable for use in dry or damp locations Do not mount it near gas heaters air outlets or other hazardous locations 8 Use this product in 32 F minimum to 122 F maximum ambient temperatures 9 The use of accessory equipment not recommended by the manufacturer may cause an unsafe...

Page 2: ...ED Test Switch so that it can be seen after installation Drill a 1 2 hole for mounting Connect the wires from the LED Test Switch to the ESL EMG 2DC model according to the wiring diagram on page 3 ESL EMG 2DC 5W ESL EMG 2DC 9W ESL EMG 2DC 15W ESL EMG 2DC 25W MODEL 5 WATTS 9 WATTS 15 WATTS 25 WATTS 13 60 VDC 14 60 VDC 15 60 VDC 25 60 VDC VOLTAGE OUTPUT EMERGENCY OUTPUT CONSTANT VOLTAGE OUTPUT INSID...

Page 3: ...D D R I V E R SELV BATTERY OUTPUT TO LED FROM LED DRIVER BATTERY RED BLACK RED WHITE LED TEST SWITCH N L DRIVER SWITCHED SWITCH HOT L EMERGENCY UNSWITCHED ESL EMG 2DC Terminal block with external battery pack choosing the different combination of the DIP switches and the corresponding battery pack to have different ESL EMG 2DC models with different emergency power outputs BATTERY MOUNTING BOX OPTI...

Page 4: ...est switch should switch off and LED loads should operate at reduced illumination 2 Preprogrammed scheduled Auto Test A Carry out first monthly auto test after initial power on for at least a full 24 hours or more Afterwards carryout a monthly auto test every 30 days B Carry out a annual auto test every 52 weeks after first power on C Auto test timing To reduce the conflict that auto test is execu...

Reviews: